5.0 – Tools Required
The following tools are required for installation:
•
Flat blade screwdrivers
•
Pozi head screwdrivers
•
10mm spanner
•
Adjustable spanner
6.0 – Installation
The air curtain is designed to be recessed within ceiling voids or bulkheads within a building and located horizontally
over a doorway. It must not be installed outside of the building.
6.1 – Location
Mount the air curtain above and as close to the doorway as possible
with:
•
The recessed grille not more than 3m above floor level
•
The air discharge (see 1, Fig 1) section of the recessed grille
nearest the doorway and the air inlet section (see 2, Fig 1)
furthest from the doorway.
•
Beware of doorway top edges, structural beams, door
opening/closure devices etc. which may interfere with the air
stream and affect the location of the unit.
NOTE: For the air curtain to work well, the doorway should be less than the width of the airstream.