SX:NETLINK handles up to 6 simultaneous SIOX bus (communication and power) should normally Net and 6 Modbus TCP/IP connections. use terminal 4 (SIOX bus), terminal 5 (power) and terminal 6 (ground). However, use of terminal 5 4 INSTALLATION AND STARTUP for power to the modules is optional.
Error SIOX bus shorted SIOX Turned OFF Error High level detected PWR + SIOX Double blink on both LEDs on SIOX bus (possibly shorted to positive supply) Error 50/60Hz detected on PWR + SIOX Fast blink on both LEDs SIOX bus...
1 - 63 depending on earlier the address in the Server Address field (seen by pressing F6 to enter SIOX Bus setup). Also check/ configuration. This address cannot be used by change the Station Address field to correspond with other SIOX modules.
SIOX tab SIOX bus is connected to the SX:NETLINK. To summarize the steps involved to get in contact ES3 address (1 - 63) on the SIOX bus for with the unit: its virtual SIOX module, thru which these 1. Connect the SX:NETLINK by Ethernet, either to configurations are carried out.
1 - 62. The SX:NETLINK occupies one address parameter no. 1 and so on. Please refer to the itself, typically address 63 (factory default). By specific SIOX module manual to find out where the using Group Addressing even more modules actual I/O bits are located.
SIOX SIOX Addressing modules connected to the SIOX bus but also The address of the SIOX module that a Modbus with Modbus RTU slave units connected to message wants to access has to be stored in...
04 Read Input Registers (returns same data as RTU devices should have addresses assigned Read holding Registers) to them that are greater than this number. SIOX 05 Write Single Coil devices should have addresses lower or equal 06 Write Single Register to this number.
(SIOX and RTU). This ’ Only this bit is relevant. will prevent ground loops which otherwise may This bit is used for other purposes.
Page 10
If so, document the change for of the wire capacitance which may necessitate a future reference to make it easy to get in contact change to a lower baud rate. Secondly, fewer SIOX with the module. It will be reset to 1024 by doing modules can be connected to the bus.
Page 11
Default Bit pattern Description 0000 tttt tttt tt” ‘”’ 00-3F = Additional SIOX timeout 0 ms to 63 ms. Leave at zero for normal conditions. However, if there are special SIOX modules connected to the bus, i.e. modems or radio modules, extra timeout may be added to compensate for the delay in these units.
Page 12
= Last modbus slave address assigned for SIOX. Addresses above this number are on Modbus RTU and addresses less than or equal are on SIOX. A value of 0 or greater than 247 will set it to 255. That means all addresses can be used by the SIOX bus.
10 ELECTRICAL SPECIFICATIONS Tamb = 20 °C Min Typ Max Unit Power supply voltage Power Supply Current (@24 VDC) Idle, no SIOX communication Normal operation SIOX bus shorted 11 ENVIRONMENTAL SPECIFICATIONS Min Typ Max Unit Operating Temperature Range 0 +55 °C Storage Temperature Range -20 +70 °C...