Industrial pressure transducers

Advertisement

Quick Links

E Model
®
Introduction
®
Swagelok
industrial pressure transducers allow for elec-
tronic monitoring of system pressures in a variety of indus-
trial applications. The E model transducer is specifically
designed to meet durability and performance demands of
industrial applications where explosion-proof ratings are
required.
Contents
I
General Information and Ratings . . . . . . . . . . . . . . 1
I
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . 1
I
Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . 1
I
Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . 2
I
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
I
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
General information and Ratings
FM Approval Ratings
Explosion-proof
for Class I, Division 1, Groups A, B, C, D
Dust-ignition proof
for Class II and III, Division 1, Groups E, F, G
FM standards according to
FMRC 3600, 3615, and 3810
CSA Approval
CSA Standards according to CSA 25-1966, 30-M1986,
94-M91, and 142-M1987
MS-CRD-PTI-E
Rev 0
3-04-WEL
Industrial Pressure Transducers
Safety Instructions
!
For proper and safe operation, Swagelok E model
transducers must be installed, operated, and
serviced according to NEC, applicable local
regulations, and these instructions. Otherwise,
serious personal injuries, damage or both can
occur.
!
Except for adjusting the length of the wires, the
electrical connection provided on the transducer
must be used as originally supplied and not
bypassed. Only qualified persons should work on
theses instruments.
!
The shield / ground connection must be wired to
ground to protect the instrument from electromag-
netic disturbances.
!
Do not exceed the overpressure rating.
Safe Product Use
Follow any enclosed instructions and refer to the product
catalog for detailed product information. When using a
transducer, the total system design must be considered to
ensure safe, trouble-free performance. Function, material
compatibility, adequate ratings, proper installation, oper-
ation, and maintenance are the responsibilities of the
system designer and user.
Mechanical Installation
Using the appropriate mating process connection, install the
transducer away from excessive heat and vibration whenev-
er possible. Be sure to install the system in accordance with
NEC requirements.
User's Manual
E Model
Use this hex only to
secure transducer while
installing electrical
conduit.
Use this hex to install
the transducer process
connection
50 N • m (36 ft • lb) max
www.swagelok.com

Advertisement

loading
Need help?

Need help?

Do you have a question about the E and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Swagelok E

  • Page 1 Explosion-proof conduit. for Class I, Division 1, Groups A, B, C, D Dust-ignition proof for Class II and III, Division 1, Groups E, F, G FM standards according to FMRC 3600, 3615, and 3810 Use this hex to install the transducer process...
  • Page 2 Use yellow/green wire or braided conductor for shield/ground connection. Hazardous (Classified) Location Nonhazardous Location Class I, Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F, G Class III 0 V dc/S– (Note 1) Control Equipment...
  • Page 3 0 V dc /S– black Signal– Signal+ brown Hazardous (Classified) Location Nonhazardous Location Class I, Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F, G Class III (Note 1) Control Equipment Pressure V dc– Transducer V dc+...
  • Page 4 Maintenance Caution: Swagelok E model pressure transducers are tested Do not attempt to clear the pressure port with a and calibrated at the factory. There are no user service- screwdriver or other sharp objects as this may able components inside the case. DO NOT ATTEMPT damage the sensing element of the transducer.