8. Install the Battery Cover, and secure it
with the two thumb screws.
9. Reconnect the front cover by aligning
the bottom grove first, and rotating
the cover upward. Gently apply
pressure to secure the cover.
10. Affix the "Replace By" label to the UPS.
If MopUPS software is being used with this UPM, please see the below steps to update the "Date
Last Replaced" field.
1. Open MopUPS software
2. Select "UPS" from the top of the screen
3. Select "Configure UPS"
4. Under the "Battery" tab, change the "Date Last Replaced" to today's date.
5. Select "Apply to UPS" on the right-hand menu.
VS009
April 4, 2018
Issue 2