  • Page 1 PSU EN54-4 Power Supplies www.advancedco.com...
  • Page 2 Ordering: Models, Sales Order Parts: SPARES: MXP-549 1.5A PSE in 7Ah enclosure Mxs-049 1.5A Caged Unit only MXP-550 3.0A PSE in 17/18Ah enclosure Mxs-050 3.0A Caged Unit only MXP-550D 3.0A PSE in 25Ah enclosure Mxs-051 5.0A Caged Unit only MXP-551 5.0A PSE in 17/18Ah enclosure (Supplied with AC lead and terminal block) MXP-551D...
  • Page 3 Specifications: Item Specification Details Approvals All Power Supply Units comply with the requirements of EN54-4:1997 +A1:2002 +A2:2006, EN55022 class B emissions limits & EN60950-1:2006 safety standards. 1.5A PSE 220-240V AC, 50/60Hz, Fuse T3.15H250 Input Supply 3.0A/5.0A PSE : 200-240V AC, 50/60Hz, Fuse T3.15H250 Output Voltage Max 28.5V DC, Min 19.7V DC at minimum battery voltage of 21V with mains disconnected (Output...
  • Page 4: Table Of Contents

    ATTERIES 1 Introduction The Advanced 1.5A, 3.0A and 5.0A Power Supply Units can be used for any fire alarm system installation that specifies EN54-4 Power Supply Equipment. Suited for almost any application (except for CIE in separate cabinet), the power supply unit/battery charger has been developed using the latest surface mount technology to provide a high efficiency switch mode power supply.
  • Page 5: En54 Functions

    (transmission path) circuits such that a short or open circuit in one circuit does not prevent supply of power to the CIE. Advanced Electronics Ltd does not warrant that the equipment continues to satisfy the requirements for compliance with the EMC Emissions Directive, Low Voltage Directive or EN54-4 when caged units are mounted in a customer’s own enclosure.
  • Page 6: Mounting Instructions

    17Ah / 38Ah Enclosure Advanced Electronics Ltd does not warrant that the equipment continues to satisfy the requirements for compliance with the EMC Emissions Directive and Low Voltage Directive when equipment, other than that manufactured by Advanced Electronics Ltd and installed in accordance with the supplied documentation, is mounted in the enclosure.
  • Page 7: Mxp-549, Mxp-550, Mxp-551

    3.1.2 Mxp-549, Mxp-550, Mxp-551 The Mxp-549, Mxp-550 and Mxp-551 are power supplies mounted within an IP30 steel enclosure. These can accommodate 7Ah, 18Ah up to 38Ah capacity batteries depending on enclosure size (refer to specifications page). When batteries are installed, the Mxp-551 can weigh in excess of 16Kg.
  • Page 8: Mounting Batteries

    MXP-550/D & MXP-551/D 3.1.2.2 Mounting batteries MXP-549 MXP-550 & MXP-551 MXP-550/D & MXP-551/D 24Ah / 38Ah 24Ah / 38Ah 3.1.3 Mxs-049, Mxs-050, Mxs-051 PSE Modules The PSE modules can be installed in Mx-5000 Rack and other Utility enclosures. Refer to the relevant product manuals for further information. The dimensions and fixing points are shown below.
  • Page 9: Wiring Installation

    3.2 Wiring Installation 3.2.1 AC Mains Wiring The power supply is classified as Class1 equipment construction and must be earthed in accordance to PSU Internal Mains Field Connections EN60950 recommendations. Wiring FUSE Brown Route the high voltage mains AC wiring into the LIVE enclosure using a suitable knockout and keeping the AC Grn/Yel...
  • Page 10: Output Connections

    3.2.2 Output Connections: 3.2.2.1 To Load: Connect the 28V output connections to the load via terminals Remote Temp VO+ & VO– respectively via appropriately rated cable for the Sensor output rating: Jumper Link for local temperature sensor For 3.0A/5.0A PSE a minimum 0.75 mm² Serial Link For 1.5A PSE a minimum of 0.22mm²...
  • Page 11: Remote Led Indication

    3.2.2.4 Remote LED indication: A pin header, J1, provides a means for remote/ external On-board Indicators indication of “Power” and “Fault” indications. The following indicators on the printed circuit card The Mxp-049, Mxp-050 & Mxp-051 models are supplied give further diagnostic information. fitted with separate Green and Amber LED Indicators.
  • Page 12: Remote Temperature Sensor

    3.2.2.7 Remote Temperature Sensor Provision is made on the 3.0A and 5.0A PSE models for the connection of a remote battery Remote Temp temperature sensor (Mxp-501). This is for Sensor Jumper Link for local applications where the modules are installed in temperature sensor rack mount enclosures or in large enclosures and Serial Link...
  • Page 13: Commissioning

    4 Commissioning: When all connections in the Installation section have been made and checked for correct wiring, switch on the mains power supply; the following conditions should occur: The green “Power” LED should be ON, the “Fault” LED should be OFF. The load should be supplied with power, check this with a voltmeter at the –VO &...
  • Page 14: Maintenance

    5 Maintenance: Maintenance of the power supply and charger should be minimal. The batteries, however, do have a limited life span and a maintenance program should be in place to determine battery replacement schedules. It is recommended that the charger output should be checked on a yearly basis to ensure the charging characteristics have not drifted.