Description The LED area of the Cala KNX IL LED light signal can illuminate or flash in the col- ours green, yellow or red. This allows states to be visualised for the KNX bus system.
The programming button can be reached through the opening on the rear of the hous- ing; it is recessed. Use a thin object to reach the button, e.g. a 1.5 mm² wire. Cala KNX IL light signal • Version: 04.04.2023 • Technical changes and errors excepted.
Light signal status colour yellow R-CT- [1.1] DPT_Switch 1 Bit signal On/Off Output light Light signal status colour green R-CT- [1.1] DPT_Switch 1 Bit signal On/Off Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
Page 11
AND logic 3: 1 bit switching out- R-CT- [1.2] DPT_Bool 1 Bit Logic 166 Output AND AND logic 3: 8 bit output A R-CT- depending on 1 Byte Logic setting Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
Page 12
OR logic 4: 8 bit output B R-CT- depending on 1 Byte Logic setting 188 Input OR Logic OR logic 4: Block -WC-- [1.1] DPT_Switch 1 Bit Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
Off • On valid until the first communication Set the brightness of the light signal after a reset. Brightness 0…100 % valid until the first communication Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
Page 14
1 x scenario object: Set the scenario numbers. In case of pre-set values, Cala KNX IL does not light up at all for scenario number 1, lights up green for scenario number 2, yellow for 3 and red for 4.
Page 15
Set the limit value for colour change from green to yellow. You can specify the thresh- old value via communication object no. 25 (light signal TV green/yellow) also. Start limit value for change from green to -6700000…6700000; 200 yellow [x 0.1] Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
Page 16
Set the display behaviour of the red light signal. If the signal colour Red is active, the light • be permanently On signal should be • be permanently Off • flashing Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
Page 17
= red Value for ‘Status colour RGB’ object in sta- #000000 ...#FFFFFF tus = Off (only for 3 x one-bit object and 1 x scenario object) Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
During initial commissioning, a threshold value must be defined which will be valid un- til the first call with a new threshold value. For units which have already been taken into Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
Page 21
The behaviour of the switching output during blocking can be set. Switching output behaviour On blocking • Do not send message • send 0 • send 1 Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
• 1 = Block | 0 = release • 0 = block | 1 = release Specify an object value until first communication. Blocking object value 0 • 1 before the first communication Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
Page 23
During initial commissioning, a set point value must be defined which will be valid un- til the first Communication of a new setpoint value. For units which have already been Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
Page 24
You should set the time appropriate to the ventilation system (follow the manufactur- er's instructions). Reset time in minutes 1...255; 30 Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
The block can take effect at value 0 or 1, depending on the intended use. Assessment of the block object • at value 1: block | at value 0: release • at value 0: block | at value 1: release Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
AND Logic 1 / 2 / 3 / 4 not active • active OR logic OR Logic 1 / 2 / 3 / 4 not active • active Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
0 … 255 / 100% / 360° / 127; 0 monitoring time exceeded Output value object B if 0 … 255 / 100% / 360° / 127; 0 monitoring time exceeded Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.
Page 28
The behaviour of the output on release can be set. on release • Do not send message (with 2 second release delay) • transmit value for current logic status Cala KNX IL light signal • Status: 04.04.2023 • Technical changes reserved. Errors reserved.