IMPACT MONO Type CONTENTS Part 1 General Information ................3 Part 2 Engineering Data ................17 Part 3 Installation and Field Settings ............61...
Page 15
IMPACT MONO type Modularity is perfect when an extension of capacity becomes required as the building cooling/heating demand evolves. 6 units can be controlled in group. The group control system can control and view the operation of the entire system only by connecting the master to the wire controller.
IMPACT MONO type 1 Specifications Outdoor unit model name AHPM-V6W/D2N8-B*** AHPM -V8W/D2N8-B *** AHPM-V10W/D2N8-B*** AHPM -V4W/D2N8-B*** Power supply V/Ph/Hz 220-240/1/50 Capacity 4.20 6.35 8.40 10.0 Heating A7W35 Rated input 0.82 1.28 1.63 2.02 5.10 4.95 5.15 4.95 Capacity 4.30 6.30 8.10 10.0 Heating A7W45...
Page 20
IMPACT MONO Type -25 43 Water side heat exchanger Plate type Water side connection R1 " R1 " R5/4" R5/4" Cooling 5 25 Water setting Heating 25 65 temperature range 30 60 Notes: Relevant EU standards and legislation: EN14511; EN14825; EN50564; EN12102; (EU) No 811/2013; (EU) No 813/2013; OJ 2014/C 207/02. Sound power test condition EN12102-1 Maximum domestic hot water temperature 60 is only available with TBH support.
Page 21
IMPACT MONO type Outdoor unit model name -V16W/D2N8-B*** -V14W/D2N8-B*** -V12W/D2N8-B*** AHPM AHPM AHPM Power supply V/Ph/Hz 220-240/1/50 Capacity 12.1 14.5 15.9 Heating A7W35 Rated input 2.44 3.15 3.53 4.95 4.60 4.50 Capacity 12.3 14.1 16.0 Heating A7W45 Rated input 3.32 3.92 4.57 3.70...
Page 22
IMPACT MONO Type Water side heat exchanger Plate type Water side connection R5/4" 5 25 Cooling Water setting temperature range 25 65 Heating 30 60 Notes: Relevant EU standards and legislation: EN14511; EN14825; EN50564; EN12102; (EU) No 811/2013; (EU) No 813/2013; OJ 2014/C 207/02. Sound power test condition EN12102-1 Maximum domestic hot water temperature 60 is only available with TBH support.
Page 23
IMPACT MONO type Outdoor unit model name -V12W/D2RN8-B**** -V14W/D2RN8-B**** -V16W/D2RN8-B**** AHPM AHPM AHPM Power supply V/Ph/Hz 380-415/3/50 Capacity 12.1 14.5 15.9 Heating A7W35 Rated input 2.44 3.15 3.53 4.95 4.60 4.50 Capacity 12.3 14.1 16.0 Heating A7W45 Rated input 3.32 3.92 4.57 3.70...
Page 24
IMPACT MONO Type Water side heat exchanger Plate type Water side connection R5/4" 5 25 Cooling Water setting temperature range 25 65 Heating 30 60 Notes: Relevant EU standards and legislation: EN14511; EN14825; EN50564; EN12102; (EU) No 811/2013; (EU) No 813/2013; OJ 2014/C 207/02. Sound power test condition EN12102-1 Maximum domestic hot water temperature 60 is only available with TBH support.
IMPACT MONO type 2 Dimensions and Center of Gravity -V4W/D2N8-BE30 / -V6W/D2N8-BE30 AHPM AHPM Figure 2-2.1: dimensions and center of gravity AHPMS-V4(6)W/D2N8-BE30 (unit: mm) unit mm Model 4/6kW...
Page 26
IMPACT MONO Type -V8W/D2N8-BE30 / -V10W/D2N8-BE30 AHPM AHPM -V12W/D2N8-B / -V14W/D2N8-B / -V16W/D2N8-B AHPM AHPM AHPM -V12W/D2RN8-BER90 / -V14W/D2RN8-BER90 / -V16W/D2RN8-BER90 AHPM AHPM AHPM Figure 2-2.2: -V8(10, 12, 14,16)W/D2(R)N8 dimensions and center of gravity (unit: mm) AHPM unit mm Model 8/10kW 12-16kW 1Ph 12-16kW 3Ph...
Page 35
IMPACT MONO type Combination system diagram Figure 2-4.4 Combination system diagram for single phase 4~16kW models...
Page 36
IMPACT MONO Type Figure 2-4.5 Combination system diagram for three phase 12~16kW models Notes: 1. Aircon recommends 6 units to be controlled by one controller and installed by reversed return water system for better hydraulic equilibrium. 2. In order to ensure the success of automatic addressing, all machines must be connected to the same power supply and powered on uniformly.
Page 37
IMPACT MONO type Circular wiring : Copper wire terminal Insulation tube Proper power wiring connections Power cord 9. Power Cord Connection of group control system Use a dedicated power supply for the indoor unit that is different from the power supply for the outdoor unit. Use the same power supply, circuit breaker and leakage protective device for the indoor units connected to the same outdoor unit.
Page 55
IMPACT MONO type 8.2 Octave Band Levels Figure 2-8.2: -V4W/D2N8-B*** octave band AHPM levels Cooling in rated frequency Outdoor air temperature 35 C DB; EWT 12 C, LWT 7 C Cooling in rated frequency NR-90 Outdoor air temperature 35 C NR-80 DB;...
Page 56
IMPACT MONO Type Figure 2-8.4: -V8W/D2N8-B*** octave band levels AHPM Cooling in rated frequency Outdoor air temperature 35 C DB; EWT 12 C, LWT 7 C NR-90 Cooling in rated frequency NR-80 Outdoor air temperature 35 C NR-70 DB; EWT , LWT NR-60 NR-50...
Page 57
IMPACT MONO type Figure 2-8.6: -V12W/D2N8-B*** octave band levels AHPM Cooling in rated frequency Outdoor air temperature 35 C DB; EWT 12 C, LWT 7 C NR-90 Cooling in rated frequency NR-80 Outdoor air temperature 35 C DB; NR-70 , LWT NR-60 Heating in rated frequency NR-50...
Page 58
IMPACT MONO Type Figure 2-8.8: -V16W/D2N8-B*** octave band levels AHPM Cooling in rated frequency Outdoor air temperature 35 C DB; EWT 12 C, LWT 7 C NR-90 Cooling in rated frequency NR-80 Outdoor air temperature 35 C NR-70 DB; EWT , LWT NR-60 Heating in rated frequency...
Page 59
IMPACT MONO type Figure 2-8.10: -V14W/D2RN8-B**** octave band levels AHPM Cooling in rated frequency Outdoor air temperature 35 C DB; EWT 12 C, LWT 7 C NR-90 Cooling in rated frequency NR-80 Outdoor air temperature 35 C NR-70 DB; EWT , LWT NR-60 Heating in rated frequency...
IMPACT MONO Type 9 Accessories 9.1 Standard accessories Table 2-9.1: Standard accessories Name Shape Quantity Name Shape Quantity Tighten belt for customer wiring use Operation manual Tighten belt for customer wiring use Thermistor for domestic hot water tank Technical data manual or zone 2 water flow or balance tank Y-shaped filter Network matching wires...
Page 62
IMPACT MONO Type ..................................................................................................................................................................................
Page 63
IMPACT MONO type MDV IMPACT Mono project. Notes for installers boxes contain important information which may primarily be of use during field installation, rather than during desk-based system design.
Page 64
IMPACT MONO Type When units are delivered check whether any damage occurred during shipment. If there is damage to the surface or outside of a unit, submit a written report to the shipping company. Check that the model, specifications and quantity of the units delivered are as ordered. Check that all accessories ordered have been included.
Page 65
IMPACT MONO type Outdoor units should not be exposed to direct radiation from a high-temperature heat source. Outdoor units should not be installed in positions where dust or dirt may affect heat exchangers. Outdoor units should not be installed in locations where exposure to oil or to corrosive or harmful gases, such as acidic or alkaline gases, may occur.
Page 66
IMPACT MONO Type In cold climate locations installation Never install the unit at a site where the suction side may be exposed directly to wind. To prevent exposure to wind, install a baffle plate on the air discharge side of the unit. To prevent exposure to wind, install the unit with its suction side facing the wall.
Page 67
IMPACT MONO type Drainage ditch should be provided to allow drainage of condensate that may form on the air side heat exchanger when the unit is running in heating mode or domestic hot water mode. The drainage should ensure that condensate is directed away from roadways and footpaths, especially in locations where the climate is such that condensate may freeze.
Page 68
IMPACT MONO Type 1.1.2 Model A(mm) B1(mm) B2(mm) C(mm) 4-6KW 1500 8-16KW 2000 1000 Model A(mm) B1(mm) B2(mm) C(mm) 4-6KW 2500 1000 8-16KW 3000 1500 2.10...
Page 69
IMPACT MONO type Impact Impact Mono units The maximum water pressure 3 bar. The maximum water temperature 70 according to safety device setting. Always use materials that are compatible with the water used in the system and with the materials used in the unit. Ensure that components installed in the field piping can withstand the water pressure and temperature.
Page 70
IMPACT MONO Type Water connections must be made correctly in accordance with the labels on the outdoor unit, with respect to the water inlet and water outlet. If air, moisture or dust gets in the water circuit, problems may occur. Therefore, always take into account the following when connecting the water circuit: Use clean pipes only.
Page 72
IMPACT MONO Type Caution All installation and wiring must be carried out by and in accordance with all applicable legislation. Electrical systems should be grounded in accordance with all applicable legislation. Overcurrent circuit breakers and residual-current circuit breakers (ground fault circuit interrupters) should be used in accordance with all applicable legislation.
Page 73
IMPACT MONO type Make sure no external pressure is applied to the terminal connectors. When installing the ground fault circuit interrupter make sure that it is compatible with the inverter (resistant to high frequency electrical noise) to avoid unnecessary opening of the ground fault circuit interrupter This unit is equipped with an inverter.
Page 77
IMPACT MONO type he Impact Mono's settings and parameters should be configured by the installer to suit the installation configuration, climate conditions and end-user preferences. The relevant settings are accessible and programmable through the FOR SERVICEMAN menu on the Impact Mono's user interface.
Page 88
IMPACT MONO Type 7.11 7.12 9 SERVICE CALL SETTING PHONE NO. 0000000000000 MOBILE NO. 0000000000000 CONFIRM ADJUST 7.13 10 RESTORE FACTORY SETTINGS 10 RESTORE FACTORY SETTINGS All the settings will come back to factory default. Do you want to restore factory settings? CONFIRM...
Page 89
IMPACT MONO type 7.14 7.14.1 11 TEST RUN Do you want to turn off the test run (AIR PURGE)function? CONFIRM 7.14.2...
Page 90
IMPACT MONO Type 7.14.3 7.14.4 11 TEST RUN Test run is on. Circulation pump is on. CONFIRM 7.14.5 11 TEST RUN Test run is on. Cool mode is on. Leaving water temperature is 15°C. Impact CONFIRM...
Page 91
IMPACT MONO type 7.14.6 Impact Mono systems 7.14.7 11 TEST RUN Test run is on. DHW mode is on. Water flow temper. is 45°C Water tank temper. is 30°C CONFIRM...
Page 92
IMPACT MONO Type 7.15 7.15.1 7.15.2 12.1 PREHEATING FOR FLOOR 30°C t_fristFH 72 HOURS ENTER EXIT ADJUST...
Page 93
IMPACT MONO type 7.15.3 increase from a starting point of 25 Phase 2: maintain peak temperature Phase 3: gradual temperature decrease from the peak temperature to 45 12.2 FLOOR DRYING UP START DAY 01-01-2019 ENTER EXIT ADJUST...
Page 102
IMPACT MONO Type 10.1 USB FUNCTION USB FUNCTION READ SET PARAMETER READ SET PARAMETER WRITE SET PARAMETER WRITE SET PARAMETER SUCCESS Aircon USB FUNCTION USB FUNCTION READ SET PARAMETER READ SET PARAMETER WRITE SET PARAMETER WRITE SET PARAMETER SUCCESS...
Page 103
IMPACT MONO type 10.2 USB FUNCTION USB FUNCTION READ SET PARAMETER READ SET PARAMETER WRITE SET PARAMETER WRITE SET PARAMETER PD25319B84M200415V24.bin PD25319B84M200415V24.bin PD25319B86M200421V35.bin PD25319B86M200421V35.bin SUCCESS OPERATION PARAMETER OPERATION PARAMETER Tbt1 BUFFERTANK_UP TEMP. T3 OUTDOOR EXCHANGE TEMP. Tbt2 BUFFERTANK_LOW TEMP. T4 OUTDOOR AIR TEMP Tsolar TF MODULE TEMP.
Page 107
IMPACT MONO type Water flow failure (E8 appears 3 times) Phase sequence error (for 3 phase models) Communication error between the main control board of hydraulic module and user interface Backup electric heater exchanger water outlet temperature sensor T1 error Domestic hot water tank temperature sensor T5 error Air side heat exchanger refrigerant outlet temperature sensor T3 error Outdoor ambient temperature sensor T4 error...
Page 108
IMPACT MONO Type DC bus high voltage protection MCE error Zero speed protection Phase sequence error Compressor frequency variation greater than 15Hz within one second protection Actual compressor frequency differs from target frequency by more than 15Hz protection Water side heat exchanger anti-freeze protection High temperature protection of refrigerant outlet temperature of condenser in cooling mode Water side heat exchanger inlet temperature is higher than outlet temperature in heating/DHW mode PED board error...