LEDone LOD-EXTED Series Instructions

Emergency driver

Advertisement

Quick Links

AC OPERATION
AC power is present. The AC driver operates
the LED load (the LED load must be less than
100W) as designed. The emergency pack is
charging in a standby mode. The test button
will be lit showing that the battery is
charging.
EMERGENCY OPERATION
When the AC power goes out, the emergency
pack detects the power outage and
automatically switches to the emergency
mode. The LED load is illuminated for a
minimum of 90 minutes. When the AC power
is restored, the emergency pack switches
back to normal mode and starts to recharge.
MODEL NUMBER
LOD-EXTED-M20W
120-277Vac, 50/60Hz
TESTING
NFPA 101 Life Safety Code Schedule
INPUT VOLTAGE
INPUT CURRENT
100mA max.
Phone:
(844) LEDONE6 |
Fax:
Date: _______________ Location: _____________________________________
Product: ___________________Project: ________________________________
Quantity: _____________Catalog #: ____________________________________
LED LOD-EXTED Emergency Driver Series
Press the test button to cut the power to the AC driver and switch
the system to emergency mode.
Release the test button to return to normal mode.
Switch off the circuit breaker to simulate a full power outage.
For initial testing, allow the unity to charge approximately 1 hour.
Then conduct a short discharge test.
Allow for a 24-hour charge before conducting a 1-hour test.
Monthly:
o
Ensure that the test button light is illuminated. Conduct a
30-second discharge test by depressing the test button.
The LED load should operate at reduced output.
Annually:
o
Ensure that the test button light is illuminated. Conduct a
full 90-minute discharge test by depressing the test
button. The LED load should operate at reduced output.
INPUT POWER
RATING
5.5W max.
1-510-217-9461 |
Web:
www.ledonecorp.com
FEATURES
Listed to UL924
Test to CSA C22.2 NO. 141 Field or factory
installation
Wattage Adjustable: 10W / 15W / 20W
Constant output power
Output LVLE Compliant
Battery: Ni-MH
Battery Charging Current: 250mA
Battery:
o
Over voltage protection
o
Low voltage protection
o
Over temperature protection
o
Short circuit protection
Ambient Temp:
0°-50°C (32°F-122°F)
5-year warranty
OUTPUT
OUTPUT POWER
VOLTAGE
25-48Vdc
20W max.
RECHARGE
TIME
24Hrs.

Advertisement

loading

Summary of Contents for LEDone LOD-EXTED Series

  • Page 1 Date: _______________ Location: _____________________________________ Product: ___________________Project: ________________________________ Quantity: _____________Catalog #: ____________________________________ LED LOD-EXTED Emergency Driver Series FEATURES • Listed to UL924 • Test to CSA C22.2 NO. 141 Field or factory installation • Wattage Adjustable: 10W / 15W / 20W •...