Download Print this page

SANJIANG A9036T Manual

Addressable optical smoke and heat multisensor detector

Advertisement

Quick Links

A9036T Addressable Optical Smoke and Heat Multisensor Detector
Read through these instructions before using this device to ensure correct installation and use!
1.
Product overview
The A9036T point composite smoke and temperature
fire detector (hereinafter referred to as the detector) is
composed of a smoke sensor and
It not only has the performance of
fire detector, but also has the performance of heat detector.
The detector is made of non-polar two bus, which can be
used with
fire alarm control panel produced by our
company.
2.
Product features
Dual heat sensors
The low profile design of the Optical/Heat Multisensor detector Detector is sleek and evolutionary, with a 360° LED
indicator which illuminates red when in alarm.
Non-polarity, two-bus connection that ensures convenient installation and maintenance.
It can realize electronic coding and rewrite the address via coder in site.
Within a single-chip MCU, it can realize real-time data acquisition and processing, realize a curve tracing for the field
situation.
It has a temperature, humidity and dust accumulation drift compensation function and a sensor fault detection
function (fault reporting to fire alarm control panel).
A sophisticated dynamic algorithm, providing transient rejection and compensation for drift whilst maintaining
accurate sensitivity.
Reference to Table 1, the detector has five modes.
3.
Technical data
Executive standard:EN54-5 & EN54-7
Operating voltage: 24V (pulse modulation)
Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm status
Coding mode: It can realize electronic coding via coder in site. Address codes 1 to 324 are available for selection
Wiring method: non-polarity two-bus system (L1, L2)
Operating environment: Indoor, temperature: -10℃~+55℃; relative humidity: ≤95% (non-condensing
External dimensions: diameter: 100mm, height: 58mm (with the base)
Weight: about 123g(with Base)
4.
Appearance and dimensions (see Fig.1)
dual heat sensors.
photoelectric
smoke
Table 1 Optical Heat Multisensor detector modes
MODE
1
heat sensor in A2R
2
heat sensor in A2
3
heat sensor in A2R
4
heat sensor in A2S
5
-
Fig.1(unit:mm)
Working mode can be set with a coder.
FUNCTION
optical sensor
optical sensor
-
-
optical sensor
- 1 -
Version:30010900210219
or icing
)

Advertisement

loading

Summary of Contents for SANJIANG A9036T

  • Page 1 Version:30010900210219 A9036T Addressable Optical Smoke and Heat Multisensor Detector Read through these instructions before using this device to ensure correct installation and use! Product overview The A9036T point composite smoke and temperature fire detector (hereinafter referred to as the detector) is composed of a smoke sensor and dual heat sensors.
  • Page 2 Use and engineering application Fig.2 is the schematic diagram of the matched mounting base. Definitions of terminals(non-polarity two-wire system): 1 --Signal terminal (L1) 3 --Signal terminal (L2) Fig.2 Wiring method: The detector is accessed through a compatible fire alarm control panel via a two-wire bus. It uses non-polarity connection.
  • Page 3 dimensions, the mounting hole diameter and the mounting hole spacing of the base are DZ-912, Ф100mm×26.4mm (diameter×thickness), Ф4.5mm and 44.5mm~64.3mm respectively. Fig.5 Wiring requirement: It is proper to use RVS twisted pairs with a section area of equal to or larger than 1.0mm for the signal buses L1 and L2.
  • Page 4 Send the detector back to the factory for fire alarm signal during an The internal circuit is damaged. repair. alarm test. Address: 3/F, Guangcai Xintiandi Mansion, Nanshan Road, Nanshan District, Shenzhen, Guangdong, 518054, P.R.China Tel: +86(755)86226969 Fax: +86(755)86223939 Website: http://www.sanjiang-security.com - 4 -...