Job:___________________
ITEM NO.
Features:
 All medium-carrying parts are made of
brass
 3/4" copper compression fittings
 Fully pre-assembled on steel wall
support, quick and easy to mount on
the wall due to stable snap-lock
technology
Two ball valves with brass flow check
valves 7.9 inch head (200 mm wc) and
spindle exchangeable under pressure
 All-metal temperature gauges
integrated into the ball valve with
immersion sleeve
 Flowmeter 0.8-6 USgpm (3-22 l/min)
with ball valve
 Safety assembly with pressure relief
valve 87 psi (6 bar), pressure gauge
and connection for expansion tank
 Airstop with manual bleeding for
venting the solar circuit, flush and fill
valves
Total height
Total width
Dimen-
Depth
sions
Center distance,
supply/return
Pipe connections
Max. admissible pressure:
Operating
Max. operating temperature
data
Max. propylene glycol content
Valves and fittings
Gaskets
Materials
Check valves
Insulation
Viessmann products specified in Imperial or metric units are approximate and are provided for reference only. For precise measurements, please contact Viessmann Technical
Service.
Viessmann reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such
changes and modifications on Viessmann products previously or subsequently sold .
25
Submittal Data Information
Solar Station Solar-Divicon DN20B
Version: 01
Effective: July 1st, 2015
Engineer:________________
MODEL NO.
15.9" (405 mm)
13.9" (344 mm)
5.9" (150 mm)
3.9" (100 mm)
3/4" compression fitting
87 psi (6 bar)
248°F (120°C)
50%
Brass
EPDM
Brass
EPP,  = 0.043 W/(m K)
Supersedes:
Contractor:_______________
For use in closed loop design only. The
solar station is used on the primary loop of
solar thermal systems to control the
temperature in the hot water storage tank.
This station contains the functional and
safety devices for optimum circuit control.
The components enable:
 Solar fluid circulation with solar pump
 Safety against pressure increase
 Exact flow rate control
 Flushing, filling and draining the circuit
 Measuring the supply and return
temperatures
 Deaerating the solar loop
 Shutting off the circuits
 Preventing gravity circulation
 Thermal insulation of the components
Flow rate [US gpm]
7675 210