General
ACTIVAL Model VY51XXJ is a series of motorized
two-way valves with flanged connections.
and actuator are integrated in a single unit.
The ACTIVAL is used to control chilled/hot water, hot
water (in high temperature) or steam, and the body rating
corresponds to JIS 10K (JIS: Japanese Industrial Stan-
dards).
The actuator has a reversible synchronous motor, which
operates at a low voltage of 24 V AC.
4 kinds of control signals are available to operate the
ACTIVAL. The built-in feedback potentiometer provides
proportional control in combination with a proportionally
controlled electronic controller. The nominal resistance
135 Ω input provides proportional control in combination
with a proportionally controlled electric controller.
4-20 mA DC and 2-10 V DC inputs provide proportional
control in combination with a direct digital controller
(DDC).
Features
• Compact and lightweight.
• Valve and actuator integrated in a single unit.
• A variety of control signals available:
- Nominal 135 Ω feedback potentiometer
- Nominal 135 Ω resistance input
- 4-20 mA DC input
- 2-10 V DC input
• Valve for water or steam with high differential pressure,
large Cv values, high rangeability and low leakage.
ACTIVAL
Motorized Two-Way Valve
with Flanged Connection
Model VY51XXJ
(JIS 10K-FC200, -SCS13A)
The valve
1
   
• Durable design.
• Low power consumption.
• Equal percentage flow characteristics.
• 2-10 V DC output (for position feedback) available with
4-20 mA DC input type and 2-10 V DC input type.
AB-6464
Specifications/Instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ACTIVAL VY51XXJ and is the answer not in the manual?

Questions and answers

Summary of Contents for Yamatake ACTIVAL VY51XXJ

  • Page 1 AB-6464 Specifications/Instructions     ACTIVAL Motorized Two-Way Valve with Flanged Connection Model VY51XXJ (JIS 10K-FC200, -SCS13A) General ACTIVAL Model VY51XXJ is a series of motorized two-way valves with flanged connections. The valve and actuator are integrated in a single unit. The ACTIVAL is used to control chilled/hot water, hot water (in high temperature) or steam, and the body rating corresponds to JIS 10K (JIS: Japanese Industrial Stan-...
  • Page 2: Safety Instructions

    Do not incinerate this product for waste disposal. Do not recycle all or a part of this product, either. • Dispose of this product as industrial waste in accordance with the local regulations. Trademark information: ACTIVAL, Infilex, Neostat are trademarks or registered trademarks of Yamatake Corporation in Japan or other countries. AB-6464...
  • Page 3 Specifcations Valve Item Specification Model Two-way valve with flanged connection Body pressure rating JIS 10K (Max. pressure: 0.98 MPa) Size, Cv Maximum pressure drop Nominal size (in inch) Max. pressure drop (close-off ratings) DN15 (1/2) 980 kPa DN15 (1/2) 980 kPa DN15 (1/2) 980 kPa DN15 (1/2)
  • Page 4 Actuator Item Specification 24 V AC ± 15 % 50 Hz/60 Hz Power supply Applicable valve size DN15 to DN80 of standard torque type Power consumption Nominal 135 Ω feedback potentiometer type: 7 VA Other types (nominal 135 Ω resistance input, 4 mA DC to 20 mA DC input and 2 V DC to 10 V DC input): 8 VA 63 ±...
  • Page 5: Selection Guide

    Option Item Specification Diameter of wire (mm): φ 7 to φ 9 Seal connector (Part No. 83104346-003) (Seal connector is necessary for waterproof protection.) Auxiliary switches Number of auxiliary switches: Two (Part No. 83161792-001) Maximum applied voltage/current: 30 V DC, 3 A DC Switch actuating position: Adjustable between 0 % (fully closed) to 50 % for SW1 Adjustable between 50 % to 100% (fully open) for SW2...
  • Page 6 Dimensions Min 100 Min 300 See note Note: Leave a clearance of 300 mm if you require to Note: When opening the top cover, open the top cover after the ACTIVAL is installed. leave a space at least 300 mm wide. Flow direction Figure 1.
  • Page 7: Parts Identification

    Parts Identification cover Actuator Knockout hole Pointer Yoke Joint Stem Seat ring Plug Figure 3. Parts identification Precautions for Installation Environment 3) Install a bypass pipe and gate valves on the inflow, outflow and bypass sides. Also, install a strainer on CAUTION the inflow side.
  • Page 8 Actuator Changing the Actuator Mounting Position 1) Change the actuator mounting position only when the CAUTION actuator is in fully open position. • Although the ACTIVAL can be used in high 2) Remove the screws connecting the actuator and the humidity environments (max.
  • Page 9 Manually Opening/Closing Valve Wiring precautions 1) Do not apply 24 V AC to the terminals 4, 5 and 6. CAUTION (Max. applicable voltage: 5 V DC) • To manually open or close the valve, be 2) To lead the wires into the actuator, cut out a knockout sure to disconnect the ACTIVAL from the hole for a wiring port.
  • Page 10: Wiring Terminals

    For splash-proof enclosure... 1) Be sure to completely close the terminal cover and the top cover. 2) Waterproof the wiring port. • For cable connection, use a water-proof connector. Recommended product: Seal conector ( Part No. 83104346-003 ) • For conduit connection, use a water-proof plica tube or the like to ensure water proofing. Wiring Terminals Open Close...
  • Page 11 Wiring Connection Examples: Connection to Yamatake’s Controllers     • • • • Connection with Neostat (Model TY900XZ)     • • • • Connection with Infilex Transformer Neostat Model TY900XZ Model VY512XJ (Nominal 135 Ω resistance input)
  • Page 12 Wiring Connection of Auxiliary Switches / Auxiliary Potentiometer • • • • Connection of auxiliary switches Common Auxiliary switch 1 (Adjustable between 0 % to 50 % positions) Terminal block Common Auxiliary switch 2 (Adjustable between 50 % to 100 % positions) Part No.
  • Page 13: Inspection And Maintenance

    Abnormal noise and vibration • Unstable open/close operation • Valve hunting Table 2 Troubleshooting (If an your problem is not solved by the corresponding action, please contact Yamatake near you.) Problem Part to check Action • Fluid leaks from the flange face.
  • Page 16 Specifications are subject to change without notice. Building Systems Company http://www.yamatake.com Rev. 2.0 Oct. 2005 AB-6464 0.5H-H (W00) (J: AI-6464 Rev. 1.0) Printed in Japan.

Table of Contents