Status Messages Specifications Other Symptoms Certifications UL Verified Performance Data Maintenance General Mesh Screen Filter Tech Tips General Limited Warranty Setup Obtaining Service Operational Controls Display and Buttons Status Icons and Messages Port Routing Control MR45 Refrigerant Flow Dynamic Pressure Measurement...
Safety Information WARNING Read, understand, and follow this entire FAILURE TO HEED THESE HAZARDS AND ACTIONS CAN RESULT IN manual, with special attention given to Warning SERIOUS INJURY OR DEATH: and Caution statements before operating this • Do not operate in a wet location as electrical shock risk. machine •...
• Make power connection of the recovery machine and other equipment outside of the Temporary Flammable Zone • Bond the recovery machine outlet port to the recovery tank’s unpainted Intentionally Blank fitting with a grounding strap to dissipate static electricity build up during during recovery process •...
Description Features • Lightweight (22 lbs) The MR45 is the first variable speed DC motor • Smooth and Fast Operation (1 HP DC Motor) recovery machine with a digital display Pump • Digital Display with Status Messages refrigerant more easily and quietly than ever •...
Tech Tips Ensure there’s enough room in the recovery cylinder to not exceed 80% filled during the job, or monitor and have a second cylinder ready. General Always purge hoses before recovery. If cylinder is too hot, use an Store in the self purge or recover position. Do not store in the ice bath to reduce the temperature and pressure of the cylinder.
Input Pressure Output Pressure MUTE AUTO-STOP LEVEL MR45 PRESS 3 SEC The icon is shown when MR45 is set to MUTE. Refrigerant Recovery Machine PRESS 3 SEC ZERO SENSOR PRESS 3 SEC OK TO START Motor stopped. Temperatures, voltages, and pressures are currently UNITS safe to start the motor again.
Port Routing Control RECOVER • Input and Output fully open. CLOSED • Set to this fully open position for most of the recovery process. • Input and Output closed. • Set to either closed position to close off both ports during setup. RECOVER (throttled) •...
Refrigerant liquid and vapor are pulled through MR45 pressure readings are designed only the machine by the pressure difference created for monitoring pressures Do not use MR45 for by the compressor For maximum performance, diagnostic pressure measurements increase the IN pressure and reduce the OUT If a system’s pressure is stable, MR45 pressure...
10 seconds at 0 psig (0 kPa), the default auto-stop level. 5. Use a P/T chart or digital manifold to find specified pressure. 7. MR45 is working well if High Pressure Cutoff occurs around 550 psig 6. Open the evacuated vapor port.
Press STOP to manually halt recovery at any time. Vapor 12. Set knob to SELF PURGE and press START to empty MR45. MR45 stops automatically when purging is complete. 13. Close manifold and cylinder valves after self purge is complete.
CAUTION: Understand all class A2L refrigerant warnings and notices if applicable (pages 4-6). Filter Drier Close valves of recovery cylinder and MR45. Set up as shown in the diagram. Open valves of liquid hose and removal tool at liquid system port.
CLOSED. Excessive noise during liquid recovery. Motor Fault 1 MR45 is experiencing a high load. Rotate the knob of MR45 to Motor temperature measured above operating range. Motor throttle the refrigerant flow. stopped. Extremely high ambient temperature, extended liquid recovery time, or high cylinder pressure can be the cause.
Grooved Input Fitting Mesh Screen Filter When the mesh screen filter becomes dirty and clogged, it means it’s working to keep your MR45 O-ring working well for a long time You need to clean or replace this screen often Visit our website for...
Need help?
Do you have a question about the MR45 and is the answer not in the manual?
Questions and answers
Does the Fieldpiece MR45 refrigeration recovery unit require periodic calibration?
The provided context does not mention the need for periodic calibration of the Fieldpiece MR45 refrigerant recovery unit.
This answer is automatically generated