Data and Installation
Mains Switching Interface Units
(SEN-INT-IOAC & SEN-INT-4IOC)
FIRE ALARM
INTERFACE
EQUIPMENT INTERFACED
SEN-INT-IOAC
The Mains switching interface units (SEN-INT-IOAC
and SEN-INT-4IO) connect to the device loop of a
SenTRI 4 and SenTRI 2 panel based system.
¨
The SEN-INT-IOAC is a 1-channel unit having
1 - medium voltage output that consist of single
pole change over contacts along with 1 low
voltage input when using V1.27 commissioning
tool and 4 low voltage inputs when using V1.28
¨
The SEN-INT-4IO is a 4-channel unit having
4 - medium voltage outputs of single pole
change over contacts, each accompanied with a
low voltage input.
The output can be individually sectored. The units
are remotely powered by the control panel via the
loop circuit.
Software compatibility
The table below shows the minimum software
requirements when this interface unit is used in a
SenTRI 4 or SenTRI 2 panel based systems.
³ - equal to or greater than
Main Controller
Loop Processor
Commissioning tool
4188-1002 issue 4_Part 1_09/13_Mains Switching I/F
Technical data
Standards -
designed to meet
Overall dimensions height - 227mm x
Assembled weight
(approximate)
Enclosure
Colour
Storage
temperature
EN54 - 17:2005 &
EN54 - 18:2005
Ambient operating
temperature
Relative Humidity
(Non condensing)
Ingress Protection
(estimated)
Output
Relay contact
rating
Input
Modes of operation Input
EN54-17 : 2005
(section 4.8)
data:
Software version
Emission
³ V4.43
³ V4.41
Immunity
³ V1.28
EN54:Part 17:2005
EN54:Part 18:2005
width - 245mm x depth - 77mm
1.1Kg
ABS V-O rated
Back box - Dark Grey
Lid - Light Grey
-20 to +70ºC
-10 to +60°C
up to 95%
Temperature +5 to +45°C
IP31
Resistive load: Single pole
change over contacts rated 16A
230V ac. 100,000 cycles
Switching power: 4000 VA
Input can be normally open or
normally closed switch
Output
Input and Output
Input with confirmation Output
Output with confirmation Input
V
42V
I
max
C max
V
40V
I
nom
S max
V
24V
I
min
L max
V
16V
Z
SO max
C max
V
8V
SO min
BS EN61000-6-3: 2007 EMC for
residential, commercial & light
Industry.
BS EN50130-4: 1996 +
A1:1998 + A2 2003
for alarm systems
0.4A
1A
20mA
0.1W
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the SEN-INT-IOAC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SMS SEN-INT-IOAC

  • Page 1 Ingress Protection IP31 SenTRI 4 and SenTRI 2 panel based system. (estimated) ¨ The SEN-INT-IOAC is a 1-channel unit having Output Resistive load: Single pole 1 - medium voltage output that consist of single Relay contact change over contacts rated 16A...
  • Page 2: Installation

    FIRE ALARM INTERFACE EQUIPMENT INTERFACED Aperture Width: 233mm Door locking EN54 - 17:2005 & SEN-INT-IOAC EN54 - 18:2005 Refit the 'Chassis plate/Board assembly' into the point backbox and secure it with the two screws and washers at positions ~. How to install the Backbox...
  • Page 3 Mains Switching Interface Data and installation Cable Output circuits (Output Channels) OUTPUT Channel The cable usage per circuit of: ¨ Clean contact Input - 50m maximum ¨ Relay output - unlimited. COMx Cable termination and separation TB1 - 4 & There should be as much physical separation between cables of OUTPUT circuits, INPUT circuits and...
  • Page 4 A confirmation input generates a fault if a change of 0359 state is not seen within the predefined period of a SMS by Honeywell (Novar Systems Limited) Manufactured by: Honeywell Life Safety Systems, specific output. 140 Waterside Road, Hamilton Industrial Park,...
  • Page 5: Commissioning Tool

    Commissioning information Mains Switching Interface Units (SEN-INT-IOAC & SEN-INT-4IO) Commissioning tool The Input and Output circuits of a Mains switching interface unit are individually configured using the Commissioning tool at V1.28 or higher. Wiring Ensure the input and/or output circuits are securely wired to the respective channels terminals of a Mains switching interface unit.
  • Page 6 Commissioning information Mains Switching Interface Fire input mode The following example shows how to wire and configure Channel 1 of a Mains switching interface unit as a Fire input. A delay can be applied before input acceptance to account for switch transition. This mode of operation can be applied in a similar manner to Channels 2, 3 and 4.
  • Page 7: Output Mode

    Mains Switching Interface Commissioning information Supervisory input mode The following example shows how to wire and configure Channel 1 of a Mains switching interface unit as a Supervisory input. A delay can be applied before input acceptance to account for switch transition. This mode of operation can be applied in a similar manner to Channels 2, 3 and 4 on a 4-channel unit.
  • Page 8 Commissioning information Mains Switching Interface Output and Fire input mode The following example shows how to wire and configure Channel 1 of a Mains switching interface unit as both Output as well as an Fire input. A delay can be applied before input acceptance to account for switch transition.
  • Page 9 Mains Switching Interface Commissioning information Output and Supervisory input mode The following example shows how to wire and configure Channel 1 as both Output as well as a Supervisory Input. A delay can be applied before input acceptance to account for switch transition. This mode of operation can be applied in a similar manner to Channels 2, 3 and 4 on a 4-channel unit, but only to Channel 1 on a 1-channel unit.
  • Page 10 Commissioning information Mains Switching Interface Confirmation Output mode The following example shows how to wire and configure Channel 1 of a Mains switching interface unit as a Confirmation output that operates immediately with any other associated Input channel. This mode of operation can be applied in a similar manner to Channels 2, 3 and 4 on a 4-channel unit and only to Channel 1 at a 1-channel unit.
  • Page 11 Mains Switching Interface Commissioning information Confirmation Output on receiving a Fire Input The following example shows how to wire and configure Channel 1 of a Mains switching interface unit to provide Confirmation Output on receiving a Fire Input at any one of the associated Channel. A delay can be applied before input acceptance to account for switch transition.
  • Page 12 Commissioning information Mains Switching Interface Confirmation Output on receiving a Superv. Input The following example shows how to wire and configure Channel 1 of a Mains switching interface unit to provide Confirmation Output on receiving a Supervisory Input at any one of the associated Channel. A delay can be applied before input acceptance to account for switch transition.