Rolling distribution rack

Advertisement

Setting Up PowerRACK™ Rolling Distribution Racks (continued)
Step 6: De-energizing Rolling Distribution Racks
1. Turn off all the individual circuit breakers powering the receptacles
2. Move the Mains Circuit Breaker to the 'O/OFF' position
3. Turn OFF the power source supplying power to the rack
4. When BREAKING the line connections (cam inlets) connection, begin with the HOT connections, then the WHITE neutral
connection and finish with the GREEN ground connection
5. Break the load connections (receptacles) per the individual wiring device type
Troubleshooting
If there is no power at the Power Inlet (LED Indicators are not illuminated):
– Ensure that all cam connections are in place and tight
– Ensure that power source is live and activate if not on
If there is no power at the Receptacles (Individual LED Indicators are not illuminated)
– Ensure that the mains circuit breaker is 'I/ON'
– Ensure that the relevant individual circuit breaker(s) is 'I/ON'
If a circuit breaker trips, identify source of short circuit or overload and correct before resetting
– Check to see if the circuit is overloaded and reduce loads as needed
– Check for short circuits in the cabling or load device and correct as needed
If a GFCI trips, identify source of current leakage and correct before resetting the GFCI
– Check to see if the circuit is overloaded and reduce loads as needed
– Check for short circuits in the cabling or load device and correct as needed
– Ensure the GFCIs are set by pressing the 'RESET' button
If there is still no power at Receptacles:
– Remove rack from us and contact Lex Products for next course of action
Technical Support
Lex Products is available to help answer any product related inquiries. For any questions or technical advice, please call toll free 800-
643-4460 or email info@lexproducts.com.
WE DELIVER THE POWER
Contact Lex Products: 800.643.4460 info@lexproducts.com
4
Lex Products
11 Forest Parkway
Shelton CT 06484
203.363.3738
TM
203.363.3742 Fax
Lex West
www.lexproducts.com
12701 Van Nuys Blvd.
info@lexproducts.com
Suite Q
800.643.4460
Pacoima CA 91331
818.768.4474
818.768.4040 Fax
© Copyright Lex Products 2021
Produced in the United States of America
05-30 All Rights Reserved.
Lex Products logo and lexproducts.com are
trademarks or registered trademarks of Lex
Products in the United States, other countries,
or both.

Advertisement

loading

This manual is also suitable for:

Powerrack presidential prmm18q-2mr8u-x-lv