Secutron MRM-800MP Series Installation Instructions

Fire alarm manual station

Advertisement

Quick Links

Secutron's MRM-800MP(U) Series Fire Alarm Manual Stations
provide manual fire alarm activation.
This guide covers these models:
MRM-810MP Single Stage, Dual Action, MP Addressable Manual
Station
MRM-810MPU Single Stage, Dual Action, MP Addressable
Manual Station (US)
MRM-802MP Two Stage, Dual Action, MP Addressable Manual
Station
MRM-822MP Two Stage, Dual Action, MP Addressable Manual
Station with additional door contacts
Specifications & Dimensions
Compatible with MR-400 series and MMX™-4000 Fire Alarm
Control Panels
Electrical Rating:
Nominal Operating Voltage: 15-30 VDC
Maximum alarm current: 3.3 mA
Standby current: 2 mA
Electrical Rating for MRM-822MP maglock terminal:
1A at 30VDC
Dimensions:
139 mm H x 104 mm W x 34 mm D
(5 1/2" H x 4 1/8" W x 1 3/8" D)
Notes
• Environment: Indoor, dry
• Do not change factory applied finishes.
• Wire as shown so that supervision of connections is
maintained.
• Maximum wire size: 14 AWG
• ADA compliant.
• To be installed per ADA 4.27.1 to 4.27.4 inclusive.
• Wiring must be in accordance with CSA C22.1, Canadian
Electrical Code, Part I, Safety Standard for Electrical
Installations, Section 32 and CAN/ULC-S524, Standard for
Installation of Fire Alarm Systems.
• All manual fire alarm stations shall be installed as per the
specific requirements outlined in the UL/ULC codes, as well
as all other applicable national or local codes. Final
acceptance is subject to the local authority having
jurisdiction.
• These devices may be operated with a blunt hand (no use of
fingers) and do not require a striking action, tight grasping,
pinching, or twisting of the wrist. The force required to
actuate the devices is less than 22 N (5 lbf).
1
MRM-800MP(U) Series
Fire Alarm Manual Station
Install the manual station
Contents of kit
MRM-810MP, MRM-810MPU: 2 mounting screws, 2 reset keys
(black)
MRM-802MP, MRM-822MP: 2 mounting screws, 2 reset keys
(black), 2 stage two keys
A. Open
1.
Insert the reset key into the reset keyhole and turn it.
2.
Pull the cover open.
RESET KEYHOLE
STAGE TWO
KEYHOLE (MRM-802MP
AND MRM-822MP)
PUSH BAR
LED FLASHES RED
WHEN POLLING AND IS
STEADY RED IN ALARM
PULL HANDLE
Figure 1 Front of manual station
COVER
Figure 2 Opening the station
Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 1-888-647-2665
www.secutron.com LT-6168SEC Rev. 0 Feb. 2023
MOUNTING
PLATE
U.S.A
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Tel: 1-888-647-2665

Advertisement

loading

Summary of Contents for Secutron MRM-800MP Series

  • Page 1 MRM-800MP(U) Series Fire Alarm Manual Station Install the manual station Secutron’s MRM-800MP(U) Series Fire Alarm Manual Stations provide manual fire alarm activation. Contents of kit This guide covers these models: MRM-810MP, MRM-810MPU: 2 mounting screws, 2 reset keys MRM-810MP Single Stage, Dual Action, MP Addressable Manual...
  • Page 2 STI-1230 (Deep Cover without Gasket) The stage two alarm activates immediately. Note: Mount the manual station with the Secutron logo on the Note: The stage two alarm will activate automatically a certain bottom. amount of time after the handle has been pulled if no action is taken.

This manual is also suitable for:

Mrm-800mpu seriesMrm-810mpMrm-810mpuMrm-802mpMrm-822mp