Fike system. Fike has a worldwide distribution network. Each distributor sells, installs, and services Fike equipment. Look on the back of the cabinet door, there should be a sticker with an indication of the distributor who installed the system. If you can not locate the distributor, please call Fike Customer Service for locating your nearest distributor, or go to our web-site at www.fike.com.
PRODUCT MANUAL PRODUCT OVERVIEW The Impulse Releasing Interface (P/N 70-290) is designed to provide an interface between the supervised releasing circuit(s) of a non Fike releasing panel (approved for suppression releasing service) and Fike’s Impulse Valve Operator (IVO). The IVO is the mechanism that is used to release the fire suppressant agent from a Fike impulse valve container.
PRODUCT MANUAL IRI CIRCUIT BOARD SPECIFICATIONS RED BLK Exhibit 3: Impulse Releasing Interface Circuit Board Power Input (Vdc): 17.8 V to 30 V Current Consumption: +24V Supervisory 22.0 mA (during capacitor charging, 60 sec. or less) 2.0 mA (after capacitor is charged) -24V Activated: 57.0 mA (both LEDs active) Temperature:...
If the installer is properly grounded at all times, damage due to static discharge will not occur. If the module requires repair or return to Fike, it must be shipped in an anti-static bag. Remove the IRI enclosure cover.
PRODUCT MANUAL WIRING The IRI circuit board is pre-wired to the termination block provided, as shown in Exhibit 5. No field connections are to be made to the IRI card. All connections for field wiring shall be made to the wire termination block provided on the IRI mounting plate.
PRODUCT MANUAL WARNING Before proceeding to the next step, make sure that the IVO’s are NOT connected to the suppression containers. Apply power to the host releasing panel. With power applied, both the red and yellow LEDs on the IRM should NOT illuminated.
PRODUCT MANUAL ARMING/DISARMING THE SYSTEM WARNING If there are ground faults present on the host releasing system (control panel), do NOT connect the Impulse Valve Operator to the suppression container. Doing so could result in accidental agent discharge. To Arm the system: 1.
PRODUCT MANUAL INSPECTIONS AND TESTING The suppression system(s) shall be inspected and tested in accordance with the requirements of EN 15004 / ISO 14520. Inspection and testing shall be performed by the system installer or an approved maintenance company who has been trained in the proper operation and testing of the system. Any defects should be recorded and reported immediately to the person responsible for routine testing.