FutureNow FNIP-4xSH-12 and FNIP-4xSH-24
Installation Manual
rev 15.01.2014
TCP/IP and Web Controllable
Four Channel DIN Rail Window Shading Controller with Local Inputs
OVERVIEW
The FNIP-4xSH can be used for controlling four motorized window coverings, such as
shades, shutters, blind, curtains, awnings or projection screens and any other devices
equipped with four-wire bidirectional AC motors with built-in limit switches either via its local
inputs, custom TCP protocol or via its built-in web interface.
The FNIP-4xSH can be controlled and monitored from standard network capable devices
such as computers, smartphones, web-tablets, etc. either locally or via the Internet.
Figure 1. The FNIP-4xSH Window Shading Controller
The module can be used independently or as part of a complex control system in residential,
or commercial installations.
FutureNow FNIP-4xSH Installation Manual rev 15.01.2014
1

Advertisement

Table of Contents
loading

Summary of Contents for p5 FutureNow FNIP-4xSH-12

  • Page 1 P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ FutureNow FNIP-4xSH-12 and FNIP-4xSH-24 Installation Manual rev 15.01.2014 TCP/IP and Web Controllable Four Channel DIN Rail Window Shading Controller with Local Inputs OVERVIEW The FNIP-4xSH can be used for controlling four motorized window coverings, such as...
  • Page 2: Main Features

    P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ In addition to the outputs, the FNIP-4xSH also provides local inputs for manual control, which give the customer the ability of using the system even before a central controller is installed or the network is built, offering stand-alone operation. This also improves reliability since the operation of the outputs via the inputs do not rely on a controller or network components that are usually single points of failure.
  • Page 3: Installation

    P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ TCP communication with simple ASCII commands • Automatic event reports about status changes of inputs and outputs • Firmware upgrade via LAN • Industry-Wide Interoperability Full Integration with home controllers from most major vendors (Control4, AMX etc.) •...
  • Page 4 P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Figure 2. FNIP-4xSH front view with terminal connectors Description Description Motor 1. Up Out Motor 1. Up Input Neutral Inputs common Motor 1. Down Out Motor 1. Down Input Motor 2. Up Out Motor 2. Up Input...
  • Page 5: Recommended Wire Types

    P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Wiring A typical wiring diagram is shown in figure 3. Figure 3. Wiring diagram All outputs in this example are used to control line voltage motors on the same phase. Providing different voltage across terminals 13 and 14 motors with different power requirements can also be used but all four motor has to be have the same power requirement.
  • Page 6: Power Requirements

    P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ The inputs use low voltage signals. The inputs use low voltage signals. • All wires used and the way they are run must be in accordance with the local electrical codes. Keep line voltage wiring physically separated from Ethernet and signal wiring.
  • Page 7: Status Led Indicators

    P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ WARNING! Avoid supplying voltage on these terminals! All input ports are galvanically isolated to protect the module against unwanted effects of ground loops, overvoltage or misconnections. It should be noted that the galvanic isolation is only effective when an independent power supply is used for powering the inputs.
  • Page 8 P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Figure 4. The board layout of the FNIP-4xSH Output status LEDs Each channel has two dedicated (red and green) output status LEDs. The green LED is on when the corresponding output is activated (the motor is powered). The red LED indicates the direction of the movement.
  • Page 9: Configuration Via The Web Interface

    P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ St LED This status LED indicates that the bootloader of the module is active. This should only happen during firmware update. Please never disconnect power from the module while this LED is on! If this LED stays on after the firmware update, please contact your distributor! CONFIGURATION Configuration can be done either via the built-in website or via TCP/IP connection.
  • Page 10 P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Figure 5. Authentication Window The default user has administrator rights and can access all settings and functions. The default user name is:admin The default password is:futurenow Once logged in, you will automatically be directed to the control page. There is a menu on the top of each web page to navigate between the different control and configuration pages.
  • Page 11 P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Figure 6. Network Configuration Page Adding users and setting up user rights Three different users can be defined each with three different user rights: admin, actor and observer. Admins have access to all functionality, including control of the outputs, monitoring the status of the inputs and outputs and changing all the settings.
  • Page 12 P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Observers are allowed to monitor the status of inputs and outputs but not allowed to control the outputs, nor can they change any settings. To modify user settings click on User in the top menu. The user configuration page is shown in Figure 7.
  • Page 13 P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Board configuration Clicking on Board in the top menu takes you to the board configuration page, where the following settings can be configured: Figure 8. Board Configuration Page FutureNow FNIP-4xSH Installation Manual rev 15.01.2014...
  • Page 14: Operation

    P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Setting the motor running time Set the motor running time to the length of time it takes for the shutter/blind to go from one of the extreme positions to the other. Since the time may be different in the two directions it is possible to set a different value for each direction.
  • Page 15 P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Active inputs (input mode 1/factory default) There are separate directional inputs for the two possible motor directions. If the motor is inactive (off) and an input is activated, then the motor will start moving in one direction. If the same input is activated again while the motor is still running, it will stop.
  • Page 16 P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Figure 9. Control Page Each input can either be active (input terminals shorted) or inactive (input terminals open) A grey icon means that the corresponding input is inactive. An active input is indicated by a green icon.
  • Page 17 P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ The blind is moving up (opening) The blind is moving down (closing) The blind is partly open. With the new firmware version the position is also displayed. (e.g. 52% open) Controlling the blinds is also possible via this web page: Clicking on the “up arrow”...
  • Page 18: Technical Specifications

    Crestron • • Software modules/plug-ins for the above controllers are either available or P5 will provide full assistance in creating them. Besides these special-purpose controllers, there are many applications for embedded industrial PC boards, PCs and smartphones running Linux, Windows, Mac OS.
  • Page 19: Test Methods

    P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ Inputs: 10-25V DC, max. 90mA@24V Outputs Type: 4 x Up/Down relay outputs Load: max. 4x2A@230V AC for inductive (cos(fi)=0.4) loads Inputs Power: 8-16V DC Current: Approx. 15 mA@12V per closed inputs Type: 4x2 galvanically isolated, noise protected common GND digital inputs for dry contacts...
  • Page 20: Contact Details

    P5 Kft. 2014 www.futurenow.hu _____________________________________________________________________________________________ REFERENCES FNIP Search Utility FNIP-4xSH TCP Communication Protocol Description CONTACT DETAILS support@p5.hu FutureNow FNIP-4xSH Installation Manual rev 15.01.2014...