Tyco Security Products Software House PSX-D8 Installation Manual

Advertisement

Quick Links

Description
The PSX-D8 and PSX-D8P simple distribution accessory
provides eight zones of fused (PSX-D8) or PTC-protected
(PSX-D8P) distribution with no built-in control features. The
PSX-D8/D8P accepts one or two power inputs, which can be
powered either by the DC1 and DC2 outputs of a single PSX
power supply or by the DC1 outputs of two separate supplies.
Each output zone of the PSX-D8/D8P is selectable for either
input source.
Specifications
Input
Voltage
Current
Standby Current 65mA
Output
Voltage
Current
(PSX-D8)
Current
(PSX-D8P)
Fuse
3A ATM automotive style
(PSX-D8
Only)
Size
PSX-D8/PSX-D8P
Weight
PSX-D8/PSX-D8P
Connecting the PSX-D8, PSX-D8P Power Distribution Module
h
Remove all AC and battery power from the system before adding or replacing a PSX-D8, PSX-D8P module
Required Connections
Optional Connections
FlexIO in from System
Input from Main
DC voltage source
Input from Second
DC source (optional)
BR in from System
5-24VDC nominal +/- 15%
12A maximum
Same as input
3.0A resistive
2.5A resistive
(Class 2 Power Ltd)
4.00" x 2.50" x 1.0"
(102mm x 64mm x 25 mm)
0.15lb (0.07kg)
FLEXIO
FLEXIO
PSX-D8
B1
2 1
2 1
2 1
2 1
2 1
2 1
B2
BR
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8
DC OUT terminals to devices to be powered
PSX-D8 & PSX-D8P Installation Manual
Regulatory Information
The equipment discussed within this manual has been tested
to the following standards:
• UL294, UL603, UL864, UL1076
• ULC S318, ULC S319
1
• CSFM Approved
Mounting the PSX-D8/D8P Power Distribution Module
Mounting of the board to an enclosure is via the four
snap-in standoffs supplied.
1. Locate the appropriate
mounting holes in the
enclosure and snap
the standoffs into the
holes.
2. Align the board mount-
ing holes with the
standoffs (be sure the PC board is properly oriented)
and snap the board onto the standoffs.
Each of the B1, B2, BR, and FlexIO busses has two connectors.
These connectors may be used interchangeably.
For example: FlexIO from the power supply may be connected
to either of the PSX-D8's FlexIO connectors, the Main DC
voltage source may connect to either B1 terminal, etc.
FLEXIO
FLEXIO
B1
2 1
2 1
B2
BR
PSX-D8/D8P
FlexIO continues to other accessories
Main DC voltage continues to
other accessories
Second DC Source continues to
other accessories
BR continues to other accessories
P03-007 revAO7

Advertisement

loading
Need help?

Need help?

Do you have a question about the Software House PSX-D8 and is the answer not in the manual?

Questions and answers

Rick
March 4, 2025

F/A input terminal block L L are these points for dry contact to kill power to mag lock?

Summary of Contents for Tyco Security Products Software House PSX-D8

  • Page 1 PSX-D8 & PSX-D8P Installation Manual Description Regulatory Information The PSX-D8 and PSX-D8P simple distribution accessory The equipment discussed within this manual has been tested provides eight zones of fused (PSX-D8) or PTC-protected to the following standards: (PSX-D8P) distribution with no built-in control features. The • UL294, UL603, UL864, UL1076 PSX-D8/D8P accepts one or two power inputs, which can be • ULC S318, ULC S319...
  • Page 2 PSX-D8 and PSX-D8P INSTALLATION MANUAL PSX-D8, D8P – Accessory Overview   FLEXIO FLEXIO FLEXIO FLEXIO PSX-D8 FLEXIO FLEXIO     Class 2 power limited wiring must be seperated from non-power limited wiring   by a minimum of 1/4 inch and must use seperate knockouts ...
  • Page 3 PSX-D8 and PSX-D8P INSTALLATION MANUAL PSX-D8, D8P – Application Examples Single Voltage - No FAI This application shows PSX-D8/D8P usage in a single-supply system when FAI is not required. • The B1 input is connected to the DC1 output of a PSX power supply or the DCOUT of a PSX-B100 secondary power sup- ply.
  • Page 4 PSX-D8 and PSX-D8P INSTALLATION MANUAL PSX-D8, D8P – Application Examples Dual Voltage - 12V and 24V Zone Programming This application shows PSX-D8/D8P usage in a dual-supply system. • The B1 input is connected to the DC1 output of a PSX power supply. B2 is connected to the DC1 output of a second PSX power supply or the DCOUT of a PSX-B100 secondary power supply.
  • Page 5 PSX-D8 and PSX-D8P INSTALLATION MANUAL PSX-D8, D8P – Application Examples Single Voltage with FAI Control • PSX-D8/D8P jumper - output selection position 1 provides constant 24VDC Out (No FAI Control) • PSX-D8/D8P jumper - output selection position 2 provides FAI controlled 24VDC Out •...
  • Page 6 PSX-D8 and PSX-D8P INSTALLATION MANUAL PSX-D8, D8P – Application Examples Dual Voltage with Two Power Supply's • Buss 1 supplied by Power Supply 1: Buss 2 supplied by Power Supply 2 • Each Power Supply requires its own back-up battery set •...
  • Page 7 PSX-D8 and PSX-D8P INSTALLATION MANUAL PSX-D8, D8P – Application Examples Triple Voltage (24V/12V/5V) with Power Supply and two PSX-B100's • Each output on PSX-D8/D8P #1 selectable for 24V or 12V DC • Each output on PSX-D8/D8P #2 selectable for 24V or 5V DC •...
  • Page 8 c o I n t e r n a t i o n a l C o m p a n y PSX-D8 and PSX-D8P INSTALLATION MANUAL www.swhouse.com The trademarks, logos, and service marks displayed on this document are registered in the United States [or other countries]. Any misuse of the trademarks is strictly prohibited and Tyco International Ltd. will aggressively enforce its intellectual property rights to the fullest extent of the law, including pursuit of criminal prosecution wherever necessary.

This manual is also suitable for:

Software house psx-d8p