Fire Management Accessories Manual 445 Lamp Driver Modules Section Technical Bulletin Issue Date 0394 L DM L am p Driver M o du les Introduction Page 3 Description Design Considerations Limits Wire Runs *5 Wiring Specifications 5 Receive Only Annunciators 6 Receive/Transmit Annunciators *6 Lamp Driver Electrical Ratings *7 Calculating the Power Supply Requirements *9...
Page 2
LDM-32 and the IFC-1010/2020 Page 23 Capabilities 23 Software Required *23 Hardware Required*23 Programming for Remote Annunciation *24 Operating the LDM-32 with the IFC-1010/2020 25 Configuring the Lamp Driver for the IFC-1010/2020 LDM-32 and the FC-2000 Capabilities *31 Software Required *31 Hardware Required*31 Operating the LDM-32 with the FC-2000 *31 Configuring the Lamp Driver for the FC-2000 *32...
Introduction Description This document describes how to install the LDM Series Lamp Driver with an IFC-1010/2020 Intelligent Fire Controller, IFC-200 Intelligent Fire Controller, or an FC-2000 Fire Controller. The Lamp Driver Module (LDM) provides the IFC-1010/2020, IFC-200, or FC-2000 with a direct interface to a custom graphic display.
Page 4
E x pan de r R ibb on C a ble (75 120 ) Cable sets for connecting LDM-32 and LDM-E32 outputs to lamps or LEDs are provided through the optional LDM-CBL24 (24 inch long) and LDM-CBL48 (48 inch long) assemblies. Each cable has a plug on one end for connection to the annunciator module and stripped and tinned ends on the other end of the assembly.
Page 5
Note: The LDM-32 is functionally identical to the ACM-16AT or ACM-32A Annunciator Control Modules. The terms “lamp driver” and “annunciator” are used interchangeably throughout this document. Although the term “lamp” is used, the LDM is most often used to drive Light-Emitting Diodes (LEDs).
Design Considerations When considering the design of your LDM annunciator system, there are two different types of configurations available: Receive Only Annunciators or Receive/Transmit Annunciators. Limits Up to 32 annunciators may be installed on an RS-485 circuit. The actual number of annunciator modules may be larger, depending on the number of expander modules employed.
Do not run cable adjacent to, or in the same conduit as, 120 VAC service, noisy electrical circuits that power mechanical bells or horns, audio circuits above 25 volts (RMS), motor control circuits, or SCR power circuits. Receive Only Annunciators For redundant annunciation of system points, annunciators can be configured as Receive Only annunciators.
"Receive Only" Annunciator Set to Address "X" Fire Alarm Control Panel RS-485 Annunciator Trunk Circuit * LDM-32 LDM-E32 Full Function "Receive/Transmit" Annunciator Set to Address "X" * RS-485 Annunciator Trunk Circuit (6000 feet max) is supervised and power-limited. LDM-32 LDM-E32 ldmannun Figure 3: Connecting Receive Only LDM Annunciator Lamp Driver Electrical Ratings...
Page 9
LDM-32 cannot be supervised. Therefore, circuits connected to the relay contacts, as well as all LEDs or lamps, must be located within 20 feet of the LDM series modules. If the lamps are in a separate cabinet from the LDM modules, the inter-cabinet wiring must be enclosed in conduit or metal raceway.
Calculating the Power Supply Requirements The LDM series annunciators can draw their power from the MPS-24A or PS5-BFS-24-UL power supply and must be considered when calculating primary and secondary power requirements. Table 2: Standby Current Draw for LED Power at 24 VDC Standby Current ] No.
Installation The LDM-32 and LDM-E32 modules mount on four standoffs inside a custom annunciator graphic box. Alternately, the modules may be installed in a standard CHS-4L chassis (not CHS-4) in a CAB-x3 series enclosure. The module size is approximately 4.4 in. x 7.1 in. If you are using a CHS-4L chassis to mount the LDM, see Figure 4.
Page 13
CHS-4L LDM-32 ldminstl Figure 4: Installing the LDM Module in the CHS-4L Chassis Connecting LDM-E32 Expander Modules (Optional) Connect an expander ribbon cable between the LDM-32 (Connector J2) and the LDM-E32 expander modules (Connector J3) as illustrated in the figure below. Expander Ribbon Cables (75120) LDM- 32 LDM-E32...
Page 14
Attach ribbon cables between the LDM-32 and the LDM-R32 for each group of relays needed (connector J5 to J5, J6 to J6, etc.) as illustrated at in Figure 6. Note: The relay module can also be connected to an LDM-E32. (75119) LDM-32 LDM-R32...
Wire the RS-485 annunciator trunk circuit using a twisted-shielded pair cable. Do not run cable adjacent to, or in the same conduit as, 120 VAC service, noisy electrical circuits powering mechanical bells or horns, audio circuits above 25 VRMS, motor control circuits, or SCR power circuits.
Page 16
Leave the 120-ohm ELR resistor installed across the RS-485 Out terminals at the last annunciator on the circuit. (See Figure 10). Remove this resistor from all other annunciators. Connect earth ground to a mounting screw on the backbox or cabinet. The 24 VDC power supplied to the annunciator need not be supervised by an end-of-line power supervision relay.
Page 17
The Trouble Input on P3, terminals 6 and 7 can be used for supervising local power sources or other devices containing a normally closed contact. If employed, all changes in status (to and from the trouble state) will be sent to the control panel in the event of device failure or restoral.
Page 19
Point Status LEDs: Use red for alarm points, yellow for trouble points, and green for output points. Use 60 ohm, 1/4 watt resistors for each point. Outputs J11 (optional) +5 V Common Relay Keyswitch Lamp Power Figure 13: Typical LDM-to-Custom Annunciator Connection @ 5 VDC (Using High Efficiency 2 mA LEDs) Note:To find the resistor size for LEDs other than 2 mA, use this...
Page 20
System Point Status LEDs: Trouble All LEDs must be Use red for alarm points, LED: located in the yellow for trouble points, (Yellow) same room as and green for output points. the modules. U se 1 0 K oh m , 1 /4 - w a tt To find the resistor size for re sisto r s fo r e ac h p o in t.
Page 21
Connecting the Main Power Supply MPS-24A Main Power Supply For the FC-2000, connect the power run for the LDM to MPS-24A TB3 Terminals 1 (+) and 2 (-) (1 amp max.). The IFC-1010/2020 requires non-resettable power. Connect the power run for the LDM to MPS-24A TB3 Terminals 3 (+) and 4 (-) (2 amps max.).
Page 22
Lamp Test/ Acknowledge The LDM series annunciator includes a single lamp test switch. The lamp test switch, connected to J1 on the master (LDM-32), illuminates all LEDs on its module, and after a short delay, each expander module in turn illuminates its LEDs. A switch installed...
Page 23
The graphic annunciator may contain a yellow System Trouble LED and a red System Alarm LED which will light for all trouble or alarm conditions (respectively) in the system (not just for those points of zones mapped to the annunciator/expanders). Note: For programming the lamp driver series into IFC-1010/2020 memory, and for mapping system points and software zones to annunciator points, refer to the Designing...
Page 24
LDM-32 and the IFC-1010/2020 Capabilities When installed with an IFC-1010/2020, LDM series modules can annunciate the status or control addressable devices, software zones, and several system control functions: Addressable Devices--2551J (Photo), 1551J (Ion), 2551TJ (Photo with non-analog heat), and 5551J (Thermal) Intelligent...
Page 25
Note: Cut R74 to enable second R S -2 3 2 C o m m o n RS-485 annunciator trunk. E a rth G ro u n d (c h a s s is ) R S -4 8 5 L o o p 1 (+ ) SIB-2048 R S -4 8 5 L o o p 1 (-) R S -4 8 5 L o o p 2 (+ )
Page 26
To program the LDM-32 into IFC-1010/2020 memory, and for mapping system points and software zones to annunciator points, refer to the Entering the Database document in the IFC-1010/2020 Technical Manual (FAN 448). Operating the LDM-32 with the IFC-1010/2020 LDM points “track” or follow the system points they are programmed to annunciate.
Page 27
Lamp Driver Mode Switch Ones Lamp Driver Address Set in the Range 01-04 Tens "Alarm/Trouble" Mode (SW4 Set to Right Side) DIP Switch (SW3) (See settings below.) "Alarm Only" Mode (SW4 Set to Left Side) ldmcon DIP Switch Set to DIP Switch Set to "ON"...
Page 28
LDM configuration are illustrated in Figures 20, 21, 22, and 23. All LEDs, lamps, and relay circuits being driven by the LDM series must be located in the same enclosure as the modules, or in separate enclosures less than 20 feet apart.
Page 29
The LDM-32 and up to 3 expanders can be configured for up to 64 alarm and trouble points by setting Switch SW4 to the “Alarm/Trouble” position. See Figures 19 and 21. LDM-32 Lamp Driver Points P o ints P oin ts P oin ts Alarm Trouble A larm T ro uble...
Page 30
IMPORTANT: When setting each of the LDM switches (SW4) for the LDM-32 and LDM-E32s, make sure that the switch settings agree on all LDMs (LDM-32 and LDM-E32s) with the same address. LDM-R32 IFC-1010/2020 Alarm Point Configurations Figure 22 illustrates wiring the LDM-R32 Relay Module to activate alarm relays for up to 64 IFC-1010/2020 points.
Page 31
Figure 23 illustrates wiring the LDM-R32 Relay Module to activate alarm and trouble relays for up to 64 IFC-1010/2020 points. P o in ts P oin ts P o in ts P o in ts LDM-32 1 - 4 5 - 8 9 - 12 13 - 16 1st LDM-E32...
Page 32
LDM-32 and the FC-2000 Capabilities When installed with an FC-2000, LDM Series modules can annunciate the status of initiating and indicating circuits, relays, and several system control functions. Each lamp driver output is automatically assigned to one system point. Circuits--IZM-8 Initiating Device Circuits (alarm and...
Page 33
Configuring the Lamp Driver for the FC-2000 Setting the Address Figure 25 illustrates the address rotary switches. Lamp Driver Mode Switch Ones Lamp Driver Address Set in the Range 01-04 Tens "Alarm/Trouble" Mode (SW4 Set to Right Side) DIP Switch (SW3) (See settings below.) "Alarm Only"...
Page 34
Flash Inhibit--Set to ON position to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also disables the piezo from sounding. Flash Inhibit must be ON when using the relay expander module (LDM-R32). The lamp driver can be set for addresses 1, 2, 3, or 4. The actual mapping arrangement for a respective module and its expanders depends on FC-2000 annunciator programming.
Page 35
The CPU-2000 can be programmed for an alternate method of annunciating the AIM-200. Up to 192 intelligent devices can be annunciated on a single AIM-200 with LDM series annunciators. The FC-2000 annunciates the AIM-200 installed directly to the right of the CPU-2000. Note that an annunciator cannot be used to execute manual ON/OFF control of intelligent AIM-200 points, only standard FC-2000 zones.
Page 36
A IM -2 0 0 8 CPU Points 8 Unusable AIM-200 Points 48 Points Mapped to the Next 6 Modules Installed aim-200 Figure 26: Point Location 36 Lamp Driver Modules—LDM Lamp Driver Modules...
Page 37
Table 11: Point Annunciation for the AIM-200 Annunciator Address 1 8 CPU points (CPU point shift not an option). 8 unusable points (redundant AIM-200 points). 48 points mapped to the next 6 modules installed in the FC-2000 (which can also be AIM-200s for annunciation of their 8 software zones).
Page 38
Table 13: Alarm and Trouble Mode with 8-Point Shift Switch LDM-32 First Second Third LDM-E32 LDM-E32 LDM-E32 Circuit 1 Circuit 17 Circuit 33 Circuit 49 Circuit 2 Circuit 18 Circuit 34 Circuit 50 Circuit 3 Circuit 19 Circuit 35 Circuit 51 Circuit 4 Circuit 20 Circuit 36...
Page 39
Alarm Points Only Operation Figure 27 illustrates wiring the LDM-32 to annunciate alarms for up to 120 zones (not zone troubles) with the first eight points (P1-P8) dedicated to the FC-2000 functions listed in Figure 27: Address 1 LDM-32 System Functions 1st LDM-E32 9-12 13-16...
Page 40
Figure 28 illustrates wiring the LDM to annunciate alarms for up to 56 zones (with no zone troubles) with the last eight points (P57-P64) dedicated to the FC-2000 functions listed below. Address 1* LDM-32 9-12 13-16 1st LDM-E32 17-20 21-24 25-28 29-32 2ndLDM-E32...
Page 41
Alarm and Trouble Points Operation Figure 29 illustrates wiring the LDM-32 to annunciate alarms and trouble for up to 120 zones with the first eight points (J5: P1 through P8 and J6: P1 through P8) dedicated to FC-2000 system functions. Address 1 LDM-32 System Functions...
Page 42
Figure 30 illustrates wiring the LDM to annunciate alarms and trouble for up to 56 zones with the last eight points (16 LEDs) dedicated to the FC-2000 system functions listed below. Address 1* LDM-32 9-12 13-16 1st LDM-E32 17-20 21-24 25-28 29-32 2ndLDM-E32...
Page 43
Alarm Relays with LDM-R32 Figure 31 illustrates wiring the LDM-R32 Relay Expander to activate alarm relays for up to 56 zones with the first eight relays dedicated to the FC-2000 functions listed below. Address 1 Points Points Points Points LDM-32 System Functions 1 - 8 9 - 16...
Page 44
Figure 32 illustrates wiring the LDM-R32 Relay Expander to activate alarm relays for up to 56 zones with the last eight relays dedicated to the FC-2000 functions listed below. Address 1 Points Points Points Points LDM-32 1 - 8 9 - 16 17 - 24 25 - 32 LDM-E32...
Page 45
Alarm and Trouble Relays with LDM-R32 Figure 33 illustrates wiring the LDM-R32 Relay Expander to activate alarm and trouble relays for up to 120 zones with the first eight relays dedicated to the FC-2000 functions listed below. Address 1 LDM-32 System Functions 1st LDM-E32 9-12...
Page 46
Figure 33: Alarm and Trouble Relays with the LDM-R32 Alarm and trouble Relays with CPU Shift Figure 34 illustrates wiring the LDM-R32 Relay Expander to activate alarm and trouble relays for up to 56 zones with the last eight relays dedicated to the FC-2000 functions listed below: Address 1* LDM-32...
Page 49
Notes Controls Group FAN 445 507 E. Michigan Street Fire Management Accessories Manual P.O. Box 423 Printed in U.S.A. Milwaukee, WI 53201 Lamp Driver Modules—LDM Lamp Driver Modules 49...
Need help?
Do you have a question about the LDM Series and is the answer not in the manual?
Questions and answers