Page 1
Dual 200A 4/5 TPA/GMT Fuse Alarm Panel with Bay Alarms Model 009-8005-1404 Installation Guide...
Page 2
Amphenol Network Solutions assumes no liability from the application or use of these products. Amphenol Network Solutions does not convey any license under its patent rights nor the patent rights of others. This document and the products described herein are subject to change without notice.
Immediately report any shipping damage, defects or missing parts to Amphenol Network Solutions at 509-926-6000. Keep all documentation that comes with your shipment. Amphenol Network Solutions is not liable for shipping damage. If the product is damaged, please notify the carrier and call Amphenol Network Solutions Customer Service at 509-926-6000 for further recourse.
Torque supplied bolt (using 7/16 in. or 12 mm socket) to 4 ft-lb dual-hole compression lug (5.42 N•m) Ground wire size Up to #4 AWG (depends on input interrupt device) Dual 200A 4/5 TPA/GMT Amphenol Network Solutions All rights reserved. 12.17.19 126152-6 Fuse Alarm Panel with 509.926.6000 – amphenol-ns.com...
Page 6
~14 lb. (~6 kg) Weight, shipping ~15 lb. (~7 kg) Environment: Specifications: Operating temperature range -10°C (14°F) to 55°C (131°F) Dual 200A 4/5 TPA/GMT Amphenol Network Solutions All rights reserved. 12.17.19 126152-6 Fuse Alarm Panel with 509.926.6000 – amphenol-ns.com Bay Alarms...
ALERT! Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region such as Underwriter’s Laboratories (UL), TUV, etc. Dual 200A 4/5 TPA/GMT Amphenol Network Solutions All rights reserved. 12.17.19 126152-6 Fuse Alarm Panel with 509.926.6000 –...
12. Insulate lug barrels with UL94 V-0 rated heat shrink tubing. 13. Clean terminals and lugs with a nonabrasive, nonmetallic pad. 14. Amphenol Network Solutions recommends a light coating of antioxidant on lugs and input BATTERY and RETURN terminals before connecting input terminals on back of the panel, as shown in Figure 5.
21. Repeat steps 17 through 20 to power up Side B. PWR ON A and PWR ON B must both be lit. Figure 8 – Alarm Terminals Dual 200A 4/5 TPA/GMT Amphenol Network Solutions All rights reserved. 12.17.19 126152-6 Fuse Alarm Panel with 509.926.6000 –...
25. Clean the panel terminals and lugs with a nonabrasive, nonmetallic pad. 26. Amphenol Network Solutions recommends a light coat of antioxidant on the lugs and output BATTERY and RETURN terminals before connecting lugs to the terminals, as shown in Figure 9. (NEC specifies only one lug and load at each output terminal.)
Expect continuity (0Ω) between C and NC of each set of terminals • Expect an open circuit (∞Ω) between C and NO of each set of terminals Dual 200A 4/5 TPA/GMT Amphenol Network Solutions All rights reserved. 12.17.19 126152-6 Fuse Alarm Panel with 509.926.6000 –...
Figure 13. Turn on equipment loads one at a time to verify proper operation of loads. Figure 13 – Designation Card Dual 200A 4/5 TPA/GMT Amphenol Network Solutions All rights reserved. 12.17.19 126152-6 Fuse Alarm Panel with 509.926.6000 – amphenol-ns.com...
1.5 Accessories The following lists optional and replacement items for the panel. For compression lugs, please refer to Wire Sizing & Label Convention Chart (Amphenol Network Solutions Part No. 117995) included with your panel. Item Description Part Number PWR / FUSE / BAY ALARM LEDs & Contacts...
BATT B TPA OUTPUT RTN B TPA FUSE HOLDER LEDS TPA OUTPUT BATT B INPUT B BATT Dual 200A 4/5 TPA/GMT Amphenol Network Solutions All rights reserved. 12.17.19 126152-6 Fuse Alarm Panel with 509.926.6000 – amphenol-ns.com Bay Alarms...
EIA/WECO Mounting Patterns FRONT VIEW Amphenol Network Solutions assumes no liability from the application or use of these products. Neither does Amphenol Network Solutions convey any license under its patent rights or the patent rights of others. This document and the products described herein are subject to change without notice.
Need help?
Do you have a question about the Dual 200A and is the answer not in the manual?
Questions and answers