Weigel WPM 735 E Operating Manual

Weigel WPM 735 E Operating Manual

Digital multifunctional power meter with lcd display

Advertisement

Quick Links

WPM 735 E
WPM 735 P
Contents
1.
Safety Notes..............................................................................................................2
2.
General Information...................................................................................................3
3.
Dimensions ...............................................................................................................4
4.
Connection ................................................................................................................5
4.1. Connection diagrams ................................................................................................5
4.2. Terminals ..................................................................................................................6
4.3. Installing and connecting the meter ...........................................................................7
5.
Display and Keys.......................................................................................................8
5.1. LCD Display ..............................................................................................................8
5.2. Key functions.............................................................................................................8
6.
Displaying Measured Values .....................................................................................9
6.1. Reading the real-time values .....................................................................................9
6.2. 4-Quadrant measurement and display..................................................................... 10
6.3. Reading the energy values ...................................................................................... 10
7.
Calculation Methods ................................................................................................ 12
7.1. Demand .................................................................................................................. 12
7.2. Energies.................................................................................................................. 12
7.3. Harmonics............................................................................................................... 12
Operating Manual
Digital Multifunctional
Power Meter
with LCD Display
- 1 -
679.B.121.01

Advertisement

Table of Contents
loading

Summary of Contents for Weigel WPM 735 E

  • Page 1: Table Of Contents

    Operating Manual 679.B.121.01 Digital Multifunctional Power Meter with LCD Display WPM 735 E WPM 735 P Contents Safety Notes......................2 General Information....................3 Dimensions .......................4 Connection ........................5 4.1. Connection diagrams ....................5 4.2. Terminals ........................6 4.3. Installing and connecting the meter ................7 Display and Keys.......................8 5.1.
  • Page 2: Safety Notes

    • Put all covers and protection devices in place before energizing the equipment. • Always supply the device with the correct rated voltage (see the label on the device). Not observing these precautions may cause serious injuries. WEIGEL-MESSGERÄTE GmbH P.O.B. 720 154 D–90241 Nürnberg Phone: 0911 / 4 23 47–0 Erlenstraße 14 D–90441 Nürnberg...
  • Page 3: General Information

    WPM 735 Basic unit Addon module Side view Rear view Rear view Note: The addon module and the connection layout are different on WPM 735 E and on WPM 735 P as well on custom meter versions! - 3 -...
  • Page 4: Dimensions

    3. Dimensions Addon module WEIGEL-MESSGERÄTE GmbH P.O.B. 720 154 D–90241 Nürnberg Phone: 0911 / 4 23 47–0 Erlenstraße 14 D–90441 Nürnberg Fax: 0911 / 4 23 47–39 Management: Phone: 0911 / 4 23 47–94 Internet: http://www.weigel-messgeraete.de e-mail: vertrieb@weigel-messgeraete.de...
  • Page 5: Connection

    Operating Manual 679.B.121.01 Digital Multifunctional Power Meter with LCD Display 4. Connection The WPM 735 is connected by 3 terminal strips which can be pulled out and inserted, thus facilitating on-site wiring and maintenance. The terminal strip with current connections (on top of the meter) can be fixed by two screws in order to prevent unintentional pull-out and thus prevent dangerous induction voltages when current terminals are not connected.
  • Page 6: Terminals

    L2 voltage L2 current L1 not connected current L1 voltage L1 WEIGEL-MESSGERÄTE GmbH P.O.B. 720 154 D–90241 Nürnberg Phone: 0911 / 4 23 47–0 Erlenstraße 14 D–90441 Nürnberg Fax: 0911 / 4 23 47–39 Management: Phone: 0911 / 4 23 47–94 Internet: http://www.weigel-messgeraete.de...
  • Page 7: Installing And Connecting The Meter

    1 not connected not connected not connected Notes on WPM 735 E • For the status inputs, external switch contacts are required. • For the analog and pulse outputs see the according descriptions below 4.3. Installing and connecting the meter ♦...
  • Page 8: Display And Keys

    WPM735 WEIGEL F: Communication G: Energy values and programming H: Unit of energy J: Keys K: Status inputs (WPM 735 E only) Unbal L: Pulse outputs (WPM 735 E only) M: Quadrants for energy N: SOE functions/Programming menu O: Programming...
  • Page 9: Displaying Measured Values

    Operating Manual 679.B.121.01 Digital Multifunctional Power Meter with LCD Display 6. Displaying Measured Values 6.1. Reading the real-time values The measured real-time values can be selected via the main menu and submenus. ♦ For paging the main menu, press one of these keys (down) (up).
  • Page 10: 4-Quadrant Measurement And Display

    One energy values can be displayed at a time in addition to current the real-time value display. ♦ When any real-time value is displayed, press this key , once or several times. WEIGEL-MESSGERÄTE GmbH P.O.B. 720 154 D–90241 Nürnberg Phone: 0911 / 4 23 47–0 Erlenstraße 14 D–90441 Nürnberg Fax: 0911 / 4 23 47–39...
  • Page 11 Operating Manual 679.B.121.01 Digital Multifunctional Power Meter with LCD Display The following values are displayed one after the other: Display Unit Display of energy value and other Imported inductive active energy Exported capacitive active energy Exported inductive active energy Imported capacitive active energy kVarh Imported inductive reactive energy kVarh...
  • Page 12: Calculation Methods

    The THD refers to the total of higher harmonics except fundamental harmonics, and it is calculated according to the following formula: ∑ WEIGEL-MESSGERÄTE GmbH P.O.B. 720 154 D–90241 Nürnberg Phone: 0911 / 4 23 47–0 Erlenstraße 14 D–90441 Nürnberg Fax: 0911 / 4 23 47–39...
  • Page 13: Programming The Meter

    Operating Manual 679.B.121.01 Digital Multifunctional Power Meter with LCD Display The K factor is calculated as follows: ∑ × ∑ : Harmonic order : Percentage of the effective value of each harmonic to that of the fundamental harmonic : Highest harmonic, here 31 Notes: •...
  • Page 14: General Programming Menus

    CODE Enter password 0 ... 99 1 is the preset password. WEIGEL-MESSGERÄTE GmbH P.O.B. 720 154 D–90241 Nürnberg Phone: 0911 / 4 23 47–0 Erlenstraße 14 D–90441 Nürnberg Fax: 0911 / 4 23 47–39 Management: Phone: 0911 / 4 23 47–94 Internet: http://www.weigel-messgeraete.de...
  • Page 15: Product-Specific Programming Menus

    Operating Manual 679.B.121.01 Digital Multifunctional Power Meter with LCD Display 8.3. Product-specific programming menus Menu Description Value range Notes P1-ob nULL Energy value applied to none active energy pulse output imported active energy exported active energy P2-ob nULL none Energy value applied to reactive energy pulse...
  • Page 16: Status Inputs

    9. Status Inputs WPM 735 E is equipped with 8 status input channels which can be used, e.g., to acquire switch positions. The meter provides a 30 V supply for this purpose. External contacts can be directly connected. Note: Since there is a internal supply by the meter, no external supply must be connected.
  • Page 17: Analog Output

    1 kWh/kvarh x CT x PT the set pulse count is supplied. 11. Analog Output WPM 735 E is equipped with one analog output 4-20 mA, to which one measured quantity can be assigned to. (Programming see 8.3.) The burdan shall not exceed 500 Ohms.
  • Page 18 λ : Scaling factor in the range of 1 to 10 (default: 1) CT: Current transformer ratio PT: Voltage transformer ratio WEIGEL-MESSGERÄTE GmbH P.O.B. 720 154 D–90241 Nürnberg Phone: 0911 / 4 23 47–0 Erlenstraße 14 D–90441 Nürnberg Fax: 0911 / 4 23 47–39 Management: Phone: 0911 / 4 23 47–94...
  • Page 19: Event Monitoring Soe

    LCD Display 12. Event Monitoring SOE WPM 735 E provides a function of recording up to 50 SOE events,. The records can be kept for more than 10 years. The SOE recording function can record the switch contact positions. When an event occurs, the meter will automatically record the type of the event such as closing of contact 1.
  • Page 20: Troubleshooting

    Check external contacts Power supply for ON- ON-OFF status OFF is not correct. Check external connections (WPM 735 E only) The analog output is No signal on analog set to "nULL" or output (WPM 735 E Check analog output settings.
  • Page 21: Technical Data

    Operating Manual 679.B.121.01 Digital Multifunctional Power Meter with LCD Display Check if the address of the meter is set Meter address is correctly, or if there is more than one wrong. meter with the same address on the bus. Baud rate is wrong. Check baud rate.