CONTROLLER AND
MINI-PROGRAMMER
Engineering Manual
Code : ISTR-MK85ENG07 - Vr. 0.7 (ENG)
1. OUTLINE DIMENSIONS (mm)
70
1
2 3 4 5 6 7 8 9 10 11 12
K 85
T un
Out1 Out2
-
=
+
Out3
13 14 15 16 17 18 19 20 21 22 23 24
2. CONNECTION DIAGRAM
DIG
In1
S U P P LY
1
2
3
4
R ela y s O U T 1 ,2 : 8A -A C 1 (3 A -A C 3 ) / 25 0 V
R ela y O U T 3 : 5 A -A C 1 (2A -A C 3 ) / 2 5 0 V
S S R
R E LAY S
N O
N C
1 3 14 15
1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4
O U T 1
K85
27
21
Prg
0 ..5 0 /6 0 m V, 0 . .1 V
0 /1 ..5 V , 0 /2 ..1 0 V
0 /4 ..2 0 m A
A C T I V E
4 ..2 0 m A
A C T IV E
e x t.
g e n .
4 ..2 0 m A
PA S S IV E
(2 w i re s )
DIG
In2
A
B
G N D
5
6
7
8
9
1 0 11
D I G . IN
R S 4 8 5
S S R : 2 0 m A / 1 0 V D C
C
C
N O
C
N O
O U T 3
O U T 2
SIKA - K series - ENGINEERING MANUAL -V0.7 PAGE 1
This instrument is intended for permanent installation, for
indoor use only, in an electrical panel which encloses the
rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following
characteristics:
1) it should be easily accessible
2) there is minimum vibrations and no impact
3) there are no corrosive gases.
4) there are no water or other fluid (i.e. condensation).
5) the ambient temperature is in accordance with the
operative temperature (from 0 to 50 °C).
6) the relative humidity is in accordance with the
instrument specifications ( 20% to 85 %).
The instrument can be mounted on OMEGA rail in
accordance with EN 50 022 (35 x 7.5 mm or 35 x 15
mm) regulations.
2.2 GENERAL NOTES ABOUT INPUT WIRING
1) Don't run input wires together with power cables.
2) External components (like zener barriers, etc.)
connected between sensor and input terminals may
cause errors in measurement due to excessive and/or
not balanced line resistance or possible leakage
currents.
3) When a shielded cable is used, it should be
12
connected at one point only.
4) Pay attention to the line resistance; a high line
resistance may cause measurement errors.
2.3 THERMOCOUPLE INPUT
_
11
+
12
Fig. 3 Thermocouple input wiring
External resistance: 100 Ω max, maximum error 0,5 %
of span.
Cold junction: automatic compensation from 0 to 50 °C.
Cold junction accuracy : 0.1 °C/°C after a warm-up of
20 minutes
Input impedance: > 1 MΩ
Calibration: according to EN 60584-1.
NOTE: for TC wiring use proper compensating cable
preferable shielded.
O U T 1 0 V D C
(M a x 2 0 m A )
P T C
N T C
2.4 INFRARED SENSOR INPUT
P t 10 0
_
T C
11
1 2
I N P U T
+
12
Fig. 4 Infrared input wiring
External resistance: don't care condition.
N C
Cold junction: automatic compensation from 0 to 50 °C.
Exergen
Need help?
Do you have a question about the K85 and is the answer not in the manual?
Questions and answers