Suggested Mounting Locations
Smoke alarms must be located in escape routes on
all levels within the household unit.
On levels containing sleeping spaces, they must be
installed within the sleeping space, or within
3 metres of every sleeping space door. And they
must be audible through closed doors.
Always Refer to NZS 4514:2009 or the latest
standard for full installation recommendations.
Min.
200mm
500mm
500mm
Operation & Testing
During Normal Operation the LED flashes
every 45 seconds.
Pressing the Test Button will activate test
mode, triggering both the Relay and the
Buzzer.
The smoke alarm will automatically reset
when all the smoke has cleared.
Hush feature. Whilst the smoke detector is
in activated, pressing the test button for 1
second, will silence that smoke detectors
sounder.
This will not hush the controllers
sounders or other smoke detectors connected
900mm
Min.
or less
200mm
Note. Smoke Detectors should be
mounted a minimum of 400mm away
from Air Con. or forced air vents.
Test at least once a month.
Always Refer to NZS 4514:2009 or the latest
standard for full installation recommendations.
= DON'T FIT AREA
(DEAD AIR SPACE)
CEILING
Min.
200mm
Beams, joists and
BEST
exposed rafters
LOCATION
deeper than
460mm are
treated as walls
ACCEPTABLE
LOCATION
= MOUNTING AREA
HM-SMOKE
AUTO RESETTING SMOKE DETECTOR
With Power Monitoring
Specifications
Detection Type
Photoelectric Chamber
Power Source
9-16 Volts DC
Standby Current
25mA
Alarm Current
20mA
Buzzer Output
85db @ 3 meters
Output Relay
N/O and N/C Contacts
100mA max
Dimensions
Ø100mm x 55mm
Standards:
GB4715-2005, EN14604, UL217
Service & Maintenance
Once a month: Press the test button
to trigger the detector. Note, putting
the alarm panel in programming mode,
Min.
will prevent the alarm sirens from
100mm
triggering as well.
Every 6 months: Vacuum or blow
dust out of the detector to help reduce
false alarms.
ARROWHEAD ALARM PRODUCTS Ltd.
1A Emirali Road,
Silverdale 0932
AUCKLAND
Ph. 09 414 0085
www.aap.co.nz
v2.02
Need help?
Do you have a question about the EliteControl HM-SMOKE and is the answer not in the manual?
Questions and answers