EN
Intra-Sewi TWIN L-Pr and
Intra-Sewi TWIN TH-L-Pr
Brightness and Presence Detectors
Technical specifications and installation instructions
Item numbers
66111 Intra-Sewi TWIN L-Pr
66121 Intra-Sewi TWIN TH-L-Pr
1.
Description
The Sensor Intra-Sewi TWIN L-Pr for the TWIN building bus system captures
brightness and motion in a room. Two Intra-Sewi TWIN can be connected at the
same time to one controller.
The Sensor Intra-Sewi TWIN TH-L-Pr additionally measures the temperature and
the air humidity.
Functions:
•
Brightness measurement with brightness control
• Motion detection
Additional functions Intra-Sewi TWIN TH-L-Pr:
•
Measuring the temperature and air humidity (relative, absolute)
1.0.1. Scope of delivery
•
Sensor
•
Pre-assembled clamps for false ceiling installation
•
Support ring for connector socket installation
For socket installation you will need in addition (not supplied):
•
Socket Ø 60 mm, 42 mm deep
1.1. Technical data
Housing
Plastic, glass
Colour
similar to pure white RAL 9010
Assembly
built-in, in false ceiling or connector socket
Protection category
IP 30
Dimensions
Ø approx. 80 mm;
height above wall approx. 5 mm
height in wall (installation) approx. 31 mm (incl.
clamps)
Total weight
approx. 50 g
Ambient temperature
Operation -20...+60°C, storage -20...+70°C
Ambient humidity
max. 95% RH, avoid condensation
Operating voltage
TWIN bus voltage
Bus current
max. 10 mA
Data output
TWIN +/- bus plug-in terminal
BCU type
Integrated microcontroller
PEI type
0
Brightness sensor:
Measurement range
0 lux ... 2,000 lux (higher values can be measu-
red and output)
Resolution
1 lux at 0...2,000 lux
Accuracy
±15% of the measurement value at 30 lux ...
2,000 lux
Motion sensor:
Coverage angle
approx. 94° × 82° (see also Coverage area of the
motion detector)
Range
approx. 5 m
Temperature sensor (only Intra-Sewi TWIN TH-L-Pr):
Measurement range
-20°C ... +60°C
Resolution
0.1°C
Accuracy*
±0.7°C at -20°C...-10°C
±0.5°C at -10°C...+60°C
Humidity sensor (only Intra-Sewi TWIN TH-L-Pr):
Measurement range
0% rH ... 100% rH
Resolution
0.1% rH
Accuracy
± 7.5% rH at 0% ... 10% rH
± 4.5% rH at 10% ... 90% rH
± 7.5% rH at 90% ... 100% rH
The product is compliant with the provisions of the EU guidelines.
1.1.1. *Measuring accuracy
Deviations in measured values due to interfering sources (see chapter installation
location) must be corrected in the MultiController TWIN application in order to
achieve the specified accuracy of the sensor (offset).
Sensor Intra-Sewi TWIN TH-L-Pr and Intra-Sewi TWIN L-Pr • Version: 09.08.2019 • Technical changes and errors excepted. • function Technology AS • Norway • +47 55 38 50 80 • www.function-technology.com
Sensor Intra-Sewi TWIN TH-L-Pr and Intra-Sewi TWIN L-Pr
During the Temperature measurement, the self-heating of the device is taken into
consideration by the electronics. It is compensated by the software, therefore the di-
splayed/output indoor temperature measuring value is correct.
2.
Installation and start-up
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
•
National legal regulations are to be followed.
•
Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
•
Do not use the device if it is damaged.
•
Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification
or failure to follow the operating instructions voids any and all warranty and gua-
rantee claims.
After unpacking the device, check it immediately for possible mechanical damage.
If it has been damaged in transport, inform the supplier immediately.
The device may only be used as a fixed-site installation; that means only when as-
sembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
function Technology AS is not liable for any changes in norms and standards which
may occur after publication of these operating instructions.
2.2. Installation location
Install and use only in dry interior rooms! Avoid condensation.
The Sensor is installed in a false ceiling or a standard connection socket (Ø 60 mm,
42 mm deep).
The device must be installed on the ceiling, so that the movement capturing takes
place from above. Make sure that the desired area is covered by the sensor's cover-
age angle and that no obstacles obstruct the recording.
When selecting an installation location for Intra-Sewi TWIN TH-L-Pr, please ensu-
re that the measurement results of temperature and humidity are affected as litt-
le as possible by external influences. Possible sources of interference include:
•
Direct sunlight
•
Draughts from windows and doors
•
Draughts from ducts coming from other rooms or the outdoors
•
Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
•
Connection lines and empty ducts which lead from warmer or colder areas to
the sensor
Measurement variations from such sources of interference must be corrected in the
application program for the MultiController in order to ensure the specified accuracy
of the sensor (offset).
2.2.1. Coverage area of the motion detector
Angle of coverage: approx. 94° × 82°
Range: approx. 5 m
Segmentation of the coverage area
Fig. 1
length
Size of the coverage area
Distance
Length
2.50 m
approx. 5.40 m
3.50 m
approx. 7.50 m
Orientation of the
support ring for so-
cket installation
Width
approx. 4.30 m
approx. 6.10 m
1