 Connection of drain hose
• Connect a hard socket (locally procured) to the hard socket of the attached supplied flexible hose.
• Connect a drain pipe (locally procured) to the connected hard socket.
REQUIREMENT
• Connect hard vinyl chloride pipes securely using an adhesive for vinyl chloride to avoid water leakage.
• It takes some time until the adhesive is dried and hardened (refer to the manual of the adhesive). Do not apply stress
to the joint with the drain pipe during this time period.
Insert the flexible drain hose into the upper drain pipe and fix it with the hose band.
 Gravitational drainage
1
Reattach the drain cap.
*For gravitational drainage, remove the white
connector (CN504) on the upper left of the circuit
board in the electrical control box.
2
Insert flexible drain hose into lower drain
pipe and fix it with hose band.
3
Remove drain pump connector CN504.
15-EN
Hose band
Upper pipe
Flexible
drain hose
Upper pipe
Lower pipe
Move the drain cap from
the lower pipe to the upper
pipe.
CN504
Red
Black
 Drain up
When a down-gradient cannot be secured for the drain pipe, drain-up
piping is possible.
• The height of the drain pipe must be A mm or less from the
underside of the indoor unit.
• Take the drain pipe out of the drain pipe joint with the indoor unit in
11.8" (300 mm) or less, and bend up the pipe vertically.
• Immediately after the pipe is bent up vertically, lay the pipe making
a down-gradient.
 Check the draining
In the test run, check that water drain is properly performed and water does not leak from the connecting part of
the pipes. When doing this, also check that no abnormal sounds are heard from the drain pump motor. Check
draining also when installed in heating period.
When the electrical and wiring work has been completed
Pour some water by following the method shown in the following figure. Then, while performing a cooling operation,
check that the water drains from the drain pipe connecting port (transparent) and that no water is leaking from the
drain pipe.
When the electrical and wiring work has not been completed
• Disconnect the float switch connector (3P: red) from the connector (CN34: red) on the P.C. board inside the
electrical control box. (Before doing this, the power must be turned off.)
• Connect a 208 / 230 V supply voltage to (L) and (N) on the power supply terminal block. (Do not apply a 208 /
230 V voltage to (Uv (U1)), (Uv (U2)), (A), (B) of the terminal block. Otherwise, the printed circuit board may be
damaged.)
• Pour the water by following the method shown in the following figure. (Amount of water poured: 0.4 to 0.5 gal
(1500 cc to 2000 cc))
• When the power is turned on, the drain pump automatically starts running. Check whether the water is draining
from the drain pipe connecting port, and check that no water is leaking from the drain pipe.
• After checking that the water drains and there are no water leaks, turn off the power, connect the float switch
connector to its original location (CN34) on the P.C. board, and return the electrical control box to its original
position.
208 / 230 V - 1 - 60 Hz
White
Red
Black
Black
Pull out connector CN34 (Red)
from P.C. board.
– 8 –
For drain pipes that will be
connected after setup, make a
downward slope of 1/100 or more.
Flexible drain hose
(Accessory)
11.8" (300 mm)
or less
Drain up setup dimensions