Ditek DTK-UPS1000R User Manual

On-line uninterruptible power supply systems

Advertisement

Quick Links

User Manual
DTK-UPS1000R DTK-UPS1000RE
DTK-UPS1500R DTK-UPS1500RE
DTK-UPS2000R DTK-UPS2000RE
DTK-UPS3000R DTK-UPS3000RE
On-Line
Uninterruptible Power Supply
Systems
INT-100165-001 Rev. 1.2
PN: 191-596

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DTK-UPS1000R and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Ditek DTK-UPS1000R

  • Page 1 User Manual DTK-UPS1000R DTK-UPS1000RE DTK-UPS1500R DTK-UPS1500RE DTK-UPS2000R DTK-UPS2000RE DTK-UPS3000R DTK-UPS3000RE On-Line Uninterruptible Power Supply Systems INT-100165-001 Rev. 1.2 PN: 191-596...
  • Page 2 INT-100165-001 Rev. 1.2 PN: 191-596...
  • Page 3: Table Of Contents

    Table of Contents 1. Important Safety Warning ....................1 1-1. Transportation ..................... 1 1-2. Preparation ......................1 1-3. Installation ......................1 1-4. Operation ......................1 1-5. Maintenance, service and faults................2 2. Installation and setup ....................3 2-1 Rear panel view ....................3 2-2.
  • Page 4: Important Safety Warning

    1. Important Safety Warning Please comply with all warnings and operating instructions in this manual. Save this manual and carefully read the following instructions before installing the unit. Do not operate this unit before thoroughly reading through all safety information and operating instructions.
  • Page 5: Maintenance, Service And Faults

    In order to fully disconnect the UPS system, first press the OFF/Enter button to  disconnect the mains. Do not allow fluids or other foreign objects inside the UPS system.  The EPO, RS-232 and USB circuits are an IEC 60950 safety extra low voltage (SELV) ...
  • Page 6: Installation And Setup

    2. Installation and setup NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. 2-1 Rear panel view DTK-UPS1000R DTK-UPS1000RE DTK-UPS1500R DTK-UPS1500RE...
  • Page 7: Operating Principle

    2-2. Operating principle The operating principle of the UPS is shown as below The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery charger, DC-to-DC converter, battery, dynamic bypass and UPS output. PN: 191-596 INT-100165-001 Rev. 1.2...
  • Page 8: Install The Ups

    2-3. Install the UPS For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before installing the UPS, please follow steps below to connect batteries. Step 1 Step 2 Step 3 Remove front panel. Remove battery panel Put battery panel and and connect battery wire.
  • Page 9: Setup The Ups

    Tower Installation Install UPS alone Install UPS and external battery NOTE: When installing the UPS or battery pack with feet, please keep 70mm distance from the edge of the unit. 2-4. Configure the UPS Step 1: UPS input connection Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
  • Page 10 Step 2: UPS output connection There two kinds of outputs: programmable outlets and general outlets. Please connect non-critical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by setting shorter backup time for non-critical devices.
  • Page 11 115 Vac, 12.4 A, 1425 VA, 1283 W 120 Vac, 12.5 A, 1500 VA, 1350 W 50/60 Hz DTK-UPS1000R(E) I/P: 100-120 V, 50/60 Hz, 9.1 A O/P: 100 Vac, 8.0 A, 800 VA, 720 W 110 Vac, 8.2 A, 900 VA, 810 W 115 Vac, 8.3 A, 950 VA, 855 W...
  • Page 12: Battery Replacement

    Step 6: Turn on the UPS Press the ON/Mute button on the front panel for two seconds to power on the UPS. Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period. Step 7: Install software For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
  • Page 13: Battery Kit Assembly (Option)

    Put the front panel back to the unit. 2-6. Battery Kit Assembly (option) NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select correct battery kit procedure below to assemble it. 2-battery kit Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following below chart.
  • Page 14 Step 3: Put assembled battery packs on Step 4: Cover the other side of plastic shell as one side of plastic shells and insert one below chart. Install kit in UPS. defective battery for proper spacing. Defect battery 4-battery kit Step 1: Remove adhesive tapes.
  • Page 15 Step 3: Put assembled battery packs on Step 4: Cover the other side of plastic shell as one side of plastic shells. below chart. Install kit in UPS. PN: 191-596 INT-100165-001 Rev. 1.2...
  • Page 16: Operations

    3. Operations 3-1. Button operation Button View Button Function  Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.  Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system.
  • Page 17 Display Function Backup time information Indicates the backup time in pie chart. Indicates the backup time in numbers. H: hours, M: minute Warning & Fault information Indicates that the warning and fault occurs. Indicates the warning and fault codes, and the codes are listed in details in 3-7 and 3-8 sections.
  • Page 18: Audible Alarm

    3-3. Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Overload Sounding twice every second Fault Continuously sounding 3-4. LCD display wordings index Abbreviation Display content Meaning Enable Disable Escape Rack display Tower display Low Battery Overload Battery is not connected Overcharge...
  • Page 19 01: Output voltage setting  Interface Setting You may choose the following output voltage: 100: presents output voltage is 100Vac 110: presents output voltage is 110Vac 115: presents output voltage is 115Vac 120: presents output voltage is 120Vac 02: Frequency Converter enable/disable ...
  • Page 20 05: AECO enable/disable  Interface Setting ENA: Advanced ECO mode enable DIS: Advanced ECO mode disable 06: Bypass mode enable/disable when UPS is off  Interface Setting ENA: Bypass mode is enabled when UPS is off DIS: Bypass mode is disabled when UPS is off. 07: Programmable outlets enable/disable ...
  • Page 21: Operating Mode Description

    09: LCD display direction setting  Interface Setting RAC: the LCD display is horizontal. TOE: the LCD display is vertical. 10: Acceptable input voltage range setting  Interface Setting You may choose the following Acceptable input voltage range: 55/150 alternating flashing: acceptable input voltage range is from 55V to 150V;...
  • Page 22: Faults Reference Code

    Frequency When input frequency is within 40 Hz Converter to 70 Hz, the UPS can be set at a mode constant output frequency, 50 Hz or 60 Hz. The UPS will still charge (Rack) battery under this mode. Battery When the input voltage is beyond the mode acceptable range or power failure and alarm is sounding every 4...
  • Page 23: Warning Indicator

    3-8. Warning indicator Warning Icon (flashing) Code Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not connected Sounding every second Overcharge Sounding every second Site wiring fault Sounding every second EPO enable Sounding every second Over temperature Sounding every second Charger failure...
  • Page 24: Troubleshooting

    4. Troubleshooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Remedy No indication and alarm even The AC input power is not Check if input power cord though the main is normal. connected well.
  • Page 25 Symptom Possible cause Remedy Fault code is shown as 43 and The The UPS shut down Remove excess loads from icon is lighting on LCD automatically because of UPS output and restart it. display and alarm is continuously overload at the UPS sounding.
  • Page 26: Storage And Maintenance

    5. Storage and Maintenance Operation The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer. Be sure to return expired batteries to a recycling facility. Storage Before storing, charge the UPS 5 hours.
  • Page 27: Specifications

    6. Specifications DTK-UPS1500R(E) DTK-UPS1000R(E) DTK-UPS2000R(E) DTKUPS3000R(E) MODEL 1500 VA 1000 VA 2000 VA 3000 VA Capacity 1350 W 900 W 1800 W 2700 W INPUT Rated 100*/110*/115*/120/127 VAC Voltage Required Power Voltage Range Low Line 80 VAC/70 VAC/60 VAC/55 VAC ± 5 %...
  • Page 28 External Battery Pack Specification DTK-UXB2000R Model DTK-UXB1000R DTK-UXB1500R DTK-UXB3000R Used with UPS Models DTK-UPS2000R(E) DTK-UPS3000R(E) DTK-UPS1000R(E) DTK-UPS1500R(E) Battery Type 12V 9Ah 12V 9Ah 12V 9Ah 12V 9Ah Battery Numbers 16.14 x 17.24 x 3.46 Dimensions(in) 16.14 x 17.24 x 3.46 20.10 x 17.24 x 3.46 24.80 x 17.24 x 3.46...
  • Page 29: Warranty

    DITEK with respect to the use of the products is given without charge and DITEK assumes no obligation or liability to Purchaser for the advice given or results obtained, all such advice is given by DITEK and accepted by Purchaser at Purchaser’s risk.
  • Page 30: Regulatory Compliance

    8. Regulatory Compliance FCC Notice, Class A This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.