This is why they use a decentralized external power supply instead of the M-BUS- MASTER. The ADICOS NT V40-A3 – power supply for industrial fire detectors ensures that your complex fire detection system receives the optimal power supply. Its exceptional features include: Sturdy enclosure made of sheet steel ■...
AbOuT ThIS MANuAl About this Manual Objective This manual describes how to properly install, wire, start up and operate the ADICOS NT V40-A3. Once the device has been successfully started up, this document serves as a reference in the event of malfunctions.
ADICOS branching and connection box M-BM ADICOS M-BUSMASTER ADICOS NT V40-A3 - power supply for industrial fire detectors Storing this Manual Store this manual near the equipment, in a place where it can easily be accessed when needed for reference.
Intended use also includes following the instructions in this manual and complying with all relevant local regulations. The ADICOS NT V40-A3 may not be used for any other purpose. If the device is used in any other way, or if changes are made to the product, including in the course of installation and maintenance, the warranty claim is no longer valid.
• Only use original spare parts and original accessories! • Original spare parts and accessories may only be installed by trained spe- cialist personnel. • Qualified personnel are persons as described in Chap. 2.3. 430-2410-010 EN11 ADICOS NT V40-A3...
DESCrIpTION Of prODuCT Description of Product The ADICOS NT V40-A3 is designed specifically to supply energy to ADICOS detectors. Its output voltage can supply up to 15 GSME or HOTSPOT detectors, depending on the cable paths and cross-sections. Power to the NT V40-A3 is supplied via 230 VAC mains voltage. One of its features is power failure detection with a signal relay.
Check that the delivery is complete and no items are damaged. The scope of delivery includes: Power supply unit NT V40-A3 – Mounting bracket – Mounting instructions – Instruction manual – Cable gland plate (perforated) – Cable fittings – Dimensions 430-2410-010 EN11 ADICOS NT V40-A3...
Functioning The ADICOS NT V40-A3 is an external device used to supply power to up to 15 detectors, e.g. detectors in the GSME or HOTSPOTseries. The short-circuit-proof power supply ensures optimal power supply to complex fire detection systems in large industrial plants and power plants.
INSTAllATION Electromagnetic Radiation The electronics contained in the ADICOS NT V40-A3 can be impaired by electromagnetic radiation. So do not place the power supply unit near high voltage equipment. And always use shielded cable. Wiring Specifications WARNING! Gefahr von Störungen und Ausfall der Melder-Anlage! Incorrect wiring of the power supply NT V40-A3 can lead to faults and failures of the detector system.
• Mounting may be performed only by properly trained personnel. CAUTION! Risk of injury! The ADICOS NT V40-A3 is heavy. Incorrect mounting or the use of unsuitable wall mounts can result in injury. • Mounting in a suitable location may be performed only by properly trained personnel.
Page 14
Remove the plastic caps from the back of the electrical cabinet. Attach the included mounting bracket to the electrical cabinet (Refer to included mount- ing instructions). Use four screws to fasten the ADICOS NT V40-A3 to the wall. Use fittings suitable to the wall design. 5.4.3 Wiring Connect the components to one another.
• Deenergize the entire detector system before cleaning the device! The ADICOS NT V40-A3 electrical cabinet can be cleaned with a soft, damp cloth and dishwashing liquid. Scouring agents, acids and bases may not be used; do not apply wa- ter pressure to clean.
The mains voltage is disrupt- and none of the displays on ed or there is a defect in the the power supply unit are il- ADICOS NT V40-A3. luminated ... some of the detectors do The voltage is insufficient to...
Device model SERIAL: Serial number Year of production (variable) (variable) ART-Nr: Article number TEMP: Ambient Degree of (variable) temperature protection COM-Nr: Communication /VA: Power supply / Internal fusing number (variable) power output (Short-circuit current) CE marking ADICOS NT V40-A3 430-2410-010 EN11...
Page 18
NOTES 410-2410-001 EN11 ADICOS NT V40-A3...