KATU PS500 Series Operating Instructions Manual

KATU PS500 Series Operating Instructions Manual

Electronic pressure sensor

Advertisement

Quick Links

Sensor and controller
Flow
pressure
temperature
level
position
Operating instruction
Electronic pressure sensor
PS500 Series

Advertisement

Table of Contents
loading

Summary of Contents for KATU PS500 Series

  • Page 1 Sensor and controller Flow pressure temperature level position Operating instruction Electronic pressure sensor PS500 Series...
  • Page 2: Product Application

    Product application Dual pressure switches monitor system pressure with two switch outputs and one analog output. danger This switch can only be used in the specified application range. The temperature range must be within the permissible range. Do not exceed the rated pressure and power load value.Assembly, commissioning and operation must be carried out in accordance with applicable national and local safety instructions.The switch is designed to be used as a safety device for pressurizing the system in accordance with...
  • Page 3: Safety Instruction

    Safety instruction Safety instructions are intended to protect users from dangerous situations and/ or prevent material damage.In the operating instructions, the severity of the potential risk can be indicated by the following signal words: danger An imminent danger to the user. Failure to comply may result in fatal injury. warning An identifiable hazard.
  • Page 4: Switching Function

    Principle structure The diffused silicon sensor is used for pressure measurement, and the signal is processed by a post-processing circuit and converted into a standard industrial electrical signal for output and display. The all-metal casing design, with a highlighted LED digital display, enables the product line to be used in a variety of industrial applications.
  • Page 5 Install Safety instructions are intended to protect users from dangerous situations and/or prevent material damage. In the operating instructions, the severity of the potential risk can be indicated by the following signal words: caution Vibration and violent vibration must be avoided during transportation. Even if the switch housing is not damaged, Internal components can also break down and cause failure.
  • Page 6: Panel Description

    Dimensional drawing(mm) φ38 φ35.5 M12*1 Aviation plug ES27 G thread Panel description Level 2 menu factory data reset SP2 Switch signal lamp Pressure unit indicator light Hold down [+] to restore factory Settings SP1 Switch signal lamp Pressure value switch 1 signal: (Factory default HNO) Hysteresis function: HNO (normally open) /HNC (normally closed) Window function: FNO (normally open) /FNC (normally closed) 4 digit LED digital display...
  • Page 7: Electrical Connection

    factory data reset Hold down [+] to restore factory Settings Pressure value switch 1 signal: (Factory default HNO) Electrical connection Hysteresis function: HNO (normally open) /HNC (normally closed) Window function: FNO (normally open) /FNC (normally closed) ! Wiring must be done by a qualified electrician and the national and international codes for the installation of electrical equipment must be followed.
  • Page 8 Two way switch + one analog NPN(+Analog quantity) PNP(+Analog quantity) brown 12~30VDC 12~30VDC brown white white black black grey grey blue blue One switch + one analog NPN(+Analog quantity) PNP(+Analog quantity) 12~30VDC brown brown 12~30VDC black black white white blue blue Debugging/operation The pressure switch can only be debugged and operated by authorized personnel.
  • Page 9 Level 1 menu Alarm value of Switch 1 (Factory default value is 0.2% of the range) Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed: At the press of a button, the value increases; Hold the button down and the value will keep changing.
  • Page 10 Level 2 menu factory data reset Hold down [+] to restore factory Settings Pressure value switch 1 signal: (Factory default HNO) Hysteresis function: HNO (normally open) /HNC (normally closed) Window function: FNO (normally open) /FNC (normally closed) Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed: At the press of a button, the value increases;...
  • Page 11 OUT1 shutdown delay. (The factory default is 0s) Hold + or [-] for at least 1s. After 1 second: The setting value can be changed: At the press of a button, the value increases; Hold the button down and the value will keep changing. OUT2's opening delay.
  • Page 12 Update rate and direction of the display (d1 by default) Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed: At the press of a button, the value increases; If you hold the button down, the value will keep changing. [d1] : The measured value is updated every 10ms [d2] : The measurement is updated every 100ms [d3] : Update measurement every 600ms...
  • Page 13 Display menu Level 1 menu The one-circuit switch does not have this function Level 2 menu Display menu www.katusensor.com...
  • Page 14 No analog model does not have this function Level 2 menu Display menu www.katusensor.com...
  • Page 15: Maintenance & Cleaning

    Hold down [+] or [-] for at least 1s. After 1 second: The setting value can be changed: At the press of a button, the value increases; Hold the button down and the value will keep changing. Switch point damping/process data flow (IO-Link communication) and display. (Factory default: 0.06) Maintenance/cleaning Hold down [+] or [-] for at least 1s.
  • Page 16 Katu Electronic (Kunshan)Co.,Ltd. The phone number is 400-150-8815 Website: www.katusensor.com Factory: No.1120 Jinyang East Road, Kunshan City, Suzhou City...