TECHNICAL INSTRUCTION – MICRODYN BIO-CEL®
MICRODYN BIO-CEL®
Diffusor Replacement
Introduction
This document is showing the procedure of diffusor replacement. The procedure can be applied for BIO-CEL®
50/52/100/104/208/400/416/L/XL (not for BIO-CEL® L-2/XL-2). The pictures used in this instruction belong to BIO-CEL®416,
the general steps are the same for all above mentioned BIO-CEL modules.
In case of any question which might derive during the mounting procedure, please don´t hesitate to contact us, the contact
information are shown at the end of the document.
For disassembly of the diffuser case from the module frame please refer to the corresponding document on our website
(https://www.microdyn-nadir.com/mbr-bulletins-guides/)
Safety Precautions
Please follow section 1, Safety & Warnings in the latest version of the MICRODYN BIO-CEL MBR Operation and Maintenance
Manual.
Material Required for disassembly & assembly
Please refer to the corresponding scope of supply document ((https://www.microdyn-nadir.com/mbr-bulletins-guides/) for the
part numbers needed for this replacement.
Pos.
Part
1
BIO-CEL
Diffuser Set
®
2
BIO-CEL
®
Diffuser Assembly Tool
3
Set of fork or socket wrenches of different sizes
4
Integrity test kit
FORM NO.: TI-WW024
REVISION: B | DATE: 07/01/2020
Remarks
Set of diffusers + connectors
a
Torque wrench with special wrench socket (must be ordered separately)
Customers scope of supply
Customers scope of supply (optional only)