Connect Phase (Live) to R and Neutral to S for single
phase supply
Connection U/T1, V/T2, W/T3 go to the motor
Connect 3 phase input supply L1/R, L2/S, L3/T
Connection U/T1, V/T2, W/T3 go to the motor
Instructions for Remote Setup
(Remote On/Off and Speed Variation)
•
For remote stop and start connect between DCM and
MI1 (FWD) and MI2 (REV) (DCM is your common)
•
For remote Potentiometer connect the potentiometer
to +10V, AVI and ACM (common).
•
Set 00.20 to 2 (Remote Potentiometer setting)
•
Set 00.21 to 1 (Remote ON/OFF setting)
•
Set 02.00 to 1 or 2 (2-wire operation control)
• Set 02.00 to 3 (3-wire operation control)
V/F curve set up
(Factory setting is General purpose)
QUICK SETUP INSTRUCTIONS FOR
VARIABLE SPEED DRIVE
1 PHASE TO 3 PHASE
AND
3 PHASE TO 3 PHASE
VFD-MS300 Series