Fujitsu ARXG24KHTAP Design & Technical Manual page 55

Duct type
Table of Contents

Advertisement

2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number
26
NOTE: Range of static pressure is different by model.
If the static pressure is set above maximum range, the setting will be the same as the maxi-
mum.
Example:
For 45, 54 type models, setting "170 Pa" (17) to "200 Pa" (20) will be the same as "160 Pa"
(16).
For details, refer to Chapter 5-1.
9-2. Function settings by using remote controller
Setting value
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
31
(35 Pa: 24 type; 47 Pa: 30, 36 type; 60 Pa:
32
Type name
24, 30, and 36 type
45 and 54 type
"Fan performance curve"
Setting description
30 Pa
40 Pa
50 Pa
60 Pa
70 Pa
80 Pa
90 Pa
100 Pa
110 Pa
120 Pa
130 Pa
140 Pa
150 Pa
160 Pa
170 Pa
180 Pa
190 Pa
200 Pa
Standard
45, 54 type)
Automatic airflow adjustment
Setting of static pressure range
on page 16.
- 49 -
Factory setting
30 to 200 Pa
30 to 160 Pa