Distech Controls EC-Net EC-SEC-EN-MED Hardware Installation Manual
Distech Controls EC-Net EC-SEC-EN-MED Hardware Installation Manual

Distech Controls EC-Net EC-SEC-EN-MED Hardware Installation Manual

Medium & large enclosure security

Advertisement

Quick Links

Medium & Large Enclosure Security
This document covers the mounting and wiring of the medium and large-sized EC-Net
used for housing the EC-BOS-602
and/or its expansion modules. It assumes that you are an engineer, technician, or service person who is
performing access system design or installation. Instructions apply to the following enclosure models:
Models
EC-SEC-EN-MED
Medium-sized enclosure with single DIN rail, integral
power supply, tamper switch, key lock, and capacity for
two user-supplied 12V sealed lead-acid backup
batteries.
Accommodates the EC-BOS-n
Remote Reader modules, or one Remote IO Security
module.
EC-SEC-EN-MNP
As above, but without the integral power supply.
Accommodates one additional Remote Reader module.
EC-SEC-EN-LRG
Large-sized enclosure with two (2) DIN rails, integral
power supply, tamper switch, key lock, and capacity for
two user-supplied 12V sealed lead-acid backup
batteries.
Accommodates the EC-BOS-n
Remote Reader modules, or the EC-BOS-n
with up to 2 Remote IO Security modules, or many other
possible combinations.
EC-SEC-EN-LNP
As above, but without the integral power supply.
Accommodates one additional Remote Reader module.
These are the main topics included in this document:
Preparation,
page 2
Precautions,
page 3
Related Documentation,
Installation Summary,
Pre-Installation,
page 4
Mounting and Dimensions,
Earth Grounding and Power Wiring,
EC-SEC-EN-MED and EC-SEC-EN-LRG
Ground and Power Wiring,
EC-SEC-EN-MNP and EC-SEC-EN-LNP
Ground Wiring,
Backup Batteries,
Knockout Locations,
Replacement Parts,
Information and specifications published here are current as of the date of publication of this document. Distech Controls, Inc. reserves the right to change or
modify specifications without prior notice. The latest product specifications can be found by contacting our corporate headquarters. Products or features con-
tained herein may be covered by one or more U.S. or foreign patents. NiagaraAX Framework is a trademark of Tridium Inc. © 2009 - 2013 Distech Controls,
Inc.
Medium & Large Enclosure Security Hardware Installation Guide
Part Number 05DI-HIENCML-13
Hardware Installation Guide
AX
Security or EC-BOS-616
Description
AX
Security controller or 2
controller with up to 4
AX
page 3
page 4
page 6
page 8
page 8
page 9
page 10
page 11
page 12
Updated: January 2014
AX
Security controller (EC-BOS-n
EC-SEC-EN-MED
EC-SEC-EN-LRG
AX
controller
All enclosures are NEMA type 1, with UL 294 Listing.
SECURITY
NOTE:
Separate documents cover the mounting and wiring
of EC-BOS-602
AX
Security and EC-BOS-616
Security controller and Remote Reader and Remote
IO Security expansion modules. Also, mounting
instructions for another small enclosure
(ENC-SEC-EN-SML) is in a separate document. See
"Related Documentation,"
All certifications and listing information related to an
EC-BOS
AX
Security system can be found in the
EC-BOS-602/616
AX
Guide document.
Security Enclosuress
AX
AX
Security),
Thumbnails
EC-SEC-EN-MNP
EC-SEC-EN-LNP
3TBZ
3TBZ
page 3.
Security Hardware Installation
AX
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EC-Net EC-SEC-EN-MED and is the answer not in the manual?

Questions and answers

Summary of Contents for Distech Controls EC-Net EC-SEC-EN-MED

  • Page 1 The latest product specifications can be found by contacting our corporate headquarters. Products or features con- tained herein may be covered by one or more U.S. or foreign patents. NiagaraAX Framework is a trademark of Tridium Inc. © 2009 - 2013 Distech Controls, Inc.
  • Page 2: Included In This Package

    Preparation Included in this Package Preparation Unpack the enclosure unit and inspect the contents of the package for damaged or missing components. If damaged, notify the appropriate carrier at once and return any damaged components for immediate repair or replacement. See “Returning a Defective Unit” in the EC-BOS-602/616 Security Hardware Installation Guide.
  • Page 3: Safety Precautions

    Precautions Safety Precautions Precautions This document uses the following warning and caution conventions: Cautions remind the reader to be careful. They alert readers to situations where there is a chance Caution that the reader might perform an action that cannot be undone, might receive unexpected results, or might lose data.
  • Page 4: Installation Summary

    Installation Summary Removing and replacing the enclosure door Installation Summary Installation of the medium or large Security Enclosures is covered in the following main sections: Pre-Installation, page 4 • Mounting and Dimensions, page 6 • Earth Grounding and Power Wiring, page 8 •...
  • Page 5 Pre-Installation Locate and remove enclosure knockouts Locate and remove enclosure knockouts The Security Enclosures has numerous knockouts on the top, sides, and bottom (see figure on page 11). Locate and remove any knockouts required for conduit and cabling entering the unit, before mounting it to the wall. In addition, install the appropriate conduit or cable clamps to the removed knockouts.
  • Page 6: Mounting And Dimensions

    Mounting and Dimensions Locate and mark mounting holes Locate and mark mounting holes The Security Enclosures has four main mounting holes on its back wall—the upper two holes are keyhole types. It is often convenient to mark the location of the mounting holes in the wall before continuing. Procedure 5 Locate and mark enclosure mounting holes.
  • Page 7 Mounting and Dimensions Locate and mark mounting holes Figure 2 EC-SEC-EN-MED, EC-SEC-EN-MNP medium enclosure wall mounting details. 1.0" 15.0" (25.4) NOTE: All dimensions given (381.0) in " inches and (mm). R. 0.110" (2.8) 2.5" EC-SEC-EN-MED (63.5) 0.438" (11.1) 8.25" 0.406" (209.6) (10.3) 15.0"...
  • Page 8 Earth Grounding and Power Wiring EC-SEC-EN-MED and EC-SEC-EN-LRG Ground and Power Wiring Earth Grounding and Power Wiring The Security Enclosures must be connected to a nearby earth ground. If a unit with an integral power supply, wire ground to the unit’s 3-position terminal strip, along with power •...
  • Page 9 Earth Grounding and Power Wiring EC-SEC-EN-MNP and EC-SEC-EN-LNP Ground Wiring Procedure 6 (EC-SEC-EN-MED or EC-SEC-EN-LRG only) Power and ground wiring. Remove power from the AC circuit being wired to the Security Enclosures power supply—see Step 1 previous Warning on page 8. Route the AC circuit wiring (Line, Ground, Neutral) through conduit in the top left area of the enclosure, Step 2 and terminate to the 3-position terminal strip.
  • Page 10: Backup Batteries

    Backup Batteries EC-SEC-EN-MNP and EC-SEC-EN-LNP Ground Wiring Backup Batteries If the EC-SEC-EN-MED or EC-SEC-EN-LRG enclosure will house an EC-BOS-n controller, after mounting it you can use the bottom of the enclosure to place one or two 12V sealed lead-acid backup batteries. See Figure 5 for an example of locating two batteries.
  • Page 11: Knockout Locations

    Knockout Locations EC-SEC-EN-MNP and EC-SEC-EN-LNP Ground Wiring Knockout Locations Figure 6 provides the locations of knockouts in both the Medium and Large enclosure models. Two knockout sizes are used: 0.95" (24.1mm) - for 1/2" conduit, and 1.20" (30.5mm) - for 3/4" conduit. Figure 6 Knockout numbers and locations for Medium and Large enclosures.
  • Page 12: Replacement Parts

    (EC-SEC-EN-LRG or EC-SEC-EN-LNP) security enclosure. 07CBL-TR10764 Battery wiring harness. 06KEY-TR10765 Enclosure door key lock with 2 keys. 06SWT-TR10781 Replacement tamper switch. EC-NPB-PWR-UN Only for EC-SEC-EN-MED or EC-SEC-EN-LRG enclosures with integral power supply: DIN-mountable 30W, 15Vdc power supply. 05DI-HIENCML-13 Distech Controls Inc. www.distech-controls.com 05DI-HIENCML-13...

Table of Contents