VAMP 260 Operation And Configuration Instructions

VAMP 260 Operation And Configuration Instructions

Power monitoring unit
Table of Contents

Advertisement

Quick Links

VAMP 260
Power monitoring unit
Operation and configuration
instructions
Technical description

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 260 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for VAMP 260

  • Page 1 VAMP 260 Power monitoring unit Operation and configuration instructions Technical description...
  • Page 2 VAMP 260 Power monitoring unit VAMP Ltd Operation and configuration Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 3: Table Of Contents

    6. PC software................30 6.1. PC user interface.............. 30 6.1.1. Using the VAMPSET program......... 30 6.2. Remote control connection........... 30 7. Commissioning configuration..........31 7.1. Factory settings..............31 7.1.1. Configuration during commissioning ....31 VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 4: General

    The unit is based on the same hardware and software as the protection relays. The setting and programming possibilities are comprehensive and versatile. The VAMP 260 us ideal for utility, industrial, marine and off- shore power distribution management. Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 5: Operating Safety

    Any operational measures must be carried out according to national and local handling directives and instructions. Carefully read through the relay operation instructions before any relay operational measures are carried out. VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 6: User Interface

    Operation and configuration User interface 2.1. General The VAMP 260 power-monitoring unit can be controlled in three ways: Locally with the push-buttons on the unit front panel • Locally using a PC connected to the serial port on the front •...
  • Page 7: Display

    VAMP 260 Operation and configuration 2.2.1. Display The VAMP 260 is provided with a backlit LCD dot matrix display. The display is divided into sections as shown in the next figure. Figure 2.2.1-1. Sections of the LCD dot matrix display.
  • Page 8: Indicators

    Error Internal unit fault, operates in parallel with the self supervision output relay Serial communication indicator Alarm Application- related status indications Trip Application- related status indications Application- related status indications Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 9: Local Panel Operations

    The possible navigating directions in each part of the menu are shown in the upper left corner by means of the black triangular symbols. VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 10 Figure 3.1-1. The principles of the menu structure and navigation in the menus. 6. Push the INFO key to obtain additional information about any menu item. 7. Push the CANCEL key to revert to the normal display. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 11: Function Menu Table

    • IL2 WAVEFORM • IL3 WAVEFORM • LINE VOLTAGES • PHASE VOLTAGES • RMS VOLTAGES • ANGLE DIAGRAM 1 • ANGLE DIAGRAM 2 • SYMMETRIC VOLTAG • HARM. DISTORTION • VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 12 Q DEMAND • S DEMAND • S RMS DEMAND • Evnt EVENT COUNT • EVENT LIST • DISTRUBANCE RECO • REC. COUPLING • Runh DI TOTAL TIME • START&STOP TIME • Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 13 • AO4 EXCEPT. CTRL • Imax IL MIN/MAX • IL1 MIN/MAX • IL2 MIN/MAX • IL3 MIN/MAX • Io MIN/MAX • I1 MIN/MAX • I2 MIN/MAX • I2/I1 MIN/MAX • VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 14 • FREQ. MIN/MAX • Mean USER’S AVERAGES • USER’S AVERAGES • MEAN VALUE 1 – 8 • Alrm ALARM STATUS • ALARM1..4 Ena • ALARM5..8 Ena • BLOCKING SIGNALS • Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 15 DATE/TIME SETUP • CLOCK SYNC • CLOCK SYNC 2 • PROTOCOL • MODBUS • SPABUS SLAVE • ProfiBus DP • IEC-60870-5-103 • TCP/IP • Diag DIAGNOSIS • OPSYS DIAGNOSIS • VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 16: Operating Levels

    9999. 3.2.1. Opening operating levels 1. Push the INFO key and the ENTER key on the front panel. ENTER PASSWORD Figure 3.2.1-1. Opening an operating level Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 17: Changing Passwords

    RIGHT key and then setting the desired digit value using the UP key. 3. Push ENTER. 3.2.2. Changing passwords The set passwords can only be changed using a PC connected to the local RS-232 port on the unit. VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 18: Operating Measures

    1. Move to the initial display, from the alarm list, by pushing the CANCEL key for approx. 3 s. Then reset the latched indicators and output relays by pushing the ENTER key. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 19: Reading Event Register

    2. Move to the setting state of the desired function, for example DO (see chapter 5, on page 22). 3. Select the Force function (the black cursor is in line with the Force text). VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 20: Setting Range Limits

    ENTER key. Adjust the setting to within the allowed setting range. The allowed setting range is shown in the display in setting mode: 1. Push the INFO button. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 21: Adjusting Display Contrast

    The readability of the LCD varies with the brightness and the temperature of the environment. The contrast of the display can be adjusted via the PC user interface, see chapter 6 on page VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 22: Configuration And Parameter Setting

    If the value contains more than one digit, use the LEFT and RIGHT keys to step from digit to digit, and the UP and DOWN keys to change the digits. 6. Push the ENTER key to accept the new value. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 23: Disturbance Recorder Menu Dr

    Manual trigger (MnlTrig) • Count of ready records (ReadyRe) • REC. COUPLING Add a link to the recorder (AddLink) • Clear all links (ClrLnks) • List of selected links • VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 24: Configuring Digital Inputs Di

    Forced control (0 or 1) of the Alarm relays A1…A3 Forced control (0 or 1) of the IF relay Configuration of the output signals to the output relays T1 • and T2, A1 – A3 and the operation indicators. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 25: Configuring Analogue Outputs Ao

    VALUE 8 the customized average measurements parameters Time, Unit and Lnk can be set and the State read. 2. Setting the Lnk parameter any one of the available variables of the relay can be set. VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 26: Setting Alarm Stage Parameters

    THDIL1, THDIL2, THDIL3 • U12, U23, U31, U, Umin, Umax, UL1 - UL3, Uphase, • Uphmin, Uphmax, Uo, U1, U2, U2/U1 THDUa, THDUb, THDUc • DI1 – DI6 • SW1, SW2 • Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 27: Protocol Menu Bus

    IP address of the Gateway (Gatew) • IP address of the Name Server (NameSv) • IP address of the SNTP Server (NTPSvr) • IP port number for protocol (Port) • VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 28: Configuration Menu Conf

    CLOCK SYNC 2 Sync message counter (MsgCnt) • Latest time deviation (Dev) • Filtered sync deviation (FilDev) • Cumulative deviation (I) • Max clock adjust (MaxAdj) • Min clock adjust (MinAdj) • Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 29 • Adjust save counter (ASC) • Big deviations, ext s (ESBD) • Big deviations, int s (ISBD) • Average RTC deviation (RTCdev) • Latest RTC adj time s () • VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 30: Pc Software

    REMOTE communication protocols (see details in Chapter 2.5.2 in technical description). Additional operation instructions for various bus types are to be found in their respective manual. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 31: Commissioning Configuration

    7.1.1. Configuration during commissioning The settings of the power monitoring unit VAMP 260 can be defined and checked during commissioning in accordance with the instructions given in chapter 5 of this manual. Basic parameters of VAMP 260:...
  • Page 32 Link 1-8, compare ALARM STAGE condition: Cmp1-8 1b-8b alarm limit of the stage: Set1-8 delay for alarm stages 1-8: t hysteresis for stages 1-8: Hyst1-8 no compare limits for stages 1-8: NoComp1-8 Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 33 4.5. Analogue outputs (option) ..........30 4.5.1. mA scaling examples ........... 31 4.5.2. Exception control of analogue outputs .... 33 4.6. Block diagram ..............34 4.7. Connection diagram ............36 VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 34 5.3. Disturbance recorder (DR) ..........40 6. Construction .................41 6.1. Dimensional drawing ............41 6.2. Panel mounting..............42 6.3. Semi-flush mounting ............42 7. Order information..............43 8. Reference information ............44 Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 35: Introduction

    The device measures the phase currents and the phase-to- phase voltages or phase-to-neutral voltages. Besides these directly measured data the VAMP 260 calculates much data about the state of the power network. 1.2.
  • Page 36 Built-in self-regulating dc/dc converter for auxiliary power • supply from any source within the range 40 to 260 V dc or ac, optionally 24 Vdc. Built-in disturbance recorder • Four programmable analog outputs (Option) •...
  • Page 37: Functions

    Technical description Functions The individual alarm stages of the power monitoring unit VAMP 260 can independently of each other be enabled or disabled according to the requirements of the intended application. See the configuration instructions, Chapter 5 and 7, in the first part of this manual.
  • Page 38: Power Calculations

    The minimum and maximum values of power factor, cosϕ and tanϕ are monitored and stored (see chapter 2.2.12). Power factor P.F Measuring range -1 - 0 0 - 1 Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 39 Complex conjugate of the measured phase L1 current phasor. Measured line voltage L2-L3 phasor, fundamental frequency component Complex conjugate of the measured phase L3 current phasor. real imag ϕ VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 40: Energy Calculations

    Energies flown to both directions are calculated and displayed as separate values. Energy information can be obtained as energy pulses through the contact outputs, too. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 41: Energy Pulses

    Pulse length of active values / exported energy E-PULSE 100…5000 Pulse length of reactive DURATION exported energy 100…5000 Pulse length of active imported energy 100…5000 Pulse length of reactive imported energy VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 42 The peak pulse frequency will be 50000/10 = 5000 pulses/h. Set pulse length to 3600/5000 − 0.2 = 0.5 s or less. The trip relay lifetime will be 50x10 /190 h = 30 a. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 43: Harmonics

    FFT, from the 2nd to the 15th order and displays the values in a bar graph. Harmonics U & I Number of harmonics 2 – 15 Measuring range 0 – 100% VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 44: Total Harmonic Distortion (Thd)

    One of the most important power quality functions are sag monitoring and swell monitoring. VAMP provides separate monitoring logs for sags and swells. The voltage log is trigg, if any voltage input either decreases Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 45 %Un Average voltage value during the sag/swell in the input 3 Max1 %Un Maximum voltage value during the sag/swell in the input 1 Max2 %Un Maximum voltage value during the sag/swell in the input 2 VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 46: Voltage Interruptions

    On the other hand, if the limit U < is high and the voltage has been near this limit, and then there is a short but very deep dip, it will be recognized (Figure 2.2.9-2). Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 47: Demand Values

    The device calculates a 15 min average value of all the currents, voltages and powers. This value is a running average, which is updated once a minute. The minimum and maximum of the demand values are recorded. VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 48: Di Total Time Counters

    (See the setting parameters for details). The timer outputs are available for logic functions, block and output matrix. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 49 The status of each timer is stored in non-volatile memory when the auxiliary power is switched off. At start up, the status of each timer is recovered. VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 50: User Averages

    The user can configure the monitored value and the time frame inside which the average of the value is calculated. The time can be set from 1 second to 60 hours. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 51: Logic Functions

    1.00 – 900 s DI1 – DI6 100 ms SW1, SW2 The outputs of the alarm stages can control any combination of output relays and indicator LEDs, see Figure 2.6-1 and Figure 2.6-2 VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 52: Communication

    For connection to a PC, one RS 232 serial port is available on the front panel of the unit. Any connection to the port is done with the connection cable type VX 003-3. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 53: Remote Control Connection

    When the watchdog circuit detects a permanent fault it always blocks any control of the other output relays, except for the self- supervision output relay. VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 54 IF output relay functions on the working current principle, that is the IF relay is energized when the auxiliary supply is on and within the permitted range. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 55: Applications

    • Substation infeeder cubicle measurements • The above measurement needs can conveniently be fulfilled with VAMP 260, which also provides flexible connections to other systems utilizing the same measurement information: Serial bus connection to higher level logic systems or •...
  • Page 56: Generator Measurements (Three-Phase)

    40 - 265 V ac/dc Remote 18 - 36 V dc SPABus ModBus ProfiBus TCP/IP IEC-103 Local RS232 +48 V example1 Figure 3.1-1. VAMP 260 in generator measurement (three-phase connection) Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 57: Generator Measurement, Economy Circuit Connection

    40 - 265 V ac/dc 18 - 36 V dc Remote SPABus ModBus ProfiBus TCP/IP IEC-103 Local RS232 +48 V example2 Figure 3.2-1. VAMP 260 in generator measurement, economy circuit connection VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 58: Generator Measurement, Aron's Connections

    40 - 265 V ac/dc 18 - 36 V dc Remote SPABus ModBus ProfiBus TCP/IP IEC-103 Local RS232 +48 V example4 Figure 3.3-1. VAMP 260 in generator measurement, Aron’s connections Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 59: Measurement And Data Acquisition System Based On Vamp 260S And Communication Via Profibus

    Meteringex Figure 3.4-1. The measurement and data acquisition system of an industrial power network. The system is based on VAMP 260s and a PC control room, which are linked together via a serial bus. Energy pulses are available for Energy Management Systems.
  • Page 60: Power Monitoring Unit In A 400 V Network

    VAMP 260 Power monitoring unit VAMP Ltd Technical description 3.5. Power Monitoring Unit in a 400 V network Figure 3.5-1. Example of VAMP 260 voltage measurement connection Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 61: Connections

    VAMP 260 Technical description Connections Figure 4-1. Connections on the rear panel of the unit. The VAMP 260 measuring unit is connected to the protected object through the following measuring and control connections, Figure 4-1: Phase currents I and I (terminals X1: 1-6) •...
  • Page 62: Auxiliary Voltage

    VAMP Ltd Technical description 4.2. Auxiliary voltage The external auxiliary voltage Uaux (standard 40…260 V ac or dc) for the unit is connected to the terminals X3: 17-18. Note! Polarity of the auxiliary voltage Uaux (24 V dc, option B): - = X3:17 and + = X3:18.
  • Page 63: Ma Scaling Examples

    Figure 4.5.1-1. Example of mA scaling for IL, average of the three phase currents. At 0 A the transducer ouput is 0 mA, at 300 A the output is 20 mA VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 64 Figure 4.5.1-2. Example of mA scaling for Uline, the average of the line-to- line voltages. At 0 V the transducer ouput is 4 mA, at 15000 V the output is 20 mA Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 65: Exception Control Of Analogue Outputs

    4 ... 20 mA the exception control sets the output current to 2.50 mA whenever the average of the main voltages (or any other monitored value) goes below 1000 V. LINE VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 66: Block Diagram

    VAMP 260 Power monitoring unit VAMP Ltd Technical description 4.6. Block diagram Figure 4.6-1 Block diagram of the power monitoring unit VAMP 260. Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 67 VAMP Ltd Power monitoring unit VAMP 260 Technical description Figure 4.6-2 Block diagram of the power monitoring unit VAMP 260, with mA-option.. VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 68: Connection Diagram

    VAMP 260 Power monitoring unit VAMP Ltd Technical description 4.7. Connection diagram Figure 4.7-1 VAMP 260 connection diagram Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 69: Technical Data

    48 V dc Current drain when active (max.) Approx. 20 mA Current drain, average value < 1 mA Terminal block: Max. wire dimension: - Phoenix MVSTBW or equivalent 2.5 mm (13-14 AWG) VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 70: Trip Contacts

    Minimum output current 0 - 19 mA, step 1 mA Exception output current 0 - 20.50 mA, step 10 µA Resolution 12 bits Current step < 6 µA Inaccuracy ±20 µA Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 71: Tests And Environmental Conditions

    Operating temperature ° 0 to +55 Transport and storage temperature ° -40 to +70 Relative humidity < 75% (1 year, average value) < 90% (30 days per year, no condensation permitted) VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 72: Casing

    1 min Recording time (one record) 0.1 s – 12 000 min (must be shorter than MAX time) Pre trigger rate 0 – 100% Number of selected channels 0 – 12 Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 73: Construction

    Power monitoring unit VAMP 260 Technical description Construction 6.1. Dimensional drawing 28.0 181.0 27.0 208.0 190.0 >20.0 193.0 PANEL CUT-OUT 1.0-10.0 P200_ulkomitat_kannella Figure 6.1-1. Dimensional drawing and panel cutout dimensions. VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 74: Panel Mounting

    Semi-flush mounting 21.0 28.0 181.0 27.0 P200_semi-flush Figure 6.3-1. Semi-flush mounting of protection unit Depth with raising frames Type designation VYX076 40 mm 169.0 mm VYX077 60 mm 149.0 mm Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 75: Order Information

    TTL/RS232 Converter Cable ( for Modem MD42, ILPH, ..) Cable length 4m VYX076 Raising Frame for 200-serie Height 40mm VYX077 Raising Frame for 200-serie Height 60mm VM690/230 3 Phase Nominal Voltage Matching Transformer 690V->230V , 400V->110V VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 76: Reference Information

    Fax. +358 (0)20 753 3205 24h support phone: Tel . +358 (0)20 753 3264 Email: vampsupport@vamp.fi During office hours 6.00 - 14.00 GMT, please use the following telephone number +358 (0)20 753 3200 Vamp 24h support phone : +358 (0)20 753 3264 VM260.EN004...
  • Page 77 VAMP Ltd Power monitoring unit VAMP 260 Technical description VM260.EN004 Vamp 24h support phone : +358 (0)20 753 3264...
  • Page 78 We reserve the rights to changes without prior notice VAMP Ltd Street address: Yrittäjänkatu 15 Phone: +358 20 753 3200 Post address: Fax: +358 20 753 3205 P.O Box 810, FIN 65101 Vaasa, Intenet: www.vamp.fi Finland Email: vamp@vamp.fi VM260.EN004...

Table of Contents