Control Systems NetPoint 546A-X1 Installation Sheet

General purpose unit

Advertisement

Quick Links

Controller Installation

24 VAC
24VAC
AC PWR
Power Input
24VAC
24V
GROUND
GND
Plug-In LON
Mainentance Port
LON+
FTT
LON-
LON Port
LON
TB2
ANALOG
OUT
AO-1
Analog
AO-2
Outputs
AO-3
AO-4
GND
I/STAT Port
STAT
SIG
SIGNAL
12V
POWER
GND
GROUND
INPUTS
INPUT 1
INPUT 2
INPUT 3
Universal
INPUT 4
Inputs
+24V
GROUND
DIN Rail
Mounting
Clip
Figure 1. NP-546A-X1 (Covered)

Installation Notes:

Check the mounting location for the NP-546A-X1. The available
area must measure at least 4.3" × 8" (11 × 20.3 cm) and should be
in a moisture-free container away from any large electrical devices.
The screw holes are 3.75" × 7.5" (9.5 × 19.1 cm) as shown in
Figure
1, and will require phillips or slotted pan head screws.
The onboard velocity sensor requires that you install the controller
within four feet of the pickup probe in the air inlet duct of the VAV
box.
T
he onboard velocity sensor also requires that you mount the
Connecting Analog 0–10 VDC Output Devices
LON
TB2
ANALOG
OUT
AO-1
AO-2
0–10 VDC
Analog Input
AO-3
Actuator
AO-4
GND
Figure 3. Output Device Connections
Installation Sheet
3.75 "
(9.5 cm)
LED
Communications
Indicators
TRANSMIT
TX
D1
RECEIVE
RX
D2
Output Indicator
OUTPUT 1
1
OUTPUT 2
LEDs
2
OUTPUT 3
3
OUTPUT 4
4
OUTPUT 5
5
OUTPUT 6
6
8.00 "
7
8
20.3 cm
POWER
PWR
SERVICE
SVC
N1831
MODEL:
LED
SERIAL NO.:
POWER:
Service Request
24V ~ 14VA
(62 VA MAX)
Push Button
MADE IN USA
GROUND
BY:
CONTROL
OUTPUT 6
SYSTEMS
INTERNATIONAL
OUTPUT 5
P.O. BOX 59469
DALLAS, TX
OUTPUT 4
Triac Control
75229
OUTPUT 3
Outputs
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS
OUTPUT 2
1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE AND
2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED
OPERATION.
OUTPUT 1
607573-0006
4.30 "
(11 cm)
LON+
LON-
AO-1
AO-2
AO-3
AO-4
GND
NetPoint General Purpose Unit 546A-X1
(
)
NP-546A-X1
.
24 VAC Power Input
LON Port
I/Stat Port
Figure 2. NP-546A-X1 (Cover Removed)
controller on a vertical surface. Installing the controller with the
barb fittings of the velocity sensor pointing down will help prevent
condensate from migrating into the onboard sensor.
You will not need to remove the plastic cover to install the NP-
546A-X1, or any of the connections. To replace the 4A FB fuse,
remove the plastic cover, remove the old fuse and install a new fuse
(see
Figure
2)
1. Connect the analog device to TB3-1 through TB3-4 (AO1 to AO4,
see
Figure
3).
2. Connect the ground wire of the device to the signal ground
terminal, TB3-5 (GND).
4-A FB ReplaceableFuse
LED Communications
Indicators
Service
Switch
Use the P3 Connector to
connect the X1 Sensor.
TCON289 12/00

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NetPoint 546A-X1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Control Systems NetPoint 546A-X1

  • Page 1 NetPoint General Purpose Unit 546A-X1 NP-546A-X1 Controller Installation 24 VAC Power Input 4-A FB ReplaceableFuse 3.75 " (9.5 cm) 24 VAC 24VAC AC PWR Power Input 24VAC GROUND Plug-In LON LON Port Mainentance Port Communications LON+ Indicators LON- LON Port ANALOG AO-1 Analog...
  • Page 2 NP-546A-X1 Installation Sheet TCON289–12/00 Connecting Contact, Thermistor, or Voltage (0–5 V) Sensors Warning! Ensure that no power is connected to the NP-546A-X1 during electrical installation. Failure to disconnect GROUND power from all interconnected equipment when INPUTS performing electrical installation may result in damage INPUT 1 to the components and/or electrical shock or burns.
  • Page 3 NP-546A-X1 Installation Sheet TCON289 – 12/00 Connecting the FTT-10A 1. Connect one lead of the twisted pair LON ¬cable to terminal TB2- 1 (LON+, see Figure 2. Connect the other lead of the twisted pair LON cable to terminal 24VAC TB2-2 (LON –).
  • Page 4 (Belden 9184 equivalent) 100 feet (30 m) maximum from the controller. Total capacitance CE Marked for EC Compliance may not exceed 4 000 pF. Approved and marked in accordance with Australian EMC Framework www.csi-controls.com  2000 by CSI Control Systems International, Inc. All rights reserved.