Bi-polar Ionization Series OUR MISSION IMPORTANT To design and build quality engineered air cleaning systems Save this Document to provide indoor comfort, protect occupants, and ensure the for Future Reference & Bioclimatic.com reliability of critical systems and processes. Warranty Information 356-JAN-2022...
Page 2
■ Pay close attention to all warnings and caution notices given in this guide. How to Contact Us: If you need help, please contact a Bioclimatic Air Systems Representative for technical assistance. !CAUTION! Do not touch while in operation shut off electricity before servicing! This equipment should be inspected frequently and collected dirt removed from it regularly to prevent excessive accumulation that may result in flashover or risk of fire.
1.1 Disclaimer These instructions are submitted with the implicit understanding that: 1. This manual is to guide the user of Bioclimatic equipment in the proper installation, operation and maintenance procedures to insure maximum equipment life with efficient operation. 2. The customer has assigned competent maintenance and operating personnel to the system described herein and will assume operational and maintenance responsibility upon start-up of the system.
(CDC). Clean Air Group does not maintain that its products will protect people from all modes of transmission of bacteria, viruses or other contaminants, and excludes liability for loss or damage arising from any such claims or the consequences arising out of the application, use or misuse of its products. 1-800-394-3458 356-JAN-2022 Bioclimatic.com...
■ The variable two level control circuit is contained within the generator housing. ■ All calibrations are performed (only by Bioclimatic Air Systems) on the generator circuit board. ■ The output voltage is varied by the “Hi / Lo” switch – Hi is 2350 VAC, Low is 2100 VAC.
NOTE: Ozone is a by-product of any ionization process. When installed and operated in accordance with manufacturer instructions, the Bioclimatic System will not generate ozone in excess of the standards specified by OSHA and FDA. Under normal operating conditions, there will not be measurable levels of ozone.
3.2 Installation Install the Bioclimatic unit in accordance with the following guidelines. 3.2.1 After selecting the best location for the Aerotron system, arrange the unit(s) across the plenum’s width in accordance with Aerotron Equipment Arrangement Instructions, Bulletin 163, found in our Engineering Catalog, Tab 3.
Bioclimatic Air Systems provides guidance in order to simplify the wiring connections. In the event the below listed conditions are not present, then a maximum of six (6) of the same unit may be connected to a dedicated circuit. When the quantity of the same unit precludes the use of a dedicated circuit, use an isolation transformer.
(for remote monitor). Ensure there is sufficient airflow in the system. To disconnect the System – turn to the “Off” position power switches. The calibration procedure for the remote monitors is fully described in the “Bioclimatic Remote Monitor Installation, Operation and Maintenance Manual”.
Ensure all wiring connections between the circuit breaker There is a faulty wiring connection between the circuit breaker and Remote Monitor (Aerotron unit) are secure and and the Remote Monitor or Aerotron unit. correct. Refer to custom wiring diagram. 1-800-394-3458 356-JAN-2022 Bioclimatic.com...
NOTE: FOR STABLE OPERATING CONDITION OF THE SYSTEM(S) WE RECOMMEND TO CONNECT EACH REGULATED GENERATOR (IF MORE THAN ONE) TO DEDICATED CIRCUIT (LINE, PHASE) OR USE ISOLATION TRANSFORMER(S). 06 SPECIFICATIONS Aerotron 30 Electrical: Power Requirement 115 / 230 VAC, 1 phase 50/60 Hz...
Page 13
84 / 87 VA Sensing Voltage 2.37, 2.68 VAC ±0.05 Power Regulator Gate controlled triac IG-100-8ZF 78 / 84 VA IG-100-7ZF 72 / 80 VA Mechanical Refer to Drawings IG-100-6ZF 68 / 77 VA Environment Indoor Only 1-800-394-3458 356-JAN-2022 Bioclimatic.com...
Page 20
FAULT (1) > 1250 1.35 AMBER R 28 MIN LOW LIMIT UNDER ± 25 VAC NOTES: 1. THE WORD “FAULT” IS USED TO INDICATE ABNORMAL OPERATING REGION AND/OR POTENTIAL EQUIPMENT 2. KEY VOLTAGES ARE SHOWN WITH > 1-800-394-3458 356-JAN-2022 Bioclimatic.com...
Installation, Operation & Maintenance Guide Bi-polar Ionization Series 07 PRODUCT NUMBERS* Aerotron Generators AEROIG-100R-115-STD-DUCT AEROIG-100R-230-STD-DUCT AEROIG-30R-230-STD-DUCT AEROIG-50R-115-STD-DUCT AEROIG-50R-230-STD-DUCT *If your specific model is not listed please contact the factory at: 1-800-394-3458 for operating instructions, safety information and replacement parts or service. 1-800-394-3458 356-JAN-2022 Bioclimatic.com...