Download Print this page

Liton LCALD8 Instructions

Cannon led pendant architectural downlight

Advertisement

Quick Links

CATALOG # :
LCALD8
Important: Please read and understand all instructions completely before installing
this fixture.
WARNING: Fixture installation (and use) and all electrical connections must be in accordance with
local and National Electrical Codes (N.E.C.) rules, regulations and standards. If you are unfamiliar
with installing fixture(s), accessories and/or electrical wiring have a qualified licensed electrician
install this fixture for you. Fixture should be installed by a qualified electrician.
WARNING: RISK OF SHOCK. House electric current can cause painful shock or serious injury.
WARNING: Always disconnect power before fixture installation, wiring, or maintenance.
WARNING: Before starting the wire connections, disconnect the power by turning off the circuit
breaker or removing the fuse at the fuse panel. Turning the power off using the light switch is not
sufficient to prevent electrical shock.
This luminaire must be connected with supply wire/conductors rated at 90°C. Most dwellings built
before 1985 have supply wire rated at 60°C; consult a qualified electrician before installing.
WARNING: Before service insure fixture is cool to touch.
WARNING: Check fixture for input voltage before connecting power to fixture.
Components / Parts (LCALD8 Only)
9-5/16"
Ø8-5/8"
(Side View)
LCALD8 HOUSING
LCALD8 shown with 20 ga. Wire Guard
installed in fixture
(Come pre-Installed in LCALD8 fixture)
5461 W. Jefferson Blvd. Los Angeles, CA 90016 • P. 800-515-4880 • F. 800-972-4880 • www.liton.com Product specifications subject to change without notice.
LCALD8 : 8" Lumen Cannon LED Pendant Architectural Downlight
Ø8-5/8"
(Bottom View)
LCALD8 (1)
NOTE: For wire guard (installed in the fixture) removal see step 1-4 below. If not needed skip to step 5.
Removing the Wire Guard From The Fixture
Warning: Make sure fixture in not installed and is disconnected fixture from power supply. Disassemble fixture on a table or other flat
surface to avoid loosing screws or breaking the glass lens (with gasket).
1. Remove the 5 screws with the M3 allen key (by others).
2. Remove Trim and Wire Guard from fixture while keeping the glass with gasket (not shown) in place.
3. Check to make sure that the gasket and glass are in place before putting the trim back on the fixture.
4. Replace Trim over the gasket with gasket and secure with scews by replacing the screws in the stem and tightening with the M3
LCALD8 Trim
allen key. Tighten securely until tight but do not over tighten screws.
5. Go to the following instruction page(s) for your type of fixture mounting option:
Ceiling Mount Instruction:
(5) Socket Head
• Adjustable Stem Assembly (-STM6, -STM12, -STM24, -STM36, & , -STM48):
Screws
Parts List ............................................................ Page 2
(M3 allen Key)
Installation ......................................................... Page 3
Cutting the Field Adjustable Stem to Length ............. Page 4
SAVE THESE INSTRUCTIONS
Keep these instructions in a safe place for future use/reference.
WARNING: RISK OF SHOCK. This fixture is suitable for dry and damp locations. Also for use with
covered ceiling mount.
WARNING: Do not install any fixture or assembly (etc.) closer than 6" from any curtain, or similar
combustible material.
Fixture must be installed on a circuit protected by Ground Fault Circuit Interrupter (GFCI).
Install LED fixture(s)/LED driver(s) only on their own circuit. Do not mix any other products
(Incandescent, Compact Fluorescent, H.I.D. products/fixtures, etc...) with LED fixture(s)/LED
driver(s) on a single circuit.
Do not use any other electrical equipment (example: surge protector photocell, etc.) that is not
(rated) for use with LED fixture(s)/LED driver(s) on the same circuit as LED fixture(s)/LED driver(s).
Install remote surge protector(s) (by others, goes on the circuit with nothing between the surge
protector and the LED fixture(s)/LED driver(s)), if the fixture is not already installed with a surge
protector, to help remove power surges that may harm LED fixture(s), appropriate for the
installation. Periodically check and make sure that your remote surge protector(s) are in good
working order.
20 ga. wire guard (1)
(Installed in LCALD8)
Page 1
Tools Required
• Adjustable Wrench
• M3 Allen Key
• Wire Connectors
• Hardware (screws, nuts,
etc.)
• DO NOT USE POWER
TOOLS. ONLY USE HAND
TOOLS.
08082021

Advertisement

loading

Summary of Contents for Liton LCALD8

  • Page 1 Cutting the Field Adjustable Stem to Length ..... Page 4 LCALD8 shown with 20 ga. Wire Guard installed in fixture (Come pre-Installed in LCALD8 fixture) 5461 W. Jefferson Blvd. Los Angeles, CA 90016 • P. 800-515-4880 • F. 800-972-4880 • www.liton.com Product specifications subject to change without notice. 08082021...
  • Page 2 PCT042-12 (12” Long) PCT042-24 (24” Long) PCT042-36 (36” Long) PCT042-48 (48” Long) Stem, 3/8” IPS (5/8” O.D.) 5461 W. Jefferson Blvd. Los Angeles, CA 90016 • P. 800-515-4880 • F. 800-972-4880 • www.liton.com Product specifications subject to change without notice. 08062021...
  • Page 3 • Not for chemical or pool corrosive environments. • To prevent the LCALD8 fixture with the Adjustable Stem Assembly from falling during installation secure the LCALD8 fixture with the Adjustable Stem Assembly to the j-box with a cable (by others).
  • Page 4 1/8” drilled hole on opposite side of stem and into Half Ball. When finished return to page3 of 4 to install Adjustable Stem Assembly (STM) in fixture. 5461 W. Jefferson Blvd. Los Angeles, CA 90016 • P. 800-515-4880 • F. 800-972-4880 • www.liton.com Product specifications subject to change without notice. 08092021...