ES-1E Field Installation Manual INDEX Important Instructions……………………………………………………………………………. 2 Product Specifications……………………………………………………………....3 Unpacking & Mounting ………………………………………………………….……………. Connection Type 1 …………………………………………………………………....Connection Diagram ………………………………………………..………………………… Connection Type 2 ……………………………... ……………………………………………. Connection Type 3 ……………………………………………………………………………… Electrical Data Sheet ………………………………………..…………………………………. Recommended Part List…………………………………………………..……………………. 10 ES-1E...
Any warning provided by Celec must be passed through to the end user. Celec offers a warranty only as to the quality of its product to confirm to the catalog specifications. No other warranty is offered. Celec assumes no liability for any personal injury, property damage, losses or claims arising out of the misapplication and Non performance of its products.
Page 3
Model: ……………………………………………………………………………… ES-1E Rated Voltage……………………………………………………………………… 240V AC Phases………………………………………………………………………………… Single Phase 120/240V AC Rated Frequency………………………………………………………………… 60Hz Maximum Current…………..……………………………………………….… 14 Amp per phase Maximum kVar...………………………………………………………………… 3.3 Maximum Ambient Temperature ……..……………………………..… 40 Enclosure……………………………………………………………………………… Type 1 Connection Connection Wire Type & Torque N-m Size...
CAUTION Indoor Use Only, Type-1 Enclosure. 1. Choose the dry and Clean Wall to Install the ES-1E taking care conduit connections from Bottom side Enclosure Size is 300 x 200 x 120 mm and weight 6kg (13 Pounds). 2. Premark the Mounting holes on wall or structure.
1.11 Remove the Panel cover of ES-1E exposing internal connections. 1.12 Locate Earth Terminal in ES-1E, connect the earth wire to ES-1E Earth Terminal. Connect the other side of earth wire to main breaker panel ground rod. Ensure all mechanical connections are secure and making full contact.
ES-1E unit is designed for use with Customer Main Breaker Panel Single Phase 120/240V AC up to 200 Amp. ES-1E units should be mounted with four appropriate sized fasteners before connect to Main Breaker Panel. Remove Main Panel covers exposing internal wiring and breakers.
2. Wire in rigid conduit between customer main breaker panel & external disconnect switch. Connect to ES-1E using 1/2‘’conduit. 3. Locate earth ground connection in ES-1E and connect to grounding bar or to earth ground rod in main breaker panel.
ES-1E Field Installation Manual Electrical Data Sheet Model ES-1E Phase Configuration Single Phase 120/240V AC Maximum Line Voltage 240V AC Maximum Power 3.3 kVar Indicator Power , Saving Accuracy 0.1 kVar Frequency 60Hz Protection Capacitor Inbuilt Protection P2 Equipment Protection Internal design has adequate clearance and creepage distance against line transients.
Installation of material and workmanship at the customer’s Main Breaker Panel shall be the responsibility of the qualified Electrician in accordance with NEC. Any and all connections exterior to the ES-1E unit shall be the responsibility of the qualified Electrician. ______________________________________________________________________________________...