Well-Connect WCVC-16 Installation Manual page 10

Hide thumbs Also See for WCVC-16:
Table of Contents

Advertisement

b. Volume: Most jet pumps struggle to move more than a couple gallons per minute at
the higher pressures experienced toward the end of a pump cycle. This means the
pump may run for a very long time trying to "catch up" and cycle off; many never
do, and will run continuously as long as the Well-Connect is on. This situation is
more likely to occur with the 2.5-ton Well-Connect than with the 1.5-ton, but the
issue may arise with either model. While not detrimental to the Well-Connect
itself, this can result in markedly higher than expected overall power consumption.
Supply water for the Well-Connect must be obtained by tapping into the main household
water supply piping. ¾" PEX is often the most convenient material to use for this
purpose, but copper, PVC, or CPVC may also be used. Connect the supply water line
ahead of (before) any water softener or household iron filter if present, as the Well-
Connect does not require softened water.
A spin-down type water filter is included with every Well-Connect (See Figure 3). This
must be installed somewhere in the supply water piping, in an accessible location and
with a shut off valve ahead of it to allow for easy cleaning. There should also be shut off
valves on the supply and discharge lines where the included hoses will connect to the
building plumbing for ease of installation and maintenance (See Figure 4). Plan to place
these within a couple feet of the back of the Well-Connect.
Figure 3
Follow all applicable state and local codes regarding water piping materials and practices,
and insulate all water lines that run through any area of the building or home where
condensation is undesirable.
Discharge
Supply
Figure 4
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wcvc-24

Table of Contents