Specifications
Input Voltage:
Sensing Voltage:
Frequency:
Voltage Regulation:
Parallel Operation
Output Voltage:
Maximum Continuous Output:
Minimum Field Resistance:
Regulation Type:
Physical Size:
Weight:
Voltage Regulator:
Firing Module:
Internal Build-Up Provisions:
Repairable:
Internal Protection:
External Voltage Adjustment:
Loss Of Sensing Protection:
© 2014 Power-Tronics, Inc.
208 - 240vac, 3ø
120vac, 3ø
50 or 60 Hz
+/- 1% From NL to FL
Yes
0-250vdc @ 240vac input
600adc
.42Ω @ 250vdc output
Flat Response
32 x 36 x 12 in.
95 lb.
VM120-3C
FM4
Optional
Yes
Fuses, cartridge type
Yes
Yes
SE6000B-3P
3-Phase Static Exciter
The Power-Tronics SE6000B-3P 3-Phase
Static Exciter is a self-contained complete
Static Exciter. The SE6000B-3P 3-Phase
Static Exciter is designed for continuous
operation at up to 250vdc at 600adc!
The SE6000B-3P is uniquely designed to
sit in a compact footprint while being
passively convection cooled for a long
service life. Because of its unique
modular design, the SE6000B-3P
minimizes downtime should a repair ever
be necessary! The SE6000B-3P's
compact design allows a wide variety of
installation methods, including installations
where space is at a premium.
The SE6000B-3P is a time-proven design,
utilizing high-reliability components and a
unique modular design to simplify repair.
This product also features loss of sensing
protection. If the sensing voltage is lost,
the unit will shut down to prevent
catastrophic damage caused by runaway
voltage!
The SE6000B-3P is also capable of
parallel operation with other generators or
with a utility buss. Power-Tronics' wide
variety of optional accessories also allows
the SE6000B-3P to be remotely operated
by dry contact switching or by a PLC
controller!
The SE6000B-3P is designed to provide a
lifetime of service and is specifically built to
minimize failures and potential downtime!

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SE6000B-3P and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Power-Tronics SE6000B-3P

  • Page 1 Regulation Type: Flat Response Physical Size: 32 x 36 x 12 in. Weight: 95 lb. The SE6000B-3P is designed to provide a Voltage Regulator: VM120-3C lifetime of service and is specifically built to Firing Module: minimize failures and potential downtime!
  • Page 2: Table Of Contents

    Determining Application Sizing:...................4 Connection Diagram:.....................6 Connection Diagram for Models With Optional Internal UIC200:......7 Creating an External Flashing Circuit:.................8 SERCP-3P Removable Control Panel:................9 Initial Setup and Commissioning:................11 Application Troubleshooting:..................12 Bench Check Procedures:...................13 Installation Warranty Form:..................14 Product Warranty Certificate:..................15 © 2014 Power-Tronics, Inc.
  • Page 3: Introduction And Functional Description

    (It can give a false reading!) Functional Description The SE6000B-3P 3-Phase Static Exciter is the result of over 20 years of engineering efforts and offers high-demand features at a competitive price point. The SE6000B-3P is a proven design and is engineered to greatly simplify setup while offering extreme reliability.
  • Page 4: Determining Application Sizing

    SE6000B-3P is the correct product for your application. To determine if the SE6000B-3P is the correct product for your generator you need to know any two of the following 3 specifications from the rating plate of your generator:...
  • Page 5 R is your measured field resistance. Using the values you just measured and calculated, see the chart on the previous page to determine whether the SE6000B-3P is the correct product for your application. © 2014 Power-Tronics, Inc.
  • Page 6: Connection Diagram

    DO NOT input 277VAC into the SE6000B-3P! Severe damage to the unit will result! For use on 480V systems, either connect the SE6000B-3P to the winding center taps T7, T8, and T9 or use a 480-240V step-down transformer. Paralleling CT should have 5A...
  • Page 7: Connection Diagram For Models With Optional Internal Uic200

    240VAC 3ø! DO NOT input 277VAC into the SE6000B-3P! Severe damage to the unit will result! For use on higher voltage systems connect the SE6000B-3P to an appropriately sized step-down transformer. Paralleling CT should have 5A secondary with a 25VA burden...
  • Page 8: Creating An External Flashing Circuit

    The SE6000B-3P can be ordered with an internal flashing circuit, or use an external flashing source to bring the generator up to voltage during startup.
  • Page 9: Sercp-3P Removable Control Panel

    SERCP-3P Removable Control Panel The SE6000B-3P 3-Phase Static Exciter features a removable control panel for convenient relocation of the control module and firing module to a location closer to the main switchboard and can be configured to meet the needs of your application. The...
  • Page 10 To detach the removable control panel from the SE6000B-3P, simply remove the 4 1/4- 20 nuts that hold it to the main chassis and remove the wires from TB1 and TB2. Install the control panel in the desired location, and then reconnect the wiring as originally shown.
  • Page 11: Initial Setup And Commissioning

    Initial Setup and Commissioning Install the SE6000B-3P and wire up to the correct wiring diagram (Standard hookup, or optional internal UIC200). If installing the SE6000B-3P on a brush-type generator, verify that the brushes and brush riggings are isolated, ungrounded, and connected ONLY to the SE6000B-3P.
  • Page 12: Application Troubleshooting

    22. Damaged, pitted, or grooved slip ring surface. 23. Current transformer has reversed polarity or is not shorted during non parallel operation. 24. Input to regulator is from an auxiliary winding and not the generator main stator. © 2014 Power-Tronics, Inc.
  • Page 13: Bench Check Procedures

    Turn the internal voltage adjustment on the VM120-3C Voltage Regulator fully Counter-Clockwise (Left) before beginning the testing procedures below. Input 208-240VAC, 3ø fused at no more than 5A into the SE6000B-3P and input 120VAC 3ø into terminals A, B, and C on TB3. The test light should be OFF.
  • Page 14: Installation Warranty Form

    It is very important that you fill out this form completely when installing a voltage regulator. This form serves as a history record on the application. This form also contains the information needed by Power-Tronics, Inc., for repair and troubleshooting of any product you may be having problems with.
  • Page 15: Product Warranty Certificate

    These problems should be protected with external devices provided by the customer such as fuses, surge suppressors, over/under voltage and frequency controls. Power-Tronics, Inc., warranties only parts and workmanship of this product for a period of 2 years from the original date of purchase from Power-Tronics, Inc. Under warranty, Power- Tronics, Inc.