Page 1
TYNEHAM AHP60 Air/water monobloc heat pump INSTALLATION, COMMISSIONING AND SERVICING INSTRUCTIONS Models: 50 and 70 kW IMPORTANT NOTE THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING, OPERATING OR SERVICING EQUIPMENT...
Page 2
Site Assembly Hamworthy offer a service of site assembly for many of our products in instances where plant room area is restricted. Using our trained staff we offer a higher quality of build and assurance of a boiler built and tested by the manufacturer.
AHP60-50/70 - Installation, Use and Maintenance CONTENTS 1. REGULATIONS, RECOMMENDATIONS AND WARNINGS ..............5 1.1. Applicable regulations and standards ......................5 1.2. Recommendations and warnings ......................... 5 2. DESCRIPTION OF THE EQUIPMENT ................15 2.1. Designations and scope ..........................15 2.2. Packaging ..............................15 2.3.
Page 4
7.5. Cleaning the external surfaces ........................65 7.6. Maintenance of the outdoor unit ........................65 7.7. Residual safety risks ........................... 66 7.8. Heavy maintenance work ..........................67 7.9. “Maintenance” check list ..........................68 8. END OF PRODUCT LIFE- ....................74 DATA FOR PRODUCTS ≤ 70KW ............76 9.
1. REGULATIONS, RECOMMENDATIONS AND WARNINGS 1.1. Applicable regulations and standards This outdoor heat pump has been designed in accordance with current regulations and must be used accordingly. See the list of standards on the back cover. This device must be transported in compliance with the Local Laws. This device and its refrigerant R32 must be handled in compliance with the application orders of the F Gas regulations.
Page 6
The elements indicated below are not exhaustive given the diversity of the possible installations and interventions; they cannot be considered as an undertaking as to the responsibility of Hamworthy Heating. These elements cannot replace a risk analysis, which remains the responsibility of the installer and the personnel working on the machines.
Page 7
MEASURES IN THE EVENT OF AN ACCIDENTAL LEAK Use personal protection equipment. Evacuate the personnel to safe areas. Individual precautions: Eliminate ignition sources. Ensure there is adequate ventilation. Environmental precautions: Try to stop the leak. Cleaning methods: Ventilate the area. HANDLING AND STORAGE Handling: Ensure that the premises have adequate air renewal/extraction .
Page 8
TOXICOLOGICAL INFORMATION High toxicity: LD/LC50/inhalation/4 hours/rat test = 1107000 mg/m3. Local effects: No known effects. Long term toxicity: No known effects. ENVIRONMENTAL INFORMATION Global warming potential GWP (R744=1): Ozone damage potential (R11=1): Of the ozone ODP (R11=1): Comply with the supplier’s gas collection programme. Avoid direct Disposal Considerations: emission into the atmosphere.
Page 9
at least 80% of the wall (or the equivalent if more than one wall is open to the outside air), is considered to be open to the outside air. It must be located so that no refrigerant leaks can enter the building and/or endanger people and property.
Page 10
Percentage of Efficiency cor- Absorbed power Water flow rate Loss of head cor- Freezing point [°C] glycol rection factor correction factor correction factor rection factor -3.2 0.985 1.02 1.08 -7.8 0.98 0.99 1.05 1.12 -14.1 0.97 0.98 1.10 1.22 -22.3 0.965 0.97 1.14...
Page 11
TO THE EXPANSION SYSTEM Example of recommended connection diagram (non exhaustive) 01.07.2022 11 / 78...
Page 12
1.2.5. General safety rules Before starting any operation on the units, each operator must be fully familiar with the operation of the machine and its controls and have read and understood all the information contained in this manual. The removal and/or handling of any safety device is strictly prohibited. Children and unaccompanied disabled people are not allowed to use the device.
Page 13
Be sure to maintain a posture that does not cause fatigue when installing and maintaining the unit. Also check the weight of any component before handling it. The unit works with the refrigerant R32, included in the list of greenhouse gases (GWP 675) that meet the requirements of EU Regulation No.
Page 14
AHP60-50/70 - Installation, Use and Maintenance 14 / 78 00U07362410-A_EN...
2. DESCRIPTION OF THE EQUIPMENT 2.1. Designations and scope TYNEHAM AHP60: Heat pump comprising a close-coupled heat pump Hot water production system for heating networks or thermodynamic production of domestic hot water. 2.2. Packaging Outdoor unit Model Code TYNEHAM 50...
AHP60-50/70 - Installation, Use and Maintenance 2.4. Technical data 2.4.1. Data sheet for standard units This product is designed to be installed at a maximum altitude of 2000m AHP 60 Measurement TECHNICAL CHARACTERISTICS units 50 kW 70 kW Heat output (1) 24.1 / 50.2 32.9 / 66.8 min./nom.
Page 17
AHP60-50/70 - Installation, Use and Maintenance AHP 60 Measurement TECHNICAL CHARACTERISTICS units 50 kW 70 kW Hydraulic circuit water capacity Max. pressure on water side Hydraulic connections Ø 1 1/2” (DN 40) Hydraulic Minimum volume of water for bottle circuit Maximum power of circulator 1.04 1.35...
Page 18
AHP60-50/70 - Installation, Use and Maintenance 2.4.2. 2.4.2. Electrical data for the unit and auxiliaries Electrical data for the unit and auxiliaries TYNEHAM Heat Pump Con- Unit power supply V/~/Hz 3N~400V-50Hz* V/~/Hz 12/01/1950 trol command circuit Integrated control circuit V/~/Hz 12/01/1950 Power supply to fans V/~/Hz...
Page 19
AHP60-50/70 - Installation, Use and Maintenance 2.4.3.2. Partial load Sound levels refer to units at full load and in conditions guaranteeing a thermal capacity equal to that declared at a temperature of 7°C for an average climate, in accordance with standard EN 14825, in accordance with the provisions of EU regulation 813/2013(dry bulb temperature (wet bulb temperature) of the outside air = 7°C (6°C), water temperature inlet-outlet = 47-55°C).
AHP60-50/70 - Installation, Use and Maintenance 2.5. Description 2.5.1. Models AHP60 50 - 70 kW Sor�e d’eau Entrée d’eau 1754 1110 1920 Left hand side view Right hand side view Front view Figure 1 - Dimensions of the models AHP60 50 - 70 kW Dimensions and weight Models AHP60 50 kW...
Page 21
AHP60-50/70 - Installation, Use and Maintenance In case of maintenance and/or inspection of the compressors, it is necessary to access the inside of the unit by opening the door located on the front side, where the electrical panel is also located. To unlock it, it is necessary to unscrew the fixing screws using a suitable tool and pull it towards you using the handle under the panel.
AHP60-50/70 - Installation, Use and Maintenance 2.6. Operating principle 2.6.1. Production of domestic hot water or heating When the heat pump is operating, other than in the start-up and transition phases, the inlet temperature must not fall below 25°C. A lower value may cause system anomalies, including damage to the compressor.
Page 23
AHP60-50/70 - Installation, Use and Maintenance Water flow rate on the condenser The nominal water flow rate is determined for a temperature difference of 5°C between the inlet and the outlet of the condenser. The maximum authorised flow rate is that with a temperature difference of 3°C whereas the minimum is that with a temperature difference of 8°C in nominal conditions, as shown on the data sheet.
AHP60-50/70 - Installation, Use and Maintenance 3. INSTALLATION The outdoor unit and the Tyneham Heat Control control unit must be installed CAUTION: using the new equipment supplied. 3.1. Lifting and handling Handling must be carried out by qualified personnel, correctly equipped with tools suited to the weight and size of the unit, in compliance with the accident prevention safety rules.
AHP60-50/70 - Installation, Use and Maintenance 3.2. Installation The choice of the position for installation is particularly important insofar as any later movement is a delicate operation requiring the intervention of a qualified person. Comply with the maximum and minimum distances for the outdoor unit, the performance and service life guarantees depend on this.
Page 26
AHP60-50/70 - Installation, Use and Maintenance • The outdoor unit is weatherproof, but avoid installing it in a place where it may be exposed to dirt or heavy water run-off (under a leaking gutter, under a roof, etc.). Avoid installing the unit in places where water is likely to stagnate or fall, for example from gutters.
Page 27
AHP60-50/70 - Installation, Use and Maintenance Industries / risk zones Incinerators Agriculture Paper / Salt Swimming Treatment Type Corrosive product & other Cleaning & fertiliser wood extraction pools plants combustions manufacturers Nitrogen oxides (NOX) Sulphur oxides Oxides (SxOy) Carbon oxides Sulphurs Hydrogen fluoride Volatile gases...
Page 28
AHP60-50/70 - Installation, Use and Maintenance 3.3.2. Installation precautions We recommend that you carry out a noise nuisance risk study. This will have to take into account the residual noise without the heat pump, the data of the machine, the implatation zone, the distance to the measurement point, this list is not exhaustive. The day and night normative noise level requirements are distinct.
Page 29
AHP60-50/70 - Installation, Use and Maintenance 3.3.3. Minimum technical clearances • By following the installation precautions, it is absolutely essential to ensure the following minimum service clearances are respected. • Therefore, avoid placing the appliance under canopies or near plants or walls to avoid air recirculation.
Page 30
• The unit is designed to be installed outdoors. • Installation under a shelter is only permitted for ducted versions (see “G” references in paragraph 2.2.). If the installation has a different version for a ducted installation, contact Hamworthy Heating to exchange the heat pump.
Page 31
Pressure drops that are any greater will not guarantee the declared performance. Manometric head available to the fan Nominal flow rate of fan for ducting MODELS in Pa in mm H TYNEHAM AHP60-50 kW 19555 TYNEHAM AHP60-70 kW 19976 01.07.2022 31 / 78...
The position of the centre of gravity of each heat pump is indicated in the table, with reference to the dimensions indicated in the image. Models A [mm] B [mm] Xa [mm] Yb [mm] TYNEHAM AHP60 1110 1754 50 kW TYNEHAM AHP60 1110 1754...
AHP60-50/70 - Installation, Use and Maintenance Models A [mm] B [mm] C [mm] D [mm] TYNEHAM AHP60 1410 50 kW and 70 kW 3.6. Hydraulic connections 3.6.1. The accessories to be connected to the AHP60 hydraulic station - The hydraulic connections must comply with good engineering practices according to the regulations in force.
Page 34
AHP60-50/70 - Installation, Use and Maintenance A metal filter must be fitted (with a mesh size not exceeding 1000 microns) as well as a T connector on the return pipe of the system labelled "INGRESSO ACQUA" (water inlet). If the flow rate switch is tampered with or modified, or if the metal filter and filter-settler are not fitted to the system, the warranty is immediately void.
Page 35
The adjustment and management of flow rates is the responsibility of the installer/ under installer/operator responsibility and will not be operated by CAUTION: Hamworthy Heating. During commissioning of the system, balancing control will be requested by Hamworthy Heating. Without control, commissioning will be refused.
Page 36
AHP60-50/70 - Installation, Use and Maintenance is being filled for the first time reacts with the equipment materials and quickly disappears. Without refreshing the oxygen through significant contributions of water, the unit might not experience any damage whatsoever. However, it is important to follow the sizing rules and installation guidelines in order to prevent oxygen from continuously flowing into the heating water.
Page 37
AHP60-50/70 - Installation, Use and Maintenance 3.6.6. Connecting water supply Check that the system is stopped, with the general switch in position 0. Add water until the pressure of the hydraulic circuit reaches 2 bar. The P drain valve is an automatic drainer, run the pump to readjust the pressure.
Page 38
AHP60-50/70 - Installation, Use and Maintenance 3.6.6.1. Precautions to take for water filling • Supervise all filling/refilling operations. • Before filling/refilling the system with water, disconnect the power supply to the units. • Filling/refilling the installation must always be carried out under controlled pressure conditions (max.
AHP60-50/70 - Installation, Use and Maintenance The air vent is delivered closed from the factory. It must be opened so that it can CAUTION: evacuate the air. . If there is a water leak, the component must be changed, by unscrewing it INFORMATION: with two wrenches, as shown in the picture below.
Page 40
AHP60-50/70 - Installation, Use and Maintenance 3.7.1. General remarks on electrical connections Check that the electrical power supply complies with the nominal characteristics of the appliance (voltage, phases, frequency) as stated on the data plate located on the side panel of the appliance. The electrical connection must comply with the electrical wiring diagram of the appliance and local and international regulations (fit a main circuit breaker, and differential circuit breakers for each line, and earth installation adequately, etc.).
Page 41
AHP60-50/70 - Installation, Use and Maintenance All of the installation operations must be carried out when the heat pump is stopped, and after disconnecting the electrical power supply. These operations must only be carried out by QUALIFIED PERSONNEL. CAUTION: Remove the cover without removing the cable duct support plate. When the work is complete, refit all of the covers removed with their screws and seals (if present).
Page 42
AHP60-50/70 - Installation, Use and Maintenance 3.7.4. Connecting the control unit See Tyneham Heat Control manual 3.7.5. User terminal The terminal block is located inside the electrical panel. For access, see the instructions. The terminal block must be connected in accordance with the information below. The connections shown below are standard.
Page 43
AHP60-50/70 - Installation, Use and Maintenance Terminal Connection Type input 3-Ph/N/PE, 400 Power supply Connect the earth wire VAC, 50Hz input 3-Ph/N/PE, 400 Power supply connect the neutral wire from the network VAC, 50Hz input 3-Ph/N/PE, 400 Power supply Connect the L1 phase wire from the main power supply VAC, 50Hz input 3-Ph/N/PE, 400 Power supply...
AHP60-50/70 - Installation, Use and Maintenance 4. PRE-REQUISITES BEFORE COMMISSIONING 4.1. Verification before switching on • Check that the electrical and hydraulic diagrams of the installation the machine is connect- ed to are available. • Ensure that the isolation valves of the hydraulic circuits are open. •...
- Check if heating cables of the compressors are powered correctly. 4.3. Commissioning - The heat pump must only be commissioned by Hamworthy Heating commissioning personnel. - If heating is required before the planned commissioning date, back-up generators may be used:...
AHP60-50/70 - Installation, Use and Maintenance 4.6. TYNEHAM user interface navigation * : Only in case of default in progress ** : Only if USB flash drive detected with the right files 48 / 78 00U07362410-A_EN...
AHP60-50/70 - Installation, Use and Maintenance 5. CONTROL INTERFACE 5.1. User interface The unit is equipped with a display underneath a transparent polycarbonate cover with an IP67 protection rating. The interface consists of a variable text part and a series of icons identifying the operation of the appliance as shown in the table below.
AHP60-50/70 - Installation, Use and Maintenance It normally displays the water outlet temperature in tenths of a degree Celsius or the alarm code is displayed if there is at least one alarm in progress. If several alarms are in progress, the first one is displayed, while the second one is displayed after the first one has been reset.
AHP60-50/70 - Installation, Use and Maintenance 5.3. Sensor menu [TP] Access the PSS menu to enter the maintenance technician password “195” and to activate access to a higher level. Once you have fully exited the menus, the password privileges are lost and the password needs to be entered once again. LABEL SENSOR Inlet water temperature...
AHP60-50/70 - Installation, Use and Maintenance 6. TROUBLESHOOTING 6.1. Troubleshooting of failures without error code Problems encountered Cause Solution HMI off with heat pump powered Reverse the cabling between 2 power Power supply phase reversal supply phases Power up the heat pump. Error 495 on Tyneham Heat Pair Tyneham...
Page 53
AHP60-50/70 - Installation, Use and Maintenance Code Description Cause Solution pressure sensor • Check for gas leaks in the refrigeration circuit. detects a pressure that • Check if the alarm occurs when the operating mode is lower than the “low is changed pressure setpoint”...
Page 54
AHP60-50/70 - Installation, Use and Maintenance Code Description Cause Solution • Check that the pressure sensor wiring is not inverted If the compressor has been operating for more than 150 seconds, if the pressure sensor • Check that the compressor inverter board is operating detects that the pressure correctly.
Page 55
AHP60-50/70 - Installation, Use and Maintenance Code Description Cause Solution • Check that compressor discharge sensor DT1 or the NO contact of the Kinv1 switch are connected to the terminals XC -7.1/XC-7.2 correctly Failure of the compressor dischargesensor • Check the Kinv1 switch is working correctly: The DT1 sensor is faulty 1 / intervention of E641...
Page 56
AHP60-50/70 - Installation, Use and Maintenance Code Description Cause Solution • Check that the sensor is securely attached to the terminals XC-8.1 / XC-8.2 Failure of the The EXT1 sensor is E651 external air defective sensor • Check the wiring of the fan fault contact terminals XC-8.2 and XC-9.1 with terminals 11 and 14.
Page 57
AHP60-50/70 - Installation, Use and Maintenance Code Description Cause Solution If the functional diagram connections are all present, Check: • Check if opto-coupler OPT1 is powered, if there is a 12V voltage between the VCC and GND terminals. • Bypass opto-coupler separating compressor...
Page 58
AHP60-50/70 - Installation, Use and Maintenance Code Description Cause Solution If the functional diagram connections are all present, Check: • Check if opto-coupler OPT1 is powered, if there is a 12V voltage between the VCC and GND terminals. • Bypass opto-coupler separating compressor...
AHP60-50/70 - Installation, Use and Maintenance 6.3. Inverter board errors Error shown in the display of the main Error description Possible Causes Solutions control board IPM (Intelligent Power Check if dirt has accumulated Module) temperature Too high ambient temperature in the heatsink protection (100-125°C) Driver over...
Page 60
AHP60-50/70 - Installation, Use and Maintenance Error shown in the display of the main Error description Possible Causes Solutions control board E901 (Inverter card 1) Compressor driver Compressor driver and Main control board or inverer Change the card mismatching and model mismatch model mismatch faulty with the model...
AHP60-50/70 - Installation, Use and Maintenance Error shown in the display of the main Error description Possible Causes Solutions control board E941 (Inverter card 1) PFC converter fault PFC converter fault - Input phase loss - Check the input voltage E942 (Inverter card 2) E951 (Inverter card 1) - Check heatsink temperature...
AHP60-50/70 - Installation, Use and Maintenance 7. MAINTENANCE OF THE OUTDOOR UNIT 7.1. Drainage of the outdoor unit on the water side If the unit has to be completely drained, first close the manual inlet and outlet valves (not supplied) and then disconnect the pipes provided on the outside of the water inlet and outlet so that the liquid contained in the unit can be evacuated (to make this easier, we suggest installing two drain taps on the outside of the water inlet and outlet between the unit and the manual valves).
Page 63
AHP60-50/70 - Installation, Use and Maintenance Operation even for a short period of time, with a water temperature below +5°C is not covered by the warranty. Before switching the appliance back CAUTION: on after prolonged stoppage, ensure that the temperature of the water- glycol mix is at least +5°C or more.
Page 64
AHP60-50/70 - Installation, Use and Maintenance The compulsory activities must be performed by an authorised customer service in order for the corresponding certificate to be issued. Failure to respect these activities will make the warranty void and could considerably shorten the life of your product. OPERATIONS month months...
AHP60-50/70 - Installation, Use and Maintenance 7.4.1. CLEANING THE EVAPORATOR Follow the instructions below to clean correctly: a) Remove any surface dirt. Deposits such as leaves, fibres, etc. must be removed using a vacuum cleaner (use a brush or a spray, carefully avoiding rubbing with metal or harsh parts). If compressed air is to be used, ensure that the air stream is kept pointing perpendicularly to the surface of the battery to avoid bending the aluminium fins.
AHP60-50/70 - Installation, Use and Maintenance 7.6.1. Installation drain Function used to drain the system, using the circulator at maximum speed. To enable this function: - Control in OFF mode - Access the parameters PRG => PSS => PRG => (enter password 195) - Hold down the UP and DOWN keys at the same time for 3 seconds.
AHP60-50/70 - Installation, Use and Maintenance 7.8. Heavy maintenance work Some maintenance work may involve the replacement of broken components, which can be heavy. Below is a list of components and the approximate weight of each part (take into account that residual oil, liquid gas or water can increase the weight).
AHP60-50/70 - Installation, Use and Maintenance 7.9. “Maintenance” check list ■ Before starting any work on equipment containing flammable refrigerant, safety checks must be performed to minimise the risk of ignition. Take the following steps before working on the cooling system: Measure Performed Comment...
Page 69
Only replace defective components with original parts. ■ Replace the components according to the instructions in the manual. If necessary, call on Hamworthy Heating’s technical intervention department. Carry out the following checks: ■ The refrigerant load must not exceed that allowed for the installation room.
Page 70
■ Only components suitable for a flammable atmosphere may be powered up in the vicinity of such an atmosphere. ■ Use only suitable original parts or components approved by Hamworthy. Other components may cause the refrigerant to ignite if leaked. Wiring ■...
Page 71
AHP60-50/70 - Installation, Use and Maintenance Measure Performed Comment ■ The refrigerant detector must be suitable for the R32 refrigerant to be detected. ■ The refrigerant detector must not contain any potential source of ignition. ■ Calibrate the refrigerant detector to suit the refrigerant used. Set the response threshold to <...
Page 72
AHP60-50/70 - Installation, Use and Maintenance Measure Performed Comment Topping up the refrigerant Filling with refrigerant In addition to the usual filling procedure, the following requirements must be satisfied: - make sure that the filling valve is not used for different refrigerants.
Page 73
AHP60-50/70 - Installation, Use and Maintenance j) If the recycling bottles are filled as required and the process is completed, ensure that the bottles and equipment are immediately removed from the facility and that all shut-off valves are closed. k) Recovered refrigerant must not be used to fill other systems until it has been purified and examined.
The manufacturer or its importer/distributor is available to answer any request for further information. Hamworthy Heating has signed up to the Eco-systems service which collects, recycles and cleans our used electrical equipment, according to the highest environmental requirements.
Page 75
AHP60-50/70 - Installation, Use and Maintenance Incorrect disposal of the appliance may cause serious environmental damage and endanger people. We therefore recommend that you contact authorised persons with appropriate technical training obtained through courses recognised by the competent authorities. The same precautions described in the previous paragraphs must be followed. Special attention must be paid to the disposal of the refrigerant gas.
AHP60-50/70 - Installation, Use and Maintenance 9. ANNEX A - DATA FOR PRODUCTS ≤ 70KW Product reference Trademark Hamworthy Model TYNEHAM AHP-60-50 TYNEHAM AHP-60-70 Heat pump Air-Water Nominal power (average / cool / hot climatic conditions) 44 / 50 / 51 49 / 60 / 63 Rated heat output (35°C)
Page 77
AHP60-50/70 - Installation, Use and Maintenance Product reference Trademark Hamworthy Model TYNEHAM AHP-60-50 TYNEHAM AHP-60-70 Heat pump Air-Water Nominal power (average / cool / hot climatic conditions) 44 / 51/ 49 51 / 63 / 65 Rated heat output (55°C)
Page 78
Wessex House, New Fields Business Park, Stinford Road, Poole, Dorset BH17 0NF Telephone: 01202 662500 Fax: 01202 662522 Email: aftersales@hamworthy-heating.com Website: www.hamworthy-heating.com Hamworthy reserves the right to make changes and improvements which may necessitate alteration to the specification without prior notice.