CM800/CM900
Emergency Call Signaling System
Installation & Operating Instructions
Contents

System Installation ............................................................. 1

Installation Procedure ......................................................1

Equipment Locations .......................................................1

Wiring Installation ...........................................................2
Housing Installation ........................................................2
Wire Checkout .................................................................2
Connections Checkout ....................................................2
System Operating Instructions ......................................... 7
Cm800, Cm900 Annunciators .........................................7
Sf154 Emergency Call Station .........................................7
Li381 Corridor Light .........................................................7
Li382, Li382Led Corridor Lights .....................................7
Li118B, Li123B Corridor Lights .......................................7
Be005, Be007 Corridor Bells ............................................7
Figure 1—Master Panel Housing Chart and
Wall Cut-Out Details ...............................................3
Figure 2—Ring and Back Box for SF117 series, SF118
series and SF154 Emergency Call Stations .............3
Figure 3—Ring and Back Box for IR019 & IR019B
Tone Speakers, and LI118B, LI123B, LI381,
LI382 & LI382LED Corridor Lights .........................3
Figure 4—PK2019A Tone Volume Shunt Settings .................3
Figure 5—Emergency Call Hook-Up Diagram
with SF117/2 series, SF118 series &
SF154 Emergency Switches, and
LI381 & LI118B Corridor Lights ..............................4
Figure 6—Emergency Call Hook-Up Diagram with
SF117/4 series Continuous Duty Door Release,
LI381 Corridor Light, LI123B Corridor Light
with Buzzer, and BE005 Corridor Bell ......................5
Figure 7—Emergency Call Hook-Up Diagram with
SF117/2 series Continuous Duty Door Release,
LI381 Corridor Light, Smoke Detector,
and BE007 Corridor Bell ..........................................6
Figure 8—Connection Diagram for Parallel
CM800 Panels .........................................................6
ALPHA COMMUNICATIONS
Toll-Free Technical Line: 1-800-666-4800 • Phone: (631) 777-5500 • Fax: (631) 777-5599
Website: www.AlphaCommunications.com • Email: info@alphacommunications.com
• Read the following instructions concerning system equip-
ment, and determine installation methods before proceed-
ing.
• Determine equipment locations.
• Install wiring.
• Install housings.
• Check wires.
• Connect equipment.
• Check connections.
• Apply power.
• Check system operation.
CM800, CM900 Annunciator: Locate CM800 and CM900
Annunciators within easy reach of operating personnel.
Permitted operating temperature of 10°C–30°C must not be
exceeded.
SF117 series, SF118 series, SF154 Emergency Call Stations:
Locate emergency stations where convenient for operation.
Avoid areas where direct contact with water may occur. The
SF117 series and SF118 series include a 6' long pull cord,
permitting installation high enough to provide easy opera-
tion by the staff and by seated or prone patients. The SF154
is operated by means of a push button located on the station.
IR019, IR019B Remote Annunciator Tone Speakers:Locate
annunciator tone speakers as needed and where convenient
for operation. Location must provide for unobstructed
visibility of the tone-off indicator (IR019B).
LI118B, LI123B, LI381, LI382, LI382LED Corridor Lights:
Locate corridor lights in the corridor above or beside the
door of the associated rooms. Location must provide unob-
structed visibility of the corridor light in both directions.
PK2019, PK2019A Control Unit: The PK2019 or PK2019A
may be surface mounted adjacent to the SS106, if necessary.
If remotely located, cable run from PK2019/A to CM800/
CM900 must not exceed 100'.
PK601A Power Supply: Surface mount the PK601A adjacent
to the SS106 and PK2019/A.
PK612A DC Flasher: Surface mount the PK612A adjacent to
the SS106 and PK2019/A.
®
• 42 Central Drive • Farmingdale, NY 11735-1202
Section C
Rev. 13 - 5/2011
System Installation
Installation Procedure
Equipment Locations
IL514

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TekTone CM800 and is the answer not in the manual?

Questions and answers

Summary of Contents for Alpha Communications TekTone CM800

  • Page 1 PK612A DC Flasher: Surface mount the PK612A adjacent to Figure 8—Connection Diagram for Parallel CM800 Panels ............6 the SS106 and PK2019/A. ALPHA COMMUNICATIONS ® • 42 Central Drive • Farmingdale, NY 11735-1202 Toll-Free Technical Line: 1-800-666-4800 • Phone: (631) 777-5500 • Fax: (631) 777-5599...
  • Page 2 BE005/BE007 Corridor Bells: Locate BE005 and BE007 Cor- IR019, IR019B Remote Annunciator Tone Speakers: Install ridor Bells in corridor above door height. Location in corridor double gang ring (or double gang ring and double gang box) will be determined by the number of bells required on each as shown in Figure 3 for each tone speaker station.
  • Page 3 Figure 1—Master Panel Housing Chart and Wall Cut-Out Details Housing Wall Opening Flush Surface Width (B) Height OH202 OH302 8.5" 16.25" OH203 OH303 12.5" 16.25" 16" OH204 OH304 16.5" 16.25" OH205 OH305 20.5" 16.25" 3.75" 4" min. Finished Wall 16.25" 16.25"...
  • Page 4 Page 4 • IL514 CM800/CM900 Emergency Call System Manual Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.
  • Page 5 Figure 6—Emergency Call Hook-Up Diagram with SF117/4 series Continuous Duty Door Release, LI381 Corridor Light, LI123B Corridor Light with Buzzer, and BE005 Corridor Bell RECTIFIER RECTIFIER (See NOTE 9) (See NOTE 9) TONE SPEAKER SS106 24 VAC TRANSFORMER TO ADDITIONAL (See NOTE 1) EMERGENCY SWITCHES...
  • Page 6 Figure 7—Emergency Call Hook-Up Diagram with SF117/2 series PK601A Continuous Duty Door Release, LI381 Corridor Light, Smoke Detector, and BE007 Corridor Bell SS106 16 VAC TRANSFORMER (SEE NOTE) TO ADDITIONAL EMERGENCY SWITCHES Notes: 117 VAC 1. Use 24 VAC connections on SS106 PK2019/A transformer.
  • Page 7 System Operating Instructions IR019, IR019B Remote Annunciator Tone Speakers Emergency Calls: Emergency calls are indicated by a rapidly System operators must read the following operating pulsating audible tone. The audible tone signal can be instructions concerning system equipment and terms used in silenced by pressing the tone-off switch.