Summary of Contents for Axiall Accu-Tab 2000 P Series
Page 1
DANGER: DO NOT MIX CHEMICALS! The Accu-Tab® chlorinator is designed for use with Axiall approved tablets only. Do not use Cal-Hypo tablets with stabilized chlorine or bromine products, or other sanitizing chemicals. Fire or explosion could result. Rev 02-10-21...
Page 2
The feeder is designed for use ONLY with Axiall AccuTab ® SI tablets to utilize the Axiall erosion feeder technology that erodes only the bottom layer of tablets on the sieve plate, while keeping tablets above the sieve plate dry and ready for use. Tablets other than Axiall ®...
Page 3
Installation and Start-Up Instructions A. Uncrate, remove from pallet, and check for damage that may have occurred during shipping. If damage occurred during shipment, file a claim with the shipping company. B. If the Weight Scale option was purchased, remove the blocking under the scale that was used for protection during shipment.
Page 4
Check all connections for leaks. ® Q. To begin chlorinating, remove the chlorinator lid and fill the Chlorinator with Axiall Accu-Tab tablets. R. NOTE: Add only the amount of tablets that will be consumed in 5-7 days. Tablets in the chlorinator longer than 5-7 days will pick up moisture and bridging may occur.
Page 5
Models 2075 P and 2150 P Schematic Model 2075 P shown Model 2075 Using Accu® - Tab SI Tablets For Industrial use only Flow Rate, GPM...
Page 6
Model 2150 Using Accu® - Tab SI Tablets For Industrial use only Flow Rate, GPM...
Page 9
Operating and Maintenance Instructions Clean the Check Valve at least every 4-6 months, to remove debris or scale. Disassemble Float Valve and clean every 6 months Cleaning the chlorination system Over time, and depending on the water chemical characteristics, some calcium scale may build up in the system.
Page 10
If contactor pulled in, and voltage on output side of contactor, pump motor bad. 6. Check for low level in solution tank. D. Contact Axiall Technical Service (855-934-3570) for assistance. E. Float Valve was installed in a lower flow position. Float valve may be adjusted for higher flow.
Page 11
System; (ii) you, at your cost, promptly return the System or defective part to such location as may be specified by Axiall; and, (iii) only Axiall’s Accu-Tab® SI calcium hypochlorite tablets are used in the System.