Schuch nD8611 L02 W Series Operating Instructions Manual page 5

Explosion-proof led-emergency light fitting with built-in battery
Table of Contents

Advertisement

Connection per terminal: Ampacity: 16 A max. (At maximum current load, a cross section of
Possible number of
light fittings per circuit
breaker*:
Rated luminous flux:
Emergency battery:
Dimensions:
(all measures in mm)
Equipotential bonding:
10/2022
L-01510-4-09
2.5 mm² is required)
Screw terminal: Clamping range: 1 x 0.75 - 2.5 mm² (solid core or stranded)
Required stripping length: 7 – 7.5 mm
Torque of terminal screw: 0.5 Nm
Screwless terminal: Clamping range: 2 x 0.75 - 2.5 mm² (solid core or
Req. stripping length: 8 mm (conductor 0.75 - 1.0 mm²)
Type
nD8611 L02/. W
*) Typical values; possible deviations depending on make, cable impedance and temperature
100%
1-hour version: Type 8620 (spare-part-no. 90222 9026)
3,6 V, 2,2 Ah (battery pack composed of 3 NiMh-cells)
3-hour version: Type 8621 (spare-part-no. 90222 9027)
6 V, 2,2 Ah (battery pack composed of 5 NiMh-cells)
Special versions with the possibility for cable looping:
Connection terminal for equipotential bonding on the outside of the light
fitting
Clamping range: 4 mm² max.
Torque of terminal screw: 2 Nm max.
5
1 x 1,5 - 2,5 mm² (flexible)
2 x 1.5 - 2.5 mm² (flexible)
9 mm (conductor 1.5 - 2.5 mm²)
B 10 A
B 16 A
81
130
stranded)
C 10 A
C 16 A
135
221