Summary of Contents for LPS AC Series
Page 3
270V AC (Line to Neutral) Maximum Continuous Operating Voltage U Residual Current I < 1mA Short-circuit Current Rating I 25kA SCCR Operating & Storage Temperatures -40°C to 70°C w All earth terminal of LPS® products must be connected to Power Earth. w All connecting leads must be as short and as straight as possible. w Ensure that the phase conductors are NOT connected to N (Neutral) of the SPD, otherwise the SPD will damage. w For new power system, ensure that the SPD is isolated during power system testing. w Failure to install the SPD before the Earth Leakage Circuit Breaker (ELCB) may cause nuisance tripping (except for transient protected RCCB and ELR). w It i s n ot a dvisable t o r un t he s ystem w ithout S PD. F or o ptimal p erformance, SPD should always be installed together with new equipment.