DANIMPORTANT: Read and understand the following instructions COMPLETELY before installing!! Information and specifications outlined in this manual in effect at the time of printing of this manual. ECR International, Inc. reserves the right to discontinue, change specifications or system design at any time without notice and without incurring any obligation, whatsoever.
Become familiar with symbols identifying potential hazards� This manual is intended to familiarize the installer and user of the Argo AZ Series Zone Valve Controls with their installation and operation to assure normal trouble-free This is the safety alert symbol. Symbol alerts you to operation�...
INSTALLATION MANUAL AND OPERATING INSTRUCTIONS AZ CIRCUIT BOARD The diagram below represents Argo AZ-5 Zone Valve Control. AZ-3 has similar connections� Class 2 Transformer Terminals (24 Vac) X-X Indicator LED (indicates both Green Indicator LED Class 2 X-X end switches (indicates zone is Thermostat are closed)
INSTALLATION MANUAL AND OPERATING INSTRUCTIONS Electrical Specifications & Wiring AZ Sequence of Operation • THe control will scan all TT terminals looking for a WARNING call for heat from any thermostat� Electrical shock hazard. Disconnect power before • When a call for heat is detected the green TT LED installing or servicing.
INSTALLATION MANUAL AND OPERATING INSTRUCTIONS AZ Control w/DPM-2 Outdoor Reset Control DPM-2 Outdoor Reset Control is designed to raise or lower the temperature of the boiler supply water based on a proportionate drop or rise in temperature at the outside sensor�...
INSTALLATION MANUAL AND OPERATING INSTRUCTIONS AZ Control W/Power Robbing Thermostat Argo AZ control should work well with all standard and most programmable setback thermostats. In the event the programmable thermostat you are using causes the control board relays to chatter, you will require an external 24V power supply (transformer) and an Argo IR882 Isolation Relay.
Transformer 40 VA (AZ-3) Transformer 75 VA (AZ-5) Technical Support For technical support on this and all Argo products, please contact ECR International Technical Service at 1-800-325-5479. Please have your model number available when calling. Information Needed When Calling Model Number...