Core IO 40 Multi Manual innon.com TABLE OF CONTENTS INTRODUCTION This Core IO model HARDWARE Wiring Power Supply Wiring Digital Inputs (DI) Wiring Universal Inputs (UI) Wiring Universal Outputs (UO) - Including Use as Digital Input Wiring Digital Outputs (DO)
In many installations, having cost-effective, robust, and simple hardware becomes a key factor in winning a project. The Core range provides the perfect solution to meet these criteria. Innon have collaborated with Atimus, a company with a wealth of experience in the field, and are proud to...
Core IO 40 Multi Manual innon.com This Core IO model The CR-IO-40MULTI-RS and the CR-IO-40MULTI-IP modules come with 8 universal inputs, 8 universal outputs, 16 digital inputs and 8 relay outputs. The CR-IO-40MULTI-RS only comes with the RS485 port, while the CR-IO-40MULTI-IP comes with both RS485 and IP ports.
Core IO 40 Multi Manual innon.com Wiring Digital Inputs (DI) Wiring Digital Outputs (DO) Digital Input Relay out Wiring Universal Inputs (UI) 0/4-20mA 0/2-10v Passive Sensor/Resistor Input Thermistor/ Resistor 1.0 4/10/2021 Get help at http://innon.com/support Learn more at http://know.innon.com...
Core IO 40 Multi Manual innon.com Wiring Universal Outputs (UO) - Including Use as Digital Input Digital Input 0-10V Output 0-10V actuator output example 12V DC Relay Wiring the RS485 network Some useful links to our knowledge base website: How to wire an RS485 network https://know.innon.com/howtowire-non-optoisolated...
Core IO 40 Multi Manual innon.com Front LED Panel The LEDs in the front panel can be used to get direct feedback on the status of the I/Os of Core IO and more general information. Below are some tables that will help decode each LED behaviour –...
Page 8
Core IO 40 Multi Manual innon.com UO 1 to 8 Input/Output Mode Conditions LED Status BUS and PWR Conditions LED Status 1.0 4/10/2021 Get help at http://innon.com/support Learn more at http://know.innon.com...
Core IO 40 Multi Manual innon.com CONFIGURE I/O Digital Inputs Digital Inputs can have a clean/volt free contact connected to Core IO to read its open/closed status. Each digital input can be configured to be either: • Digital Input direct •...
Core IO 40 Multi Manual innon.com Universal Inputs Universal Inputs are used to connect analogue signal inputs to Core IO. A variety of sensors and signals can be connected to a Universal Input. In terms of active signals, both voltage (0-10V, 2-10V) and current (0-20mA, 4-20mA) are supported directly. As for passive...
Core IO 40 Multi Manual innon.com Universal Outputs (Digital Inputs) Universal Outputs are primarily used as analogue outputs (0-10V, 2-10V). They can also be configured in “digital output” mode, which is just sending “0V” at a low state, “10V” at high state with 20mA max current.
Page 12
Core IO 40 Multi Manual innon.com The pulse input will, in fact count 2 totalizers as follows – • The first one is continuous; it will increase by one unit for every pulse received and will keep counting until a reset command is sent over Modbus •...
Core IO 40 Multi Manual innon.com CONFIGURING THE DEVICE Fixed Settings The RS485 Modbus Slave communication have some settings that are fixed as follows – • 8-bit data length • 1 stop bit • Parity NONE DIP Switch Setting The DIP switches are used to configure the other RS485 settings and the Modbus slave address thus–...
Page 14
Core IO 40 Multi Manual innon.com Please check our dedicated knowledge base article available at the website http://know.innon.com where we explain in detail the use of the termination and bias resistors on RS485 networks. The Modbus ID and baud rate DIP switches are configured as follows –...
Page 15
Core IO 40 Multi Manual innon.com Slave address DIP switch settings, continued. 1.0 4/10/2021 Get help at http://innon.com/support Learn more at http://know.innon.com...
Core IO 40 Multi Manual innon.com Bluetooth and Android App Core IO has built-in Bluetooth which allows the Core Settings app running on an Android device to configure the IP settings and I/O. Please download the app from Google Play – search for “core settings”...
Page 17
Core IO 40 Multi Manual innon.com Once connected, you will land on the I/O setup screen, where you can set up the I/O and read input and output current values – Use the drop-down arrows in the “I/O Mode” column to select the type of input or output type by clicking on the respective radio button –...
Core IO 40 Multi Manual innon.com Ethernet Port and Web Server Configuration (IP version only) For the IP models of Core IO, a standard RJ45 socket is available to be used for: • Modbus TCP (slave) communication • Web server access to configure the device The IP models still provide access on the RS485 port for Modbus RTU (slave) communication on these models, so the user can decide which one to use to connect the BEMS to Core IO.
Core IO 40 Multi Manual innon.com Watchdog Watchdog is an internal function of Core IO used to check if a master is online to control the I/O, and if it is not, it can position the outputs to a pre-configured (default) pattern. This could be useful to keep a critical plant running in the event of a Modbus comms or main BEMS controller failure.
Core IO 40 Multi Manual innon.com BEMS POINT LISTS Modbus Register Types Unless otherwise stated in the tables, all I/O point values/statuses and settings are held as Holding Register Modbus data type and use a single register (16 bit) to represent either an Integer (Int, range 0 - 65535) or Signed Integer (Sint, range -32768 –...
Core IO 40 Multi Manual innon.com Input and Output Scaling The holding registers associated with inputs and outputs can be scaled as follows – • Thermistors and Resistor types – precision is fixed to 1 decimal place, divide by 10 to get actual temperature reading, i.e.
Core IO 40 Multi Manual innon.com Modbus Register Tables General Points Details Stored Type Range Decimal Name 1.0 4/10/2021 Get help at http://innon.com/support Learn more at http://know.innon.com...
Page 23
Core IO 40 Multi Manual innon.com Digital Output Points Details Decimal Name Stored Type Range 1.0 4/10/2021 Get help at http://innon.com/support Learn more at http://know.innon.com...
Page 24
Core IO 40 Multi Manual innon.com Universal Output Points Details Decimal Name Stored Type Range UO 1 default UO 2 default Watchdog fall back value in case of connection lost. UO 3 default Universal Output status (digital output mode): Min register...
Page 25
Core IO 40 Multi Manual innon.com UO 1 max UO 2 max UO 3 max UO 4 max -10000... Maximum value for Universal Outputs configured as Analog 10000 UO 5 max Outputs UO 6 max UO 7 max UO 8 max UO 1 offset...
Page 26
Core IO 40 Multi Manual innon.com 0...4294967 32 bit long, total counter value (totalizer) (pulse input mode) UO 4 counter (totalizer) 32 bit long, counter value for the running timer 0...4294967 UO 4 counter (timer) (pulse input mode) Running timer in minutes. Will reset once "counter timer set"...
Page 27
Core IO 40 Multi Manual innon.com Digital Input Points Decimal Name Details Stored Type Range 5001 1389 DI 1 mode 5002 138A DI 2 mode 5003 138B DI 3 mode 5004 138C DI 4 mode 5005 138D DI 5 mode...
Page 28
Core IO 40 Multi Manual innon.com 32 bit long, counter value for the running timer 0...4294967 1123 DI 1 counter (timer) (pulse input mode) Running timer in minutes. Will reset once "counter timer set" 1125 DI 1 counter timer 0...14400 reached and start again Timer duration configuration in minutes...
Page 29
Core IO 40 Multi Manual innon.com 32 bit long, counter value for the running timer 0...4294967 1723 DI 7 counter (timer) (pulse input mode) Running timer in minutes. Will reset once "counter timer set" 1725 DI 7 counter timer 0...14400 reached and start again Timer duration configuration in minutes...
Page 30
Core IO 40 Multi Manual innon.com 0...4294967 2321 DI 13 counter (totalizer) 32 bit long, total counter value (totalizer) (pulse input mode) 32 bit long, counter value for the running timer 0...4294967 2323 DI 13 counter (timer) (pulse input mode) Running timer in minutes.
Core IO 40 Multi Manual innon.com TECHNICAL DATA Drawings Part number: CR-IO-40MULTI-RS Part number: CR-IO-40MULTI-IP 1.0 4/10/2021 Get help at http://innon.com/support Learn more at http://know.innon.com...
Core IO 40 Multi Manual innon.com Specifications P o w e r s u p p l y 24 Vac +10%/-15% 50 Hz, 24 Vdc +10%/-15% Current draw – 80mA min, 200mA max 16 x Digital Inputs (volt free) D i g i t a l I n p u t s...
Core IO 40 Multi Manual innon.com Guidelines for Disposal • The appliance (or the product) must be disposed of separately in accordance with the local waste disposal legislation in force. • Do not dispose of the product as municipal waste; it must be disposed of through specialist waste disposal centres.