Operating instruction CAN bus Repeater Firmware V2.0L Firmware V2.0L - Doku-Version V2.0 - Current to March 2021...
Page 2
All rights to any use whatever, utilisation, further development, forwarding and creation of copies remain with the Eckelmann AG company. In particular, neither the contract partners of Eckelmann AG nor other users have the right to distribute or market the IT programs/program parts or modified or edited versions without express written permission.
Technical safety information ................... 3 Function of the CAN bus Repeater ................. 4 Sample applications ........................... 5 Installation and Commissioning of the CAN Bus Repeater ........6 Installation and connection to the CAN bus ..................6 Wire assignment for male connectors in the CAN bus ..............7 Commissioning ...........................
1 Technical safety information 1. Commissioning and operation of the device may only be performed by qualified personnel. "Qualified personnel" as defined by this technical safety information means persons who have the authorisation to start up, earth and designate devices, systems and electric circuits in accordance with security technology standards.
A maximum of 2 CAN bus repeaters can be employed in an E*LDS system, for further details see the introductory chapter in the E*LDS documentation. CAN bus Repeater (order No. KGLZCANREP) Interfaces 2 x CAN bus in accordance with ISO/DIS 11 898 Voltage supply The CAN bus repeater is powered by an external 24 V DC power pack, order No.
3 Installation and Commissioning of the CAN Bus Repeater 3.1 Installation and connection to the CAN bus Before commissioning, the CAN bus repeater must first be connected to the first CAN bus segment via the front COMBICON plug. The second CAN Bus segment is then connected to the top connections of the CAN bus repeater.
3.2 Wire assignment for male connectors in the CAN bus COMBICON- plug Wire/ e.g. System centre, CAN bus CAN bus Repeater Comments colour 00, VS 3010, WR 300 Connect shield (SHLD) to SHLD SHLD earthing clamps, see chapter 3.1. CAN- G (COMBICON, front) green GND (top terminal)
3.3 Commissioning The commissioning of the CAN bus repeater consists of the following steps: 1. Connect the CAN bus repeater to the first and second CAN bus circuits, see chapter 3. 2. Attach the CAN bus repeater to the power supply 24 V DC. 3.4 Indication of the Operating Status The CAN bus repeater is equipped with a display element consisting of a yellow and a green LED with the following functions:...
4 Specifications CAN bus Repeater 4.1 Electrical data Technical data CAN bus repeater Order No. KGLZCANREP Physical interface CAN Bus in accordance with ISO/DIS 11 898 Transmission rate 50 kBit/s Voltage supply 24 V DC, max. 100 mA, separate power supply required, order No.