The Armstrong Monitoring Corporation will repair or replace components that prove to be defective in the opinion of AMC. Any equipment deemed to be defective by the user should be returned to The Armstrong Monitoring Corporation for evaluation (see product return below).
1.5 MODIFICATIONS AND SUBSTITUTIONS Due to an ongoing development program, AMC reserves the right to substitute components and change specifications at any time without incurring any obligations. 1.6 GLOSSARY Act Delay The delay in seconds between the gas concentration reaching an alarm setpoint, and the corresponding alarm level activating.
2 PRODUCT SPECIFICATIONS 2.1 AMC-1BXX MONITOR System System Warranty Period 2 Years Power Supply Requirement 120 VAC, 60 Hz, 53 VA Relays (2) DPDT, 250 VAC, 10 A Operating Temperature -4° to 104°F (-20° to 40° C) Operating Pressure 0.9 to 1.1 atm...
<5ppm Calibration Kit Part Number AMC-C1-FM1 Recommended Calibration Gas 100ppm CO Gas Flow Rate 0.176 cfm (0.5L/min) 2.2.2 Carbon Monoxide/Nitrogen Dioxide (AMC-1BVC Monitor) Gas Type CARBON MONOXIDE (CO) NITROGEN DIOXIDE (NO Sensor Module Order Number AMC-SM-VCA01 Detection Range 0-100ppm CO...
In addition, each Monitor features alarm / system status indicators, audible feedback, 2 relays, 2 analog outputs and color-coded connection terminal blocks, as listed and described herein. NOTE: The AMC-1BXX is a variant of our UTx platform. As such many of the menu items directly reference the parent product.
3.1 EXTERNAL VIEW Figure 3-1: External View Enclosure and Lid Assembly, UV Stabilized Polycarbonate, 11.750" L x 9.980" W X 5.460" (300 x Enclosure: 250 x 140 mm) Digital Display: Displays gas concentration & Status information Network Status LED: Not applicable to 1BXX series The Sensor Status LED will show the same error code that is being communicated by the Sensor Module(s) or display the highest priority error (if multiple errors codes are being communicated to it Alarm Status LED:...
3.2 INTERNAL VIEW Figure 3-2: Internal View Analog Output 1: Terminal Block for signal output 1 Analog Output 2: Terminal Block for signal output 2 2A Fuse: Device level input protection Sensor Module: Contains sensor elements for hazardous gas detection External Relays: Connection for alarm/warning system 120 VAC IN:...
AMC-FM1 3.3.1 UTx Calibration Kit The Calibration Kit, as shown below, consists of the AMC-FM1 Calibration Adaptor that secures the calibration gas hose to the front of the Sensor Module along with hose to connect to the calibration gas cylinder regulator.
4 INSTALLATION The installation of the AMC-1BXX Gas Monitor is very important as the operational quality is a direct result of the quality of the installation. The following sections provide guidelines for installation; location and mounting, wiring, and cable selection.
4.2 WIRING 4.2.1 POWER SUPPLY The monitor operates on 120 VAC, 60 Hz. The power supply connections are made at the power terminal block located inside the monitor. All power and grounding connections to equipment must be made in accordance with applicable electrical and building codes.
The AMC-RAM3 provides a remote alarm indication when employed with monitors such as the AMC Gas Monitor 1B. Each RAM3 has a red strobe light to provide a visual indicator of an alarm condition and remains active until the alarm is cleared. The Audio alert is provided by a buzzer which emits a 2900hz tone at in excess of 90 dB(A) at a distance of 24 inches.
5 OPERATION This section describes how the functionalities of the AMC-1BXX Gas Monitor are operated and performed. Please consult the operation and initial configuration chapters below before attempting to use or calibrate the Gas Monitor. 5.1 STATUS LEDS Refer to Section 3.1 for LED location and descriptions.
Page 19
LED States Network Alarm Status Sensor Module Display Screen Message • Real-Time Clock Not Applicable Solid Magenta Solid Green Not indicated on Display Screen (RTC) disabled or uninitialized Alarms Warning threshold Flashing Green Solid Yellow Solid Yellow Not indicated on Display reached (.5 sec.
5.2 MENU OVERVIEW Note a Menu Flow Chart is available in section 9. 5.2.1 Menu System – Normal Operation Upon startup, a brief splash screen is shown on the display which includes the Armstrong Monitoring Corp’s logo and the current version of the firmware. After a couple of seconds, the display will update to display the main info screen as shown below.
ighlighted ac ground indicates hich sensor is currentl failed. in normal video mode. availa le on 1 onl . ailed ensor etails pertaining to the failed sensor ar on ono ide ighlighted ac ground indicates hich sensor is currentl failed. in inverse video mode.
A AR ighlighted ac ground indicates hich sensor is currentl selected ith latched rela s. AT in normal video mode. availa le on 1 onl . etails pertaining to the selected sensor hich currentl has its rela s in ress E TER to RE EA E atched mode.
5.2.5 Menu System – Detailed Status Screen To access the detailed status for each sensor, press and hold the DOWN button until the following screen appears. a el indicates hich sensor is currentl selected urrent operational status for the selected sensor tatus ormal um er of da s since last cali ration for the selected sensor...
Menu System – Main Service Menu 5.2.7 Once the correct password is entered, the main service menu is displayed as shown in the following diagram. ighlighted ac ground indicates hich service menu is selected availa le on 1 onl . The name of the selected service menu.
The service menus remains unlocked for a programmed timeout period (set to 5 minutes). Within that period, the service menus can be re-enabled by long pressing the ENTER button. If the timeout period is allowed to expire, the password entry screen will appear prior to accessing the service menus.
Page 26
indo indo serves as a la el onl . Edit the indo filter value one digit at a time using the uttons. ress E TER to advance the cursor to the ne t digit. ress E TER hen the last digit is highlighted to save the value. onte t sensitive help Enter To Adv ursor When the...
Page 27
When the ENTER button is pressed, the confirmation screen (described previously) is displayed. If ‘Yes’ is selected, the edit value is persisted as the new value for the Sim Enable flag. Otherwise, the edit value is rejected. In either case, the menu returns to the Override sub-menu menu with the ‘...
5.2.10 Menu System – Transmitter Service Menu If the ‘ T ’ menu item is activated from the main service menu via the ENTER button, then UTx service menu will appear on the display as shown in the following diagram. ensors Alarms Rela s...
5.2.10.1 TRANSMITTER SENSOR SETTINGS rom the T service menu, selecting ‘ ensors’ ill update the displa to sho the follo ing su - menu. availa le on 1 onl . E it onte t sensitive help for the currentl highlighted menu item Edit DOWN buttons can be used to navigate the list of menus for the sensors sub-...
Table 5-6: Sensor Alarm Configuration Menu Item Description Alarm SP 1-3 Select this menu item to edit the alarm setpoints for the selected alarm (1-3) Alarm Hyst Select this menu item to edit the alarm hysteresis. This hysteresis value is applied to all alarm setpoints.
Zero uff Zero uff serves as a la el onl . Edit the alarm h steresis setpoint value one digit at a time using the uttons. ress E TER to advance the cursor to the ne t digit. ress E TER hen the last digit is highlighted to save the value.
5.2.10.2 TRANSMITTER ALARM SETTINGS rom the T service menu, selecting ‘Alarms’ ill update the displa to sho the follo ing su - menu. Alarm 1 Alarm Alarm 3 onte t sensitive help for the currentl highlighted menu item Edit Alarm DOWN buttons can be used to navigate the list of menus for the Alarms sub-menu.
Table 5-9: Transmitter Alarm Sub-Menu Settings Menu Item Description elect this menu item to edit the alarm’s ena le state Enable elect this menu item to edit the alarm’s source i.e. from the availa le sensors Source elect this menu item to edit the alarm’s input value Input elect this menu item to edit the alarm’s setpoint Level...
f ‘ nput’ is activated from the alarm su -menu, then the display will be updated to show the following editing screen. nput nput serves as a la el onl . 15m Avg The input can e selected from a list of options using the uttons to c cle et een each option.
Table 5-11: Alarm Setpoint Options Menu Item Description Alarm SP 1 Alarm setpoint 1 from the selected source Alarm SP 2 Alarm setpoint 2 from the selected source Alarm SP 3 Alarm setpoint 3 from the selected source When the ENTER button is pressed, the screen will update to display the confirmation dialog (described previously).
Page 36
Otherwise, the relay will not activate. NOTE: Relays 3 through 5 are unavailable in the AMC-1BXX Series. Any attempt to toggle the state of a checkbox associated with an unavailable relay will be ignored.
5.2.10.3 TRANSMITTER RELAY SETTINGS rom the T service menu, selecting ‘Rela s’ ill update the displa to sho the following sub- menu. Rela 1 Rela Rela 3 onte t sensitive help Edit Rela 1 DOWN buttons can be used to navigate the list of menus for the Alarms sub-menu. The following table outlines all the menu items from the Alarms sub-menu: Table 5-13: Relay Menu Menu Item...
f ‘ olarit ’ is activated from the rela su -menu, then the display will be updated to show the following editing screen. olarit olarit serves as a la el onl . ormal The polarit can e selected from a list of options using the uttons to c cle et een each option.
5.2.10.4 BUZZER From the UT service menu, selecting ‘Buzzer’ ill update the displa to sho the follo ing: uzzer uzzer serves as a la el onl . The uzzer activation level can e selected from a list of options using the uttons to c cle et een each option.
5.3 CALIBRATION Sensors naturally degrade over time, losing about 2% of their sensitivity per month. Over time a sensor will start to underreport gas concentrations, meaning that a calibration is necessary to maintain a safe environment. When the Sensor Module(s) are due for calibration the respective LED will blink cyan-yellow as opposed to its usual green to be able to see at a glance which sensor(s) is(are) overdue.
5.3.3 PRE BUMP TEST Before calibration, an “As Found” bump test) is usually performed to ensure each sensor is in working order and returning reasonable responses. The bump test involves applying a test gas to the sensor. However, sensors such as CO have a recovery time measured in multiple hours. As a result, the calibration routine would find a zero at a concentration that is not the true background concentration, should the sensor not have sufficient recovery time.
5.3.4 CALIBRATION PROCEDURE 5.3.4.1 Calibration Menu Navigate to the Service Menu and select the sensor to be calibrated. If the ENTER button is pressed then the following menu is shown. This menu is common to all sensors therefore selecting any sensor will produce the same menu. A A Ti al As ound indo...
ac ground ac ground serves as a la el onl . Edit the current ac ground one digit at a time using the uttons. ress E TER to advance the cursor to the ne t digit. ress E TER hen the last digit is highlighted to save the value. Enter To Adv ursor onte t sensitive help pan evel...
When the calibration procedure completes its cycle, the result will either be a PASSED or FAILED with calibration results as shown by the following two images. Zero evel ase evel pan evel rig. pan of rig. ressing the E TER utton returns the displa to the A A Ti al menu item ress Enter to Ac Zero evel...
Page 45
Caution: In the case of repeated CO Gas Calibrations performed in quick succession (i.e. less than 30 minutes apart) first follow the routine outlined in section 5.3.3, Pre Bump Test. Then use the Background value provided by the unit during ADAPTiCAL startup. A CO sensor element has a tendency to increase its background zero offset after each span gassing.
6.1 GENERAL The AMC-1BXX should be cleaned (brushed or wiped) as required, depending on the rate of accumulation of any dust or dirt. To avoid sensor damage, the unit MUST NOT be submerged, hosed or splashed with any liquids.
Figure 6-1: Disconnect Sensor Module 6.3.1.2 INSTALL SENSOR MODULE Rotate the replacement Sensor Module so the tab aligns as shown. Push and turn clockwise until the Sensor module is secured. Attach the IPC Cable to the top connector on the Sensor Module. Figure 6-2: Installing Sensor Module...
6.4 VERIFICATION OF OPERATION Verification of operation should be performed at least once every 6 months. For highly demanding applications more frequent verification is recommended. 6.4.1 SIMULATION OF GAS LEVELS The Monitor Service Menu allows the current gas reading to be overridden by a simulated gas level.
im as im as serves as a la el onl . Edit the simulated gas value one digit at a time using the uttons. ress E TER to advance the cursor to the ne t digit. ress E TER hen the last digit is highlighted to save the value. onte t sensitive help Enter to Adv ursor When the...
7 TROUBLESHOOTING Table 7-1 Troubleshooting Table Symptom Possible Cause How to Verify Corrective Action Network LED is not Network noise Network LED Remove any wires flashing .5 second flashing internal to Bus periodically flashes connected to A 1 and Green Module due to wires Red or Green at 1 B 1 Terminals on Bus...
Page 51
Symptom Possible How to Verify Corrective Action Cause Buzzer or Bad Connection No continuity between COM Re-seat wiring connections for Relays not to Buzzer or and NO Bus Module buzzer and relay coils. activating. Relays. terminals. Check UTx-> Buzzer menu Configuration No continuity between Relay parameters.
8 SENSOR MODULE DEFAULT SETTINGS Table 8-1: Default Alarm Settings Short SM Code Long Gas Name Set Point 1 Set Point 2 Set Point 3 Name Carbon Monoxide Carbon Monoxide Nitrogen Dioxide Table 8-2: Default Sensor Module Settings Short Engineering Zero SM Code Long Gas Name...
9 MENU FLOW DIAGRAMS ress utton to access nfo creen uttons to select sensor, press and hold utton to access ensor etails creen Timeout of 1 ress and hold seconds ill utton to result in a return get ass ord to the ain nfo creen...
rom ensor uttons to navigate ervice list and press utton to select u enu, Reset to reset the ensor odule or E it to return to the ain ervice Enter the ac ground as level one digit at a elect A A T al time using the uttons.
rom T ervice 1 91A availa le on 1 ee ensor elect ensors onfiguration uttons to navigate iagram list and press utton to elect ensor odule to access select u enu, ensor onfiguration u Reset to reset the odule or E it to return to the ervice elect Alarms...
rom T ervice enu ensors election elect Alarm elect Alarm Edit the alarm setpoint, uttons to navigate h steresis or zero uffering list and press values one digit at a time elect Alarm utton to using the select u uttons. ress or E it to return to utton to advance to ne t...
rom T ervice enu Alarms election uttons to navigate list and press utton to elect Alarm select u or E it to return to ain ervice sing the uttons to elect Ena le toggle et een Ena le isa le. ress utton to select the desired response.
Need help?
Do you have a question about the AMC-1BXX and is the answer not in the manual?
Questions and answers