NEMA Rating The UNIPLAY front bezel is NEMA 4 rated. When installed properly in a NEMA 4 panel, the NEMA 4 rating of the panel will not be compromised. This means that fl uids will not enter the panel during wash downs.
Contact your local authorities to determine which codes apply. Power Requirements The UNIPLAY is powered by d.c. power only. The specifi ed voltage range is 24±20% Volts d.c. This insures compatibility with most controller d.c. systems. The power conditioning circuitry inside the unit is accomplished by a switching power supply. The peak starting current can be as high as 2A.
Supply Voltage Condition Do not power the UNIPLAY and inductive d.c. loads, or input circuitry to the controller, with the same power supply. The 24 Vd.c. output from some controllers may not have enough current to power the UNIPLAY.
The communication ports are located on the underside of the UNIPLAY. COM1, COM2, USB host, USB client and SD card ports are not used. Ethernet: A 1:1 or cross-over Ethernet cable may be used to connect the UNIPLAY screen to a Motion Coordinator or Ethernet switch. Speaker: An external speaker / buzzer may be used for greater keypress feedback.
Page 6
USING THE UNIPLAY: UNIPLAY HMI’s work with the Trio 4xx Motion Coordinator range. Motion Perfect 3 is used to create operator HMI screens which are transferred to the UNIPLAY HMI by the Motion Coordinator at runtime. Trio recommend using a USB powered switch...
Com1 RS485, Com3 RS485, Com3 RS232 Fuse Com1 RS232, Com2 RS232 Power connector Ethernet port VESA 75mm screw holes USB Host port Line out USB Client port SD card slot UNIPLAY 7 R2mm 138mm CUTOUT DIMENSIONS 192mm 146.35mm 42.55mm 200.35mm...