This guide is designed to simplify the commissioning process by detailing the initial parameters required to Parameters - Installed Devices properly setup a Preferred Instruments Feedwater Cen- ter - Transfer Pump/Surge Tank Control. This guide is to Parameters - Scope be used in conjunction with the Installation and Operation Manual, SDI-JC-FWC-ND-OIT.
QUICK START QUIDE INITIAL PARAMETER SETUP The Preferred Instruments Feedwater Center - Transfer Pump/ MAIN MENU Surge Tank Control is designed to be field adjustable for multiple > 1. TUNING - applications. In order to customize to your installation some pre- 2.
NOT USED SURGE TANK LEVEL CONTROL If the system being set up has a control valve on the Surge VALVE Tank, change ‘NOT USED’ to “INSTAL’D’ This enables the Level Control Valve output. Preferred Instruments - Feedwater Center Model JC-FWC-ND-OIT...
CR F Condensate Return Temperature in °F A10 CR FLO Condensate Return Flow in GPM A12 TP VSD Transfer Pump VSD in Hz A13 DEMAND Demand (it is not recommended to change this value) Preferred Instruments - Feedwater Center Model JC-FWC-ND-OIT...
Page 6
MODBUS ADDRESSING MODBUS ADDRESSING NUMBERS MODBUS: The following information applies to JC-FWC-ND-OIT Feedwater Center-Transfer Pump/Surge Tank Control. NOTE: MODBUS addresses below are for the OIT version, this does not include points that are used on the touch screen. Default: Options:...
Surge Tank Level Low Alarm Set point 40041 Surge Tank Level Low Alarm Time Delay Secs 40042 Surge Tank Level High Alarm Set point 66.6 40043 Surge Tank Level High Alarm Time Delay Secs 40044 40045 40046 Preferred Instruments - Feedwater Center...
Page 8
40079 40080 40081 Surge Tank Make Up water Valve 40082 Transfer Pump 1 Speed 40083 Transfer Pump 2 Speed 40084 Transfer Pump 3 Speed 40085 40086 40087 40088 40089 40090 40091 Make Up Water Flow Preferred Instruments - Feedwater Center...
Page 10
FALSE TRUE 00030 Has Surge Tank Level NOT USED INSTAL’D 00031 00032 00033 spare 00034 spare 00035 spare 00036 spare 00037 spare 00038 spare 00039 spare 00040 Common Alarm Alarm Normal 00041 00042 00043 00044 Preferred Instruments - Feedwater Center...
Page 11
Normal 00078 Transfer Pump 1 On Start Stop 00079 Transfer Pump 2 On Start Stop 00080 Transfer Pump 3 On Start Stop 00081 00082 00083 00084 00085 00086 Disable All Enabled Disabled 00087 00088 00089 Preferred Instruments - Feedwater Center...
Page 12
Transfer Pump 4 Lead Is Lead Not Lead 00110 Transfer Pump 4 Fault Alarm Normal 00111 Transfer Pump 4 Active Start Stop 00112 Transfer Pump 4 On Start Stop 00113 Transfer Pump 4 Start Start Stop Preferred Instruments - Feedwater Center...
HOA- ROUT/2 HO.2.1 Transfer Pump 1 Start Circuit HOA- ROUT/2 HO.2.2 Transfer Pump 2 Start Circuit HOA- ROUT/2 HO.2.3 Transfer Pump 3 Start Circuit HOA- ROUT/2 HO.2.4 Transfer Pump 4 Start Circuit HOA- ROUT/2 HO.2.5 Preferred Instruments - Feedwater Center...
Page 14
Make Up Water Flow AIN/6 AI.6.2 Make Up Water Pressure AIN/6 AI.6.3 Surge Tank Temperature AIN/6 AI.6.4 Condensate Return Temperature AIN/6 AI.6.5 Condensate Retun Flow AIN/6 AI.6.6 Spare AIN/6 AI.6.7 Spare AIN/6 AI.6.8 Backup Pump Discharge Pressure Preferred Instruments - Feedwater Center...
Page 15
NOTES: Preferred Instruments - Feedwater Center Model JC-FWC-ND-OIT...
REVISION HISTORY Description FIRST ISSUE (02/13/2019) SDI-FWC-ND-OIT-QS Revision 0.0 02/13/2019 Preferred Instruments - Feedwater Center Model JC-FWC-ND-OIT...